TVR-EX 

FOR THE CONTROL OF VARIABLE AIR VOLUME FLOWS IN POTENTIALLY EXPLOSIVE ATMOSPHERES (ATEX)

Circular VAV terminal units for variable air volume systems, approved and certified for potentially explosive atmospheres (ATEX)

  • ATEX-compliant construction and parts
  • Suitable for the control of supply or extract air as well as for differential pressure control

  • Suitable for the control of supply or extract air as well as for differential pressurecontrol
  • Electronic or pneumatic control components
  • Closed blade air leakage to EN 1751, up to class 4
  • Casing air leakage to EN 1751, class C

  • Optional equipment and accessories

  • Spring return actuator
  • Auxiliary switch with adjustable switching points for capturing the end positions
  • Updating order code
    Save configuration
    Calculate price
    Updating technical data
    • Media
    Specification text:
    Updating specification text
    Show complete text Hide complete text
    Initialize order code

    General information

    Application

    • Circular EXCONTROL VAV terminal units of Type TVR-Ex for the precise supply air or extract air flow control in variable air volume systems
    • For use in potentially explosive atmospheres (ATEX)
    • Closed-loop volume flow control using an external power supply
    • Electronic or pneumatic volume flow control
    • Shut-off by means of switching (equipment supplied by others)

    Special features

    • ATEX mark and certification
    • ATEX equipment group II, approved for use in zones 1 and 2; electronic control also for zones 21 and 22
    • The volume flow rate can later be measured and adjusted on site; configuration is possible using personal computer software

    Nominal sizes

    125, 160, 200, 250, 315, 400

    Classification

    • Electronic control: Equipment group II

    Attachments

    • Electronic control
    • Pneumatic control

    Variants

    • Actuator with auxiliary switch for capturing the end positions
    • Spring return actuator

    Technical data

    • Nominal sizes: 125 to 400 mm
    • Volume flow rate range: 15 to 1680 l/s or 54 to 6048 m³/h
    • Volume flow rate control range: approx. 15 – 100 % of thenominal volume flow rate
    • Maximum differential pressure: 1000 Pa
    • Operating temperature: 10 to 50 °C

    Useful additions

    • Circular silencer CA or CAH (for Germany and Switzerland) or CAH (for EMEA) for demanding acoustic requirements

    Construction features

    • Construction and materials comply with the EU directive and guidelines for use in potentially explosive atmospheres (ATEX)
    • Zones 1 and 2 (atmosphere: gases):II 2 G c II T5: 10 °C - 50°C and T6: 10 °C - 60 °C
    • Zones 21 and 22 (atmosphere: dusts):II 2 D c II 80 °C Pneumatic control: Equipment group II
    • Spigot with lip seal, for circular connecting ducts to EN 1506 or EN 13180

    Materials and surfaces

    • Casing and inner duct made of galvanised sheet steel
    • Zones 1 and 2 (atmosphere: gases):II 2 G c II T5: 10 °C - 50°C and T6: 10 °C - 60 °C

    Construction

    • Galvanised sheet steel
    • P1: Inner duct powder-coated RAL 7001, silver grey
    • A2: Inner duct in stainless steel

    Parts and characteristics

    • Ready-to-commission unit which consists of mechanical parts and control components
    • Averaging differential pressure sensor for volume flow rate measurement
    • Damper blade
    • Connection for equipotential bonding
    • Cable glands suitable for use in potentially explosive atmospheres
    • ATEX-compliant control components, factory mounted and complete with wiring and tubing
    • Aerodynamic functional testing on a special test rig before shipping of each unit
    • Set-up data is given on a label affixed to the unit
    • High control accuracy (even with upstream bend R = 1D)
    • Control components made of die cast aluminium (pneumatic control: plastic)
    • Plastic bearings
    • Damper blade of stainless steel with thermoplastic elastomer seal TPE
    • Differential pressure sensor made of aluminium
    • P1: Inner duct powder-coated
    • A2: Inner duct in stainless steel

    Standards and guidelines

    • Directive 2014/34/EU: Equipment and protective systems intended for use in potentially explosive atmospheres

    Maintenance

    • Maintenance-free as construction and materials are not subject to wear
    • Zero point correction of the static differential pressure transducer should be carried out once per year (recommendation, with electronic control)

    Commissioning

    • The controller parameters are factory set
    • Adjustments may be required as part of commissioning (by others)

    TECHNICAL INFORMATION

    • ‌ Function
    • ‌ TECHNICAL DATA
    • Specification text
    • ORDER CODE

    The VAV terminal unit is fitted with a differential pressure sensor for measuring the volume flow rate.

    The control components (attachments) include a differential pressure transducer that transforms the differential pressure (effective pressure) into an electric signal, a controller, and an actuator.

    For most applications, the setpoint value comes from a room temperature controller which is installed outside of the potentially explosive atmosphere.

    The controller compares the actual value with the setpoint value and alters the control signal of the damper actuator if there is a difference between the two values.

    The connections for the supply voltage and for the voltage signals are made in a terminal box that is suitable for use in potentially explosive atmospheres.


    Nominal sizes125 – 400 mm
    Volume flow rate range15 – 1680 l/s or 54 – 6048 m³/h
    Volume flow rate control rangeApprox. 15 to 100 % of the nominal volume flow rate
    Maximum differential pressure1000 Pa
    Operating temperature10 to 50 °C


     


     Electronic control with attachment S1S, S1F, S1X or S1Y

    S1SSchischek: Controller ExReg-V-300-A + actuator ExMax-5.10-CY
    S1FSchischek: Controller ExReg-V-300-A + spring return actuator ExMax-5.10-CYF
    S1XSchischek: Controller ExReg-V-300-A + actuator ExMax-5.10-CY + accessories ExSwitch and ExBox
    S1YSchischek: Controller ExReg-V-300-A + spring return actuator ExMax-5.10-CYF + accessories ExSwitch and ExBox
    Supply voltage24 V AC + 15% (24.0 ... 27.6 V AC), 50/60 Hz
    Supply voltage24 V DC + 15% (24.0 ... 27.6 V DC)
    IEC protection classIII (protective extra-low voltage)
    EC conformityATEX to 2014/34/EU, EMC to 2014/30/EU, low voltage to 2014/35/EU
    The information given here is just to give you an idea. 

    For the latest information on the electronic attachments please refer to the technical data in the manufacturer's product documentation:
    Schischek GmbH, 90579 Langenzenn, Germany, www.schischek.com, info@schischek.com
    For the ExReg-V volume flow controller see the documentation from version V04 of 3 June 2022



    Electronic control with attachment TES, TEF, TEX or TEY
    Components

    TESTROX controller TCU3 +

    Schischek components: differential pressure transducer ExCos-P, actuator ExMax-5.10-Y
    TEFTROX: Controller TCU3 +

    Schischek components: differential pressure transducer ExCos-P, spring return actuator ExMax-5.10-YF
    TEXTROX: Controller TCU3 +

    Schischek components: differential pressure transducer ExCos-P + actuator ExMax-5.10-Y + accessories ExSwitch and ExBox
    TEYTROX: Controller TCU3 +

    Schischek components: differential pressure transducer ExCos-P + spring return actuator ExMax-5.10-YF + accessories ExSwitch and ExBox


     


     

    Controller TCU3 (TROX)

    Supply voltage24 V AC ±15% (20.4 .. 27.6 V), 50/60 Hz
    Supply voltage24 V DC ±15% (20.4 .. 27.6 V)
    Supply voltageOptional: 230 V AC mains supply (only with expansion module EM-TRF)
    Power rating8 VA
    Protection levelIP 20
    IEC protection classIII (protective extra-low voltage) if 24 V AC/DC is used
    InstallationIn closed rooms, outside of Ex zones (the TCU3 has to be installed away from TVR-Ex)
    EC conformityEMC to 2014/30/EU


     


     


    Differential pressure transducer (Schischek)

    Supply voltage24 V AC ±20% (19.2 .. 28.8 V), 50/60 Hz
    Supply voltage24 V DC ±20% (19.2 .. 28.8 V)
    IEC protection classI (earthed)
    Protection levelIP 66
    EC conformityATEX to 2014/34/EU, EMC to 2014/30/EU


     


     


    Actuator/spring return actuator (Schischek)

    Supply voltage24... 240 V AC/DC, ±10%, self-adjusting, 50 – 60 Hz ±20%
    Supply voltageWe recommend a mains connection for the actuator
    Power ratingBe sure to see the additional information in the Schischek documentation
    IEC protection classI (earthed)
    Protection levelIP 66
    EC conformityATEX to 2014/34/EU, EMC to 2014/30/EU, low voltage to 2014/35/EU

    The information given here is just to give you an idea.
    For the latest information on the electronic attachments please refer to the technical data in the manufacturer's product documentation:
    Schischek GmbH, 90579 Langenzenn, Germany, www.schischek.com, info@schischek.com


     


     


     Pneumatic

    Operating pressure1.3 bar ± 0.1 bar
    Air consumption – volume flow control50 ln/h
    Air consumption – pressure and volume flow cascade100 ln/h
    Control pressure0.2 – 1.0 bar
    Maximum pressure1.5 bar
    Compressed airCompressed air for instruments, free of oil, water and dust
    Protection levelIP 42


    VAV terminal units for variable and constant air volume systems in potentially explosive atmospheres, suitable for supply or extract air, available in 6 nominal sizes.

    High control accuracy (even with upstream bend R = 1D). Ready-to-commission unit which consists of the mechanical parts, the electronic control components, and parts for equipotential bonding and for use in potentially explosive atmospheres. Each unit contains an averaging differential pressure sensor for volume flow rate measurement and a damper blade.

    Factory mounted control components complete with wiring and tubing.

    Differential pressure sensor with 3 mm measuring holes (resistant to dust and pollution)

    Spigot with lip seal, for circular connecting ducts to EN 1506 or EN 13180.

    Closed blade air leakage to EN 1751, class 4 (nominal sizes 125 and 160, class 3).

    Casing air leakage to EN 1751, class C.

    Special features

    • ATEX mark and certification
    • ATEX equipment group II, approved for use in zones 1 and 2; electronic control also for zones 21 and 22
    • The volume flow rate can later be measured and adjusted on site; configuration is possible using personal computer software
    • A2: Inner duct in stainless steel

      Construction

    • Galvanised sheet steel
    • P1: Inner duct powder-coated, silver grey (RAL 7001)
    • A2: Inner duct in stainless steel

      Technical data

    • Nominal sizes: 125 to 400 mm
    • Volume flow rate range: 15 to 1680 l/s or 54 to 6048 m³/h
    • Volume flow rate control range: approx. 15 – 100% of thenominal volume flow rate
    • Maximum differential pressure: 1000 Pa

      Attachments

      Variable volume flow control with electronic controller to connect an external control signal; actual value signal can be integrated into the central BMS.
    • Supply voltage 24 V AC/DC (controller/differential pressure transducer)
    • Supply voltage 24 V AC/DC (actuator for attachment S1*)
    • Supply voltage 230 V AC (actuator for attachment TE*)
    • Signal voltages 0 – 10 V DC
    • The actual value signal relates to the nominal volume flow rate so that commissioning and subsequent adjustment are simplified
    • Volume flow rate control range: approx. 15 – 100% of thenominal volume flow rate
    • Actuator with adjustable running time, 7.5 – 120 s

      Materials and surfaces

    • Casing and inner duct made of galvanised sheet steel
    • Control components made of die cast aluminium (pneumatic control: plastic)
    • Plastic bearings
    • Damper blade of stainless steel with thermoplastic elastomer seal TPE
    • Differential pressure sensor made of aluminium
    • P1: Inner duct powder-coated

      Sizing data

    • qv [m³/h]
    • Δpst [Pa]Air-regenerated noise
    • LPA [dB(A)]Case-radiated noise
    • LPA [dB(A)]

    TVR-Ex with ATEX control component Universal
    TVR-ExP1/125/S1F/V0/200 – 400 [m³/h]/NO
    ||||||||
    12345678
    1 Type
    TVR-Ex
    VAV terminal unit for use in potentially explosive atmospheres

    2 Material
    No entry: galvanised sheet steel
    P1 Inner duct powder-coated, silver grey (RAL 7001)
    A2 Inner duct in stainless steel

    3 Nominal size [mm]
    125, 160, 200, 250, 315, 400

    4 Attachments (control components)

    Electronic control
    S1S ExReg controller and actuator
    S1F ExReg controller and spring return actuator
    S1X ExReg controller, actuator and auxiliary switch
    S1Y ExReg controller, spring return actuator and auxiliary switch

    5 Operating mode
    V
    Variable operation (adjustable setpoint value range)

    6 Signal voltage range
    For the actual and setpoint value signals
    0 0 – 10 V DC
    2 2 – 10 V DC

    7 Operating values for factory setting
    Volume flow rate [m³/h or l/s]
    qᵥmin – qᵥmax

    8 Damper blade position
    Only with spring return actuators (S1F and S1Y)
    NO Power off to open (Normally Open)
    NC Power off to close (Normally Closed)

    Order example: TVR-Ex-P1/125/S1F/V0/200-400[m³/h]/NO
    TypeTVR-Ex
    MaterialInner duct powder-coated, silver grey (RAL 7001)
    Nominal size [mm]125
    Attachments (control components)ExReg controller and spring return actuator
    Operating modeVariable operation (adjustable setpoint value range)
    Signal voltage range0 – 10 V DC
    Operating values for factory setting200 – 400 [m³/h]
    Damper blade positionPower off to open (Normally Open)



    TVR-Ex with ATEX control component based on TCU3
    TVR-ExP1/160/TEF/ECE0/M/200 – 400 [m3/h]/NO
    |||||||||
    123456789
    1 Type
    TVR-Ex
    VAV terminal unit for use in potentially explosive atmospheres

    2 Material
    No entry: galvanised sheet steel
    P1 Inner duct powder-coated, silver grey (RAL 7001)
    A2 Inner duct in stainless steel

    3 Nominal size [mm]
    125, 160, 200, 250, 315, 400

    4 Attachments (control components)

    Electronic control (controller outside of the Ex zone)
    TES TCU3 controller and actuator
    TEF TCU3 controller and spring return actuator
    TEX TCU3 controller, actuator and auxiliary switch
    TEY TCU3 controller, spring return actuator and auxiliary switch

    5 Equipment function
    Single operation
    SC Single controller – supply air (Supply Controller)
    EC Single controller – extract air (Extract Controller)

    6 External volume flow rate default setting
    E0
    Variable, signal voltage range 0 – 10 V DC
    E2 Variable, signal voltage range 2 – 10 V DC
    2P 2 switching steps (for one switch contact, by others)
    3P 3 switching steps (for two switch contacts, by others)
    F Constant value mode, one setpoint value (no external switch contact)

    7 Expansion modules
    Option 1: Power supply
    No entry: 24 V AC/DC
    T With EM-TRF for 230 V AC mains supply
    U With EM-TRF-USV (including battery pack) for uninterruptible 230 V AC power supply (UPS)

    Option 2: Digital communication interface
    No entry: without digital communication interface
    B With EM-BAC-MOD for BACnet MS/TP
    M With EM-BAC-MOD for Modbus RTU
    I With EM-IP for BACnet IP, Modbus IP and web server
    R With EM-IP (including real time clock, RTC) for BACnet IP, Modbus IP and web server

    8 Operating values for factory setting
    Volume flow rate [m3/h or l/s]

    Depends on external volume flow rate setting
    E0: qᵥmin – qᵥmax
    E2: qᵥmin – qᵥmax
    2P: qᵥ1/qᵥ2
    3P: qᵥ1/qᵥ2/qᵥ3
    F: qᵥ1

    9 Damper blade position
    Only with spring return actuators (TEF and TEY)
    NO Power off to open (Normally Open)
    NC Power off to close (Normally Closed) 


    Order example: TVR-Ex-P1/160/TEF/EC-E0/M/200-400[m3/h]/NO

    TypeTVR-Ex
    MaterialInner duct powder-coated, silver grey (RAL 7001)
    Nominal size [mm]160
    Attachments (control components)TCU3 controller installed outside of the Ex zone (away from the terminal unit)
    ActuatorSpring return actuator
    Equipment functionSingle controller – extract air (Extract Controller)
    External volume flow rate settingVariable, signal voltage range 0 – 10 V DC
    Expansion modules24 V AC/DC power supply, EM-BAC-MOD for Modbus RTU communication interface
    Operating values for factory setting200 – 400 [m3/h]
    Damper blade positionPower off to open (Normally Open)



    TVR-Ex with pneumatic attachments
    TVR-ExP1/125/PG5/V/200 – 400 [m³/h]/NO
    | | | | | | |
    1 2 3 4 5 6 7
    1 Type
    TVR-Ex
    VAV terminal unit for use in potentially explosive atmospheres

    2 Material
    No entry: galvanised sheet steel
    P1 Inner duct powder-coated, silver grey (RAL 7001)
    A2 Inner duct in stainless steel

    3 Nominal size [mm]
    125, 160, 200, 250, 315, 400

    4 Attachments (control components)

    Pneumatic control
    PG5 Volume flow controller with actuator
    PJ5 Pressure and volume flow cascade (±20 Pa)
    PL5 Pressure and volume flow cascade (±50 Pa)

    5 Operating mode
    V
    Variable operation (adjustable setpoint value range)

    6 Operating values for factory setting
    Volume flow rate [m3/h or l/s]

    For attachment PG5
    Volume flow rate qᵥmin – qᵥmax

    For attachments PJ5 and PL5
    Pressure and volume flow cascade qᵥmin – qᵥmax / Δpset

    7 Damper blade position
    Pneumatic actuators
    NO Pressure off to open (Normally Open)
    NC Pressure off to close (Normally Closed)


    Order example: TVR-Ex-P1/125/PG5/V/200-400[m³/h]/NO

    TypeTVR-Ex
    MaterialInner duct powder-coated, silver grey (RAL 7001)
    Nominal size [mm]125
    Attachments (control components)Volume flow controller with actuator
    Operating modeVariable operation (adjustable setpoint value range)
    Operating values for factory setting200 – 400 [m3/h]
    Damper blade positionPower off to open (Normally Open)

    Downloads

    product information

    certificates

    operation manuals

    production {"X-Frame-Options"=>"SAMEORIGIN", "X-XSS-Protection"=>"1; mode=block", "X-Content-Type-Options"=>"nosniff", "X-Download-Options"=>"noopen", "X-Permitted-Cross-Domain-Policies"=>"none", "Referrer-Policy"=>"strict-origin-when-cross-origin", "Strict-Transport-Security"=>"max-age=31536000; includeSubDomains", "Content-Type"=>"text/html; charset=utf-8"}

    Share page

    Recommend this page

    Recommend this page by sending a link by mail.

    Fields marked with an (*) are required fields.

    Share page

    Thank you for your recommendation!

    Your recommendation has been sent and should arrive shortly.

    Contact

    We are here for you

    Please specify your message and type of request
    Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

    Fields marked with an (*) are required fields.

    Contact

    Thank you for your message!

    Your message is send and will be processed shortly.
    Our department for Service-Requests will contact you asap.
    For general question regarding products or services you can also call:
    Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

    Contact

    We are here for you

    Please specify your message and type of request
    Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

    Attachment (max. 10MB)

    Fields marked with an (*) are required fields.

    Contact

    Thank you for your message!

    Your message is send and will be processed shortly.
    Our department for Service-Requests will contact you asap.
    For general question regarding products or services you can also call:
    Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265