Application
Control strategy
Operating modes
Modbus (M):
Analogue - variable operation (V):
Analogue - fixed value operation (F):
Interface
Communication interface
Analogue interface with adjustable signal voltage range
Note
Signal voltage ranges
When using the analogue interface:
Parts and characteristics
Construction
Commissioning
Useful additions
1 Differential pressure transducer
2 Actuator
3 Volume flow controller
4 Setpoint value via BACnet, Modbus or analogue signal
5 Shaft with effective pressure channel
Volume flow controllers are characterised by a closed control loop for controlling the volume flow, i.e. measuring - comparing - adjusting. The volume flow rate is obtained by measuring a differential pressure. This is done via a differential pressure sensor. The integrated differential pressure transducer converts the differential pressure into a voltage signal. The actual volume flow value is available as a data point and voltage signal. Due to factory adjustment, 10 V DC always corresponds to the nominal flow rate (qvnom). The volume flow setpoint is specified by a higher-level controller (e.g. room temperature controller, air quality controller, MCE). Variable volume flow control can be set between qvmin and qvmax. The controller compares the volume flow setpoint with the current actual value and adjusts the internal actuator, according to the control deviation. It is possible to override the room temperature control by override control, e.g. by a shut-off.
Compact controller for VAV terminal units
Part number | Type of installation component | VAV terminal units |
A00000082304 | TR0VM-024T-10l-DS10-MB | TVE, TVE-Q |
Compact controller TR0VM-024T-10I-DS10-MB
Type of measurement/installation orientation | static measuring principle, position-independent |
Supply voltage (AC) | 24 V AC, ± 20 %, 50/60 Hz |
Supply voltage (DC) | 24 V DC ± 20 % |
Power rating (AC) | TVE NW 100 - 160: maximum 4 VA TVE NW 200 - 400: maximum 6 VA TVE-Q up to height 200: maximum 4 VA TVE-Q from height 300: maximum 6 VA |
Power rating (DC) | TVE NW 100 - 160: maximum 2.5 W TVE NW 200 - 400: maximum 3 W TVE-Q up to height 200: maximum 2.5 W TVE-Q from height 300: maximum 3 W |
Power consumption (when running/when idle) | 1 W |
Setpoint value signal input (analogue optional) | 0 - 10 V DC, input resistance > 100 kΩ or 2 - 10V DC Ra> 50 kΩ |
Actual value signal output | 0 - 10 V DC or 2 - 10 V DC; maximum 5 mA |
IEC protection class | III (Protective extra-low voltage) |
Protection level | IP 42 (with attached terminal cover) |
EC conformity | EMC to 2014/30/EU |
Bus connection | Modbus RTU, RS485 |
Number of nodes (bus participants) | 128 |
Adjustable communication parameters for Modbus | Adjustable baud rate: 1200, 2400, 4800, 9600, 19200, 38400, 76800, 115200 baud Start bit: 1 Data bits: 8 Stop bits adjustable: 1 or 2 Parity: adjustable: None, Even, Odd |
Setpoint / actual value interface (Modbus) | via Modbus register list |
Cable termination | externally required (120 Ω) |
This specification text describes the general properties of the product.
Category
Application
Control of a constant or variable volume flow setpoint Electronic controller for connecting a reference value and capturing an actual value signal. Actual value signal related to nominal volume flow, thus simplifying commissioning and subsequent adjustment.
Area of application
Static transmitter for contaminated air in ventilation and air conditioning systems
Actuator
Integral; slow-running (running time 100 s for 90°)
Installation orientation
As needed
Connection
Supply voltage
Interface/signalling
Interface information
Special functions
Parameter setting
Factory condition
Equivalence criteria
TVE | – | D | – | P1 | – | FL | / | 100 | / | G2 | / | XS0 | / | V | 0 | / | 20 – 350 m³/h |
| | | | | | | | | | | | | | | | | | | | ||||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | ||||||||
1 Type
TVE VAV terminal unit
2 Acoustic cladding
No entry: without acoustic cladding
D with acoustic cladding
3 Material
No entry: galvanised sheet steel
P1 Air duct powder-coated RAL 7001 (silver grey)
A2 Stainless steel construction
4 Air duct connection
No entry: push-fit end, suitable for air ducts according to EN 1506; with groove for optional seal
FL Flanges on both ends
5 Nominal size [mm]
100, 125, 160, 200, 250, 315, 400
6 Accessories
No entry: without accessories
D2 Double lip seal on both sides (only with push-fit end air duct connection)
G2 Matching flange on both sides (only with air duct connection FL)
7 Attachment (control component)
XS0 Compact controller static with display, interface Modbus RTU or analogue
8 Operating mode
F Fixed value mode, one setpoint value (no external switch contact)
V Variable operation (setpoint range via analogue signal)
M Modbus RTU interface, variable operation (setpoint specification via Modbus register)
9 Signal voltage range
Only with operating mode F, V
0 0 – 10 V DC
2 2 – 10 V DC
10 Operating values for factory setting
Volume flow rate [m³/h or l/s]
qvconst (with operating mode F)
qvmin – qvmax (with operating mode V, M)
Order example: TVE-D-P1-FL/100/G2/XS0/V0/20-350[m³/h]
Type | TVE – VAV terminal unit |
Acoustic cladding | with acoustic cladding |
Material | Air duct powder-coated RAL 7001 (silver grey) |
Air duct connection | Flanges on both ends |
Nominal size [mm] | 100 mm |
Accessories | Matching flanges on both ends |
Attachment (control component) | Compact controller static with display, interface Modbus RTU or analogue |
Operating mode | variable operation |
Signal voltage range | 0 – 10 V DC |
Operating values for factory setting | 20 – 350 m³/h |
Share page
Recommend this page
Recommend this page by sending a link by mail.
Share page
Thank you for your recommendation!
Your recommendation has been sent and should arrive shortly.
Contact
We are here for you
Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
We are here for you
Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265