Compact controller XS0 for TVE and TVE-Q
Modbus_XM0png Bild

Bus interface Modbus RTU

XS0-J6_gc_04svg Bild

Volume flow controller – static transducer

XS0_img_01png.png

Control component for type TVE

TVE-Q_-P1_img_02psd.png
VAV control unit variant TVE-Q-P1 (powder-coated)

Control component for type TVE-Q

XS0_img_02psd.png
Modbus_XM0png Bild
XS0-J6_gc_04svg Bild
XS0_img_01png.png
TVE-Q_-P1_img_02psd.png

XS0

CONTROL COMPONENT WITH STATIC TRANSDUCER AND MODBUS RTU INTERFACE

Compact device for VAV terminal unit TVE and TVE-Q

  • Controller, static differential pressure transducer and actuator in one casing
  • Use in ventilation and air conditioning systems, for clean and contaminated air
  • Simple terminal connection, no additional junction boxes needed
  • Volume flow rates qvmin and qvmax are pre-set at the factory and saved in the controller as variable parameters
  • High data transparency via standardised bus communication Modbus RTU, RS485
  • Setpoint specifications, override controls, parameter setting via Modbus register
  • Integrated display for volume flow rate display, operating status display and setting of operating parameters
  • Service access for manual setting devices and PC software

Product successfully added to cart

General information 

Application

  • All-in-one control devices for VAV terminal units types TVE and TVE-Q
  • Static differential pressure transducer, controller electronics and actuator combined in one casing
  • For clean and contaminated air in ventilation and air conditioning systems:
    • E.g. in the extract air area with dust, fluff, sticky or moist components
    • Application examples: Extract air from changing rooms and shower areas as well as hospital bedrooms, production facilities and corridor areas - e.g. in schools
  • Various control options based on corresponding setpoint specification
  • Room temperature controller, management and control equipment (MCE), air quality controller and others control the variable volume flow regulation by specifying setpoint values via communication interface or analogue signal
  • Override control for activating qvmin, qvmax, shut-off, open position via Modbus register or switch or relay possible (depending on interface configuration)
  • The actual volume flow rate is available as a network data point or as a linear voltage signal
  • The damper blade position is available as a network data point


Control strategy

  • The volume flow controller works independently of the duct pressure
  • Pressure fluctuations do not cause any permanent volume flow rate deviations
  • A dead zone (hysteresis), within which the damper blade is not moved, ensures stable regulation
  • Volume flow range for the control component is factory-set (qvmin: minimum volume flow rate, qvmax: maximum volume flow rate)
  • Operating parameters are defined in the order code and parameterised at the factory


Operating modes

Modbus (M):

  • Setpoint specification via Modbus register

Analogue - variable operation (V):

  • Setpoint specification via analogue interface, signal voltage range corresponds to qvmin – qvmax

Analogue - fixed value operation (F):

  • No setpoint signal required, setpoint value corresponds to qvmin


Interface

Communication interface

  • Modbus RTU, RS485, see Modbus register list for data points

Analogue interface with adjustable signal voltage range

  • Analogue signal for volume flow setpoint value
  • Analogue signal for actual volume flow rate (factory setting)
  • Alternatively: analogue signal for damper position (on-site conversion required)

Note

  • Interface type according to order code detail Operating mode parameterised at the factory, on-site conversion is possible


Signal voltage ranges

When using the analogue interface:

  • 0 – 10 V DC
  • 2 – 10 V DC


Parts and characteristics

  • Transducer with static measurement principle
  • Overload-proof actuator
  • Connections terminals with cover
  • Display and control elements for easy menu navigation
  • Menu navigation allows for adjusting operating parameters and communication interface
  • Service interface


Construction

  • TR0VM-024T-10l-DS10-MB
  • Only for types TVE and TVE-Q


Commissioning

  • As the volume flow rates are factory-set, the control units have to be installed at the specified locations only
  • Analogue interface: ready for use after installation and wiring
  • Modbus interface: additional commissioning steps required
  • Operating parameters can be customised by the client (via display, adjustment device, PC software or via Modbus register)


Useful additions

  • Adjustment device type GUIV3-M (order code AT-VAV-G3)
  • PC software

Technical information

Function, Technical data, Specification text, Order code

  • FUNCTION
  • TECHNICAL DATA
  • SPECIFICATION TEXT
  • ORDER CODE
XS0_dia_01ai.png

1 Differential pressure transducer
2 Actuator
3 Volume flow controller
4 Setpoint value via BACnet, Modbus or analogue signal
5 Shaft with effective pressure channel

Volume flow controllers are characterised by a closed control loop for controlling the volume flow, i.e. measuring - comparing - adjusting. The volume flow rate is obtained by measuring a differential pressure. This is done via a differential pressure sensor. The integrated differential pressure transducer converts the differential pressure into a voltage signal. The actual volume flow value is available as a data point and voltage signal. Due to factory adjustment, 10 V DC always corresponds to the nominal flow rate (qvnom). The volume flow setpoint is specified by a higher-level controller (e.g. room temperature controller, air quality controller, MCE). Variable volume flow control can be set between qvmin and qvmax. The controller compares the volume flow setpoint with the current actual value and adjusts the internal actuator, according to the control deviation. It is possible to override the room temperature control by override control, e.g. by a shut-off.

Compact controller for VAV terminal units

Part number

Type of installation component

VAV terminal units

A00000082304

TR0VM-024T-10l-DS10-MB

TVE, TVE-Q


Compact controller TR0VM-024T-10I-DS10-MB

Type of measurement/installation orientation

static measuring principle, position-independent

Supply voltage (AC)

24 V AC, ± 20 %, 50/60 Hz

Supply voltage (DC)

24 V DC ± 20 %


Power rating (AC)

TVE NW 100 - 160: maximum 4 VA

TVE NW 200 - 400: maximum 6 VA TVE-Q up to height 200: maximum 4 VA

TVE-Q from height 300: maximum 6 VA


Power rating (DC)

TVE NW 100 - 160: maximum 2.5 W

TVE NW 200 - 400: maximum 3 W

TVE-Q up to height 200: maximum 2.5 W

TVE-Q from height 300: maximum 3 W

Power consumption (when running/when idle)

1 W

Setpoint value signal input (analogue optional)

0 - 10 V DC, input resistance > 100 kΩ

or 2 - 10V DC Ra> 50 kΩ

Actual value signal output

0 - 10 V DC or 2 - 10 V DC; maximum 5 mA

IEC protection class

III (Protective extra-low voltage)

Protection level

IP 42 (with attached terminal cover)

EC conformity

EMC to 2014/30/EU

Bus connection

Modbus RTU, RS485

Number of nodes (bus participants)

128


Adjustable communication parameters for Modbus

Adjustable baud rate: 1200, 2400, 4800, 9600, 19200, 38400,

76800, 115200 baud

Start bit: 1

Data bits: 8

Stop bits adjustable: 1 or 2

Parity: adjustable: None, Even, Odd

Setpoint / actual value interface (Modbus)

via Modbus register list

Cable termination

externally required (120 Ω)


This specification text describes the general properties of the product.

Category

  • Compact controller for volume flow rate


Application

Control of a constant or variable volume flow setpoint Electronic controller for connecting a reference value and capturing an actual value signal. Actual value signal related to nominal volume flow, thus simplifying commissioning and subsequent adjustment.

Area of application

Static transmitter for contaminated air in ventilation and air conditioning systems

Actuator

Integral; slow-running (running time 100 s for 90°)

Installation orientation

As needed

Connection

  • Terminals with rubber cap cover, so no additional terminal box required
  • Double terminal for supply voltage for easy wiring of up to 3 controllers


Supply voltage

  • 24 V AC/DC


Interface/signalling

  • Modbus RTU (RS485) or alternatively analogue signal 0 - 10 V DC or 2 - 10 V DC
  • Interface type parameterised at the factory using order code, can be changed on site


Interface information

  • Analogue: Volume flow setpoint and volume flow actual value signal
  • Alternatively Modbus: Volume flow setpoint and actual volume flow signal, damper position, override control, etc.


Special functions

  • Parameters specific to VAV terminal unit are set at the factory
  • Operating values: qvmin, qvmax and interface type are set in the factory
  • Subsequent adjustment via display and control element directly on the device or with optional tools: adjustment device, PC software (cable connection in each case), in Modbus mode also via Modbus register access


Parameter setting

  • Electronic controller factory-mounted on the terminal unit
  • Factory set parameters
  • Functional test under air; certified with sticker


Factory condition

  • Functional test under air using reference measurement on a regularly validated test bench in accordance with EN ISO 9001 to check the function and control accuracy of the complete volume flow controller
  • Adjustment of the device-specific parameters under air by reference measurement on a regularly validated test bench in accordance with EN ISO 9001
  • The test report of the factory parameterisation, functional test and adjustment must be made available after delivery of the volume flow controller


Equivalence criteria

  • Electrical connections with screw terminals, no additional terminal boxes required
  • The test report of the factory parameterisation, functional test and adjustment under air by reference measurement on a regularly validated test bench in accordance with EN ISO 9001 is made available
TVEDP1FL/100 / G2 / XS0 / V0 / 20 – 350 m³/h
||||||||||
12345678910

1 Type

TVE VAV terminal unit

2 Acoustic cladding

No entry: without acoustic cladding

D with acoustic cladding

3 Material

No entry: galvanised sheet steel

P1 Air duct powder-coated RAL 7001 (silver grey)

A2 Stainless steel construction

4 Air duct connection

No entry: push-fit end, suitable for air ducts according to EN 1506; with groove for optional seal

FL Flanges on both ends

5 Nominal size [mm]

100, 125, 160, 200, 250, 315, 400

6 Accessories

No entry: without accessories

D2 Double lip seal on both sides (only with push-fit end air duct connection)

G2 Matching flange on both sides (only with air duct connection FL)

7 Attachment (control component)

XS0 Compact controller static with display, interface Modbus RTU or analogue

8 Operating mode

F Fixed value mode, one setpoint value (no external switch contact)

V Variable operation (setpoint range via analogue signal)

M Modbus RTU interface, variable operation (setpoint specification via Modbus register)

9 Signal voltage range
Only with operating mode F, V

0 0 – 10 V DC

2 2 – 10 V DC

10 Operating values for factory setting

Volume flow rate [m³/h or l/s]

qvconst (with operating mode F)

qvmin – qvmax (with operating mode V, M)


Order example: TVE-D-P1-FL/100/G2/XS0/V0/20-350[m³/h]

Type TVE – VAV terminal unit
Acoustic claddingwith acoustic cladding
MaterialAir duct powder-coated RAL 7001 (silver grey)
Air duct connectionFlanges on both ends
Nominal size [mm]100 mm
AccessoriesMatching flanges on both ends
Attachment (control component)Compact controller static with display, interface Modbus RTU or analogue
Operating modevariable operation 
Signal voltage range0 – 10 V DC
Operating values for factory setting20 – 350 m³/h
 

Variants

  • Varianten

  • TVE

Downloads

product information

certificates

operation manuals

production {"X-Frame-Options"=>"SAMEORIGIN", "X-XSS-Protection"=>"1; mode=block", "X-Content-Type-Options"=>"nosniff", "X-Download-Options"=>"noopen", "X-Permitted-Cross-Domain-Policies"=>"none", "Referrer-Policy"=>"strict-origin-when-cross-origin", "Strict-Transport-Security"=>"max-age=31536000; includeSubDomains", "Content-Type"=>"text/html; charset=utf-8"}

Share page

Recommend this page

Recommend this page by sending a link by mail.

Fields marked with an (*) are required fields.

Share page

Thank you for your recommendation!

Your recommendation has been sent and should arrive shortly.

Contact

We are here for you

Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

Contact

We are here for you

Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

Attachment (max. 10MB)

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265