VRU-D3-M-B_LM24A-VST_img_01psd.png
Bussystem_MP-Bus_imgpng.png
MP-bus marketing highlights image
Bussystem_BACnet_imgjpg.jpg
BACnet marketing highlights image
Bussystem_Modbus_imgpng.png
Modbus marketing highlights image
X-AIRCONTROL_img_11psd.psd.link

X-AIRCONTROL zone module MP-bus

VRU-D3-M-B_LM24A-VST_img_01psd.png
Bussystem_MP-Bus_imgpng.png
Bussystem_BACnet_imgjpg.jpg
Bussystem_Modbus_imgpng.png
X-AIRCONTROL_img_11psd.psd.link

BUDN    

CONTROL COMPONENT WITH DYNAMIC TRANSDUCER AND  SEPARATE ACTUATOR FOR VAV TERMINAL UNITS

Universal device for use with VAV terminal units

  • Controller and dynamic differential pressure transducer in one casing
  • Separate actuator with simple plug connection
  • Use in ventilation and air conditioning systems, only with clean air
  • Suitable for constant and variable volume flow rates
  • Activation of override controls via external wiring
  • Volume flow rates qvmin and qvmax are set in the factory and saved in the controller
  • Modification of operating parameters by PC software as well as smartphone and tablet app (TROX FlowCheck app)
  • Service access for PC configuration software
  • Smartphone access via NFC interface and Bluetooth
  • Setpoint value settings, override controls and parameter adjustment via analogue interface or bus communication
  • High data transparency through standardised bus communication MP-Bus, Modbus RTU or BACnet MS/TP

 

Product successfully added to cart

General information 

Application

  • All-in-one control device for VAV terminal units
  • Dynamic differential pressure transducer and control electronics in one casing
  • Separate actuator with prefabricated connection plug
  • For use only with clean air
  • Standard filtration in comfort air conditioning systems allows for use of the controller in the supply air without additional dust protection.
  • Suitable for different control tasks depending on the specification of the setpoint value
  • The room temperature controller, central BMS, air quality controller or similar units control the variable volume flow control by specifying the setpoint values via a communication interface or analogue signal
  • Override controls for activating qvmin, qvmax, shut-off, OPEN position via MP-Bus data points or Modbus/BACnet register or switch/relay possible
  • Volume flow rate actual value is available as a network data point or linear voltage signal
  • Damper blade position is available as a network data point
  • Use TROX FlowCheck app and PC tool to configure the controller and the communication parameters

With heavy dust levels in the room

  • Install appropriate exhaust air filters upstream, as a partial volume flow is routed through the transducer for volume flow rate measurement.


If the air is additionally contaminated, e.g. with fluff or sticky components

  • Use of the BUSN attachment group instead of the BUDN universal controller described here


Control strategy

  • The volume flow controller works independent of the duct pressure
  • Differential pressure fluctuations do not result in permanent volume flow rate changes
  • To prevent the control from becoming unstable, a dead band is allowed within which the damper blade does not move.
  • Volume flow rate range in the controller set in the factory
  • qvmin: minimum volume flow rate
  • qvmax: maximum volume flow rate
  • Operating parameters are specified via the order code and set in the factory


Interface

Analogue interface

  • Analogue interface with adjustable signal voltage range
  • Analogue signal for volume flow rate setpoint
  • Analogue signal for actual volume flow rate

Digital communication interface (Bus)

  • MP bus
  • Modbus RTU, RS485
  • BACnet MS/TP, RS485
  • Data points, see bus lists

Hybrid mode

  • Mixed mode of analogue and digital interface

Factory setting

  • Setpoint value setting via analogue interface
  • Actual value output via analogue interface and Modbus communication interface


Operating modes

Variable operation (V)

  • Setpoint value setting via analogue signal, Modbus, BACnet or MP-BusWork area corresponds to qvmin – qvmax

Constant value mode (F)

  • A setpoint signal is not required, setpoint value corresponds to qvmin


Operating parameters

  • Volume flow rate range in the controller set in the factory
  • qvmin: minimum volume flow rate
  • qvmax: maximum volume flow rate
  • qvmin = 0 – 100 % of the nominal volume flow rate qvnom adjustable
  • qvmax= 20 – 100 % of the nominal volume flow rate qvenn adjustable


Signal voltage ranges


  • 0 – 10 V DC
  • 2 – 10 V DC

Parts and characteristics

  • Transducer for dynamic measurement principle
  • Separate overload protection
  • Plug-in terminal for supply line and controls including cover
  • Socket for the actuator
  • NFC and service interface
  • Release button to allow for manual operation
  • Indicator lights for displaying the operating mode
  • Addressing key for setting user addresses in bus mode
  • Controller casing prepared with 4 openings for threaded connections, 2 cable glands M16x1.5 for connecting cable in the supply package


Construction

BUDN with actuator LM24A-VST for:

  • TVR, TZ-Silenzio, TA-Silenzio, TVZ, TVA,

BUDN with actuator NM24A-VST for:

  • TVJ
  • TVT up to dimensions of 1000 × 300 or 800 × 400

BUDN with actuator SM24A-VST for:

  • TVT from dimensions of 800 × 500 to 1000 × 600


Commissioning

  • Due to the volume flow rates set in the factory, always ensure that the control units are only installed in the specified locations
  • Modbus/BACnet/MP bus interface: additional commissioning steps required
  • Operating parameters can be adjusted using the TROX FlowCheck app


Useful additions

  • TROX FlowCheck app for Android and iOS
  • Adjustment device type ZTH-EU (order code AT-VAV-B)
  • Belimo PC-Tool
  • NFC Bluetooth converter ZIP-BT-NF
  • X-AIRCONTROL zone modules for room control

Technical information

Function, Technical data, Specification text, Order code

  • FUNCTION
  • TECHNICAL DATA
  • SPECIFICATION TEXT
  • ORDER CODE
Principle of operation Universal controller: TVR, TVJ, TVT, TZ-/TA-Silenzio, TVZ, TVA, TVRK XD4_gc_01ai.ai.link

① Differential pressure transducer
② Actuator
③ Volume flow controller
④ Setpoint value signal

A closed control circuit for regulation of the volume flow rate, i.e. measuring - comparing - adjusting, is characteristic of air terminal units. The volume flow rate is measured by measuring a differential pressure (effective pressure). This is done via a differential pressure sensor. An integrated differential pressure transducer converts the effective pressure into a voltage signal. The volume flow rate actual value is available as a voltage signal. The factory setting is such that an actual output signal of 10 V DC always corresponds to the nominal volume flow rate (qvnom). The volume flow rate setpoint value is specified by a higher-level controller (e.g. room temperature controller, air quality controller, central BMS). Variable volume flow control results in a value between qvmin and qvmax. It is possible to override the room temperature control by override controls, e.g. by a complete shutoff of the duct. The controller compares the volume flow rate setpoint value to the actual value and controls the external actuator accordingly to the system deviation.

Universal controller for VAV terminal units

Controllers

Actuator

Order code detail

Part number

Type

Part number

Type

VAV terminal units

BUDNA00000073650VRU-D3-M/B TRA00000076423LM24A-VST TR


BUDNA00000073650VRU-D3-M/B TRA00000073640NM24A-VST TR


BUDNA00000073650VRU-D3-M/B TRA00000073642SM24A-VST TR



① TVR, TZ-Silenzio, TA-Silenzio, TVZ, TVA.

② TVJ, TVT up to dimensions of 1000 × 300 or 800 × 400.

③ TVT dimensions from 800 × 500 to 1000 × 600.



Universal controller, type VRU-D3-M/B TR



Measurement principle




dynamic transducer type, independent of position


Nominal voltage

AC/DC 24 V
Nominal frequency50/60 Hz

Functional range

19,2 – 28,8 V AC oder 21,6 – 28,8 V DC


Power requirement (operation/resting state)




1.5 W


Power rating

2 VA

Power rating - note

Imax 20 A @ 5 ms


Actuator connection

AC/DC supply from controller, PP link VST drive 


Bus connection

Modbus RTU*, BACnet MS/TP, MP-Bus


Adjustable communication parameters with Modbus RTU

Baud rate: 9600, 19200, 38400*, 76800, 115200;

Address: 1*,2.3 – 247;

Parity: 1-8-N-2*, 1-8-N-1, 1-8-E-1, 1-8-O-1;

Number of nodes: max. 32 (without repeater)

Terminal resistor: 120 Ω;


Adjustable communication parameters with BACnet MS/TP

Baud rate: 9600, 19200, 38400*, 76800, 115200;

Address: 1*,2.3 – 127;

Number of nodes: max. 32 (without repeater)

Terminal resistor: 120 Ω;


Addressing

Required on-site: through TROX FlowCheck app


Setpoint value signal input (analogue optional)

0 – 10 V, 2 – 10 V
Input resistance 100 kΩ


Actual value signal output

0 – 10 V, 2 – 10 V, max. 0.5 mA


IEC/EN protection classIII (protective extra-low voltage)
Protection levelIP 42

EMC

CE according to 2014/30/EU

* Factory setting.


Actuator LM24A-VST TR

Supply voltageFrom the controller
Power consumption – when running

1 W

Power rating

2 VA

Self-consumption (idle state)

0.4 W

Torque

5 Nm

Run time for 90°

120 s/90°

Setpoint value signal inputFrom the controller
IEC protection classIII (protective extra-low voltage)
Protection level

IP 54

EMC

EMC to 2014/30/EU
Weight

0.56 kg



Actuator NM24A-VST TR

Supply voltageFrom the controller
Power consumption – when running

2 W

Power rating

4 VA

Self-consumption (idle state)

0.4 W

Torque

10 Nm

Run time for 90°

120 s/90°

Setpoint value signal inputFrom the controller
IEC protection classIII (protective extra-low voltage)
Protection level

IP 54

EMC

EMC to 2014/30/EU
Weight

0.78 kg


Actuator SM24A-VST TR

Supply voltageFrom the controller
Power consumption – when running

2 W

Power rating

4 VA

Self-consumption (idle state)

0.4 W

Torque

20 Nm

Run time for 90°

120 s/90°

Setpoint value signal inputFrom the controller
IEC protection classIII (protective extra-low voltage)
Protection level

IP 54

EMC

EMC to 2014/30/EU
Weight

0.98 kg




Commissioning



  • On-site adjustment is not required
  • Due to the volume flow rates set in the factory, always ensure that the control units are only installed in the specified locations
  • After successful installation and wiring the controller is ready for use
  • Comply with the volume flow rate control ranges of the VAV terminal units, do not set a volume flow rate which is below the minimum flow rate
  • Only briefly remove the protective cap of the control component during wiring
  • For operation with the Modbus/BACnet/MP-Bus interface: additional commissioning steps such as user addressing and setting of the communication parameters are required
  • For operation with the MP-Bus interface in existing systems as a replacement for the VRP-M controller: activation of the VRP-M compatibility mode is required


Functional scope of service tools


Function/parameterisation

TROX FlowCheck app

PC-Tool

ZTH-EU

Setting qvmin, qvmaxR, WR, WR, W


Actual value signal 0 - 10 V DC, 2 - 10 V DC


R, WR, W
Setpoint value setting analogue, BusR, WR, W
Modbus, BACnetR, WR, W
MP busR, WR, W
Set bus parametersR, WR, W
Carry out override controls

No

NoNo
Trend display

Yes

Yes

R,W = Function can be read and written.

- = Function is not available for the service tool.


Communication interface Modbus RTU


NumberRegister AddressDescriptionRange EnumerationUnitScalingAccess
1

Setpoint value between 


qvmin/Δpmin (reg. address 105) and


qvmax/Δpmax (reg. address 106)

(*1) (*2) (*3) (*4)

0 – 10,000

Factory setting: 0

%

0.01[R / W]
21

Override control



Overwrites the setpoint value with override control

0: None

1: OPEN

2: CLOSED

3: qvmin/Δpmin

5: qvmax/Δpmax

Factory setting: None

WR
32

Command triggering 



Triggering of functions for service and test purposes. Command ends automatically with 0


0: None

1: Adapting

3: Synchronisation

Factory setting: None 

WR
43

Type of actuator

(*5)

0: Actuator not connected/not known

1: Actuator Air/Water with/without safety function

2: Volume flow controller VAV/EPIV

3: Fire damper

4: Energy Valve

5: 6way EPIV

RD
54

Current damper blade position acc. to mechanical limits



(*5)

0 – 10,000

%

0.01RD
65

Blade angle acc. to angle range



(*5)

0 – 9,600

°

0.01RD
76

Relative volume flow rate related to qvnom (reg. address 110)



(*6)

0 – 15,000

%

0.01RD
87

Absolute volume flow rate

(*6)

0 – qvnom

m³/h

1RD
98

Sensor value (voltage, resistance, switch)


Value dependent on the setting of the sensor type (reg. address 107)

0 – 65,535

mV,


Ω,


0/1

0.1RD
109

-[–]
1110

Absolute volume flow rate in selected volume flow unit acc. to (reg. address 117)



(Low word) < 16 of 32 bit



(*6)

0 – 500,000,000

UnitSel

0.001RD
1211

Absolute volume flow rate in selected volume flow unit acc. to (reg. address 117)



(High word) > 16 of 32 bit



(*6)

0 – 500,000,000

UnitSel

0.001RD
1312

Analogue setpoint value 

Shows the setpoint value in % with analogue control input signal. Active if reg. address 118 = 0 (analogue)

0 – 10,000

%

0.01RD
5150

Relative differential pressure 



According to application case as per (reg. address 128)

0 – 20,000

%

0.01RD
5251

Absolute differential pressure

-1,000 – 15,000

[Pa]

0.1RD
5352

[–]
5453

Absolute differential pressure in selected unit (reg. address 145)


(Low word) < 16 of 32 bit

-10,000,000 – 100,000,000

UnitSel

0.001RD
5554

Absolute differential pressure in selected unit as per (reg. address 145) 



(High word) > 16 of 32 bit

-10,000,000 – 100,000,000 

UnitSel

0.001RD
10099

Bus terminal resistor 



Indicates whether the terminal resistor (120 Ω) is active or deactivated.


Can only be set using service tools.

0: Not active


1: Active


Factory setting: Not active

RD
101100

Serial number, part 1


Example: 00839-31324-064-008


1st part: 00839


2st part: 31324


3st part: 008

RD
102101

Serial number, part 2

RD
103102

Serial number, part 3

RD
104103

Firmware version

Example: 101, version 01.01.

RD
105104

Malfunctions and service information –


automatic reset if status has ceased

Bit 0: –

Bit 1: Mechanical travel too high

Bit2: Actuator cannot be moved (e.g. mechanical overload)

Bit 3: –

Bit 4: Error of dP sensor

Bit 5: Return air flow detected

Bit 6: Volume flow rate too low

Bit 7: Flow rate in closed position

Bit 8: Internal activity (e.g. test run, adaptation)

Bit9: Gear release active

Bit10: Bus monitoring triggered

Bit 11: Actuator not suitable for application

Bit 12: Pressure sensor incorrectly connected

Bit 13: Pressure sensor not reached

Bit 14: Error in dP sensor outside of measuring range

RD
106105

Setting work areas qvmin/Δpmin 



Requirements: qvmin/Δpmin < qvmax/Δpmax


Vmax in the area 0 – 100 % of qvnom/Δpnominal

0 – qvmax/Δpmax

%

0.01WR
107106

Setting work areas qvmax/Δpmax 

Requirements: qvmax/Δpmax < qvmin/Δpmin

Vmax in the area 20 – 100 % of qvnom/Δpnominal

2,000 10,000  

%

0.01WR
108107

Type of sensor 



If reg. address 118 = 0 (analogue), then reg. address 107 = 1 (active) for mV

0: None


1: Active


2: Passive


3: –


4: Switch



Factory setting: None

WR
109108

Bus timeout monitoring 

If there is a bus timeout, the actuator moves into a position specified here. 

The position is mech. limited, qvmin/Δpmin and qvmax/Δpmax have no impact.

Release if no change takes place in reg. address 1 or reg. address 2 in the specified time for reg. address 109.

Display of release in reg. address 104.

In hybrid mode, bus timeout activation is deactivated. 

Bus timeout time: acc. to reg. address 109

0 – 10,000

Factory setting: 0

%

0.01WR
110109

Time until release bus timeout monitoring

If reg. 108 ≠ 0, then the initial automatic status is reg. 108 = 120 s. 

0 – 3,600 


0: Inactive


Factory setting: Deactivated


s

1WR
113112

Nominal volume flow rate in selected volume flow unit acc. (reg. address 117)



(Low word) < 16 of 32 bit

0 – 60,000,000

UnitSel

0.001RD
114113

Nominal volume flow rate in selected volume flow unit acc. (reg. address 117)



(High word) > 16 of 32 bit

0 – 60,000,000

UnitSel

0.001RD
115114

[–]
116115

[–]
117116

Control mode

0: Position control (open loop)

1: Volume flow control

Factory setting: Volume flow control 

[R]
118117

Unit selection –



Unit selection for reg. address 11 and 12

0: –

1: m³/h

2: l/s

3: –

4: –

5: –

6: cfm

-

WR
119118

Setpoint value setting

If reg. address 118 = 0 (analogue), then reg. address 12 = active.

If reg. address 118 = 1 (Bus), then reg. address 1 = active.

0: Analogue (0 – 10 V, 2 – 10 V)

1: Bus (Modbus, BACnet, MP-Bus)

Factory setting: Analogue 

WR
120119

Pressure operating mode 

Only for VRU-M1R-M/B TR.

0: Negative pressure

1: Positive pressure

WR
121120

[–]
122121

[–]
123122

[–]
124123

Room pressure cascade release 

Only available if reg. address 124 = 0 (volume flow control) or 2 (room pressure control).

0: Inactive


1: Active


2: Active fast (only for VRU-M1R-M/B TR)

RD
125124

Applications

0: Volume flow control

1: Pressure control

2: Room pressure control

3: Flow measurement

RD
126125

Unit height

0 – 3,000

Factory setting: 0

m

1WR
127126

Nominal differential pressure in the selected unit as per (reg. address 145)

More info in (reg. address 128)

D3: 0 – 50000

M1: 0 – 60000

M1R: 0 – 60000

UnitSel

RD
128127

[–]
129128

Nominal differential pressure in Pa 

If reg. address 124 = 0 (volume flow control), then reg. address 110 as qvnom.

If reg. address 124 = 1 (differential pressure control) or 2 (room pressure control), then the maximum is defined by the diff. pressure.

D3: 0 – 500

M1: 0 – 600

M1R: 0 – 750

Pa

0.1RD
146145

Selection of the pressure unit 

The selected unit is displayed in (reg. address 126).

0: Pascal


1: –


2: Water column


Factory setting: Pascal 

[–]

RD = Register can only be read
WR = Register can be read and written


(*1) If reg. address 118 = 1 (Bus), then reg. address 0 = active.

(*2) If reg. address 124 = 0 (volume flow control), then reg. address 0 = volume flow rate

(*3) If reg. address 124 = 0 (volume flow control) and reg. address 116 = 0 (position control), then reg. address = damper blade position

(*4) If reg. address 124 = 1 (differential pressure control) or 2 (room pressure control), then reg. address = pressure

(*5) If reg. address 124 = 2 (room pressure control) or 3 (volume flow rate measurement), then reg. address = deactivate 65535

(*6) If reg. address 124 = 1 (differential pressure control) or 2 (room pressure control), then reg. address = deactivate 65535



Protocol Implementation Conformance Statement – PICS (general information)


Date

2020-06-11

Vendor nameTROX GmbH
Vendor ID

329

Product nameVRU-D3-BAC, VRU-M1-BAC, VRU-M1R-BAC
Product model numberVRU – BAC
Application software version

01.02.0001

Firmware revision

10.02.0000

BACnet Protocol Revision

12

Product descriptionController for VAV/CAV and pressure applications
BACnet Standard Device ProfileBACnet Application Specific Controller (B-ASC)
BACnet Interoperability Building Blocks Supported

Data Sharing – ReadProperty-B (DS-RP-B)
Data Sharing – ReadPropertyMultiple-B (DS-RPM-B)
Data Sharing – WriteProperty-B (DS-WP-B)
Data Sharing – WritePropertyMultiple-B (DS-WPM-B)
Data Sharing – COV-B (DS-COV-B)
Device Management – DynamicDeviceBinding-B (DM-DDB-B)
Device Management – DynamicObjectBinding-B (DM-DOB-B)
Device Management – DeviceCommunicationControl-B (DM-DCC-B)

Segmentation CapabilityNo
Data Link Layer OptionsMS/TP master, baud rates: 9600, 19200, 38400, 76800, 115200
Device Address BindingNo static device binding supported
Networking OptionsNone
Character Sets SupportedISO 10646 (UTF-8)
Gateway OptionsNone
Network Security OptionsNon-secure device


Object processing


Object type

Optional properties

Writeable properties

Analogue input [AI]

Description
COV Increment

COV Increment

Analogue Output [AO]

Description
COV Increment

Present Value
COV Increment
Relinquish Default

Analogue Value [AV]

Description



COV Increment

Present Value



COV Increment

Binary Input [BI]

Description
Active Text
Inactive Text

Device

Description
Location
Active COV Subscriptions
Max Master
Max Info Frames
Profile Name

Object Identifier
Object Name
Location
Description
APDU Timeout (1000 – 60000)
Number Of APDU Retries (0 – 10)
Max Master (1 – 127)
Max Info Frames (1 – 255)

Multi-state Input [MI]

Description
State Text

Multi-state Output [MO]

Description
State Text

Present Value
Relinquish Default

Multi-state Value [MV]

Description
State Text

Present Value (if marked)


Processing of services

  • The device does not support the services "Create object" and "Delete object"
  • The specified maximum length of the writable character strings is based on single-byte characters
  1. Object name 32 characters
  2. Location 64 characters
  3. Description 64 characters
  • The device supports the DeviceCommunicationControl Services, no password necessary
  • A maximum of 6 active COV subscriptions with a run time of 1 – 28800 s (maximum of 8 h) is supported


Communication interface BACnet MS/TP


Object NameObject TypeDescriptionValuesCOV IncrementAccess
Device

Device [Inst.No]

0 – 4,194,302

Factory setting: 1

WR
RelPosAI[1]

Damper blade position in %

Status flags: (*1), (*2)

0 – 100

0.01 – 100

Factory setting: 1

RD
AbsPosAI[2]

Absolute position in ° 

Angular position corresponding to the entire rotation range.

Status flags: (*1), (*2)

0 – max. angle

0.01 – 90

Factory setting: 1

RD
SpAnalogueAI[6]

Analogue setpoint value in %

Shows the analogue setpoint value according to the selected application flow rate, pressure, damper blade position as per ApplicationSel MV[2]. 
If setpoint value setting in SpSource MV[122] = 1 (analogue), then SpAnalog AI[6] = active.
The analogue setpoint value is limited by Min AV[97] and Max AV[98].
 

Status flags: (*1), (*3)

0 – 100

0.01 – 100

Factory setting: 1

RD
RelDeltaP

AI[9]

Relative differential pressure in % with respect to DeltaPnom_Pa AV[122]

0 – 150

0.01 – 150

Factory setting: 1

RD
RelFlowAI[10]

Relative volume flow rate in % related to Vnom_m3h AV[112]

Status flags: (*4)

0 – 150

0.01 – 150

Factory setting: 1

RD
AbsFlow_m3h

AI[12]

Absolute volume flow rate in m³/h

Status flags: (*4)

0 – 60,000

1 – 60,000

Factory setting: 10

RD
DeltaP_UnitSel

AI[18]

Absolute differential pressure in selected unit as per UnitSelPressure MV[127]

-10,000 – 100,000

0.001 – 100,000

Factory setting: 1

RD
AbsFlow_UnitSelAI[19]

Absolute volume flow rate in selected unit as per UnitSelAirFlow MV[121]

Status flags: (*4)

0 – 500,000

0.01 – 500,000

Factory setting: 1

RD
Sens1AnalogueAI[20]

Sensor 1 as analogue value 
 

If Sensor1Type MV[220] = 2 (active), then display = analogue value in 0 – 10 V.

If Sensor1Type MV[220] = 3 (passive), then display = resistance value.

If RmPCascade MV[10] = 2 (enabled) or 3 (quickly enabled), then the sensor input is not available. 
 

Status flags: (*5)

0 – 65535

0.01 – 1000

Factory setting: 1

RD
DeltaP_Pa

AI[29]

Absolute differential pressure in Pa

0 – 600

0.01 – 600

Factory setting: 10

RD
SpRelAO[1]

Relative setpoint value in % 

The rel. setpoint value depends on the application (flow rate/pressure/damper blade position).
If SpSource MV[122] = 2 (bus), then SpRel AO[1] = active.
The analogue setpoint value is limited by Min AV[97] and Max AV[98].

Status flags: (*1), (*2)

0 – 100

Factory setting: 0

0.01 – 100

Factory setting: 1

C
MinAV[97]

Minimum setpoint value in % (qvmin/Pmin)

Requirement:

qvmin/Δpmin < qvmax/Δpmax

qvmin/Δpmin in the range 0 - 100 & qvnom/Δpnom

0 – qvmax/Δpmax

0.01 – 100

Factory setting: 1

WR
MaxAV[98]

Maximum setpoint value in % (qvmax/Pmax)

Requirement:

qvmax/Δpmax > qvmin/Δpmin

qvmax/Pmax in the range 20 - 100 % of qvnom/Pnom

qvmin/Δp – 100

0.01 – 100

Factory setting: 1

WR
Vnom_m3h

AV[112]

Nominal volume flow rate in m³/h

0 – 50,000

0.01 – 50,000

Factory setting: 1

RD
Vnom_UnitSel

AV[119]

Nominal volume flow rate in selected unit as per UnitSel MV[121]

0 – 250,000

0.01 – 1,000:

Factory setting: 1

RD
SystemAltitude

AV[120]

System altitude in metres above sea level

0 – 3,000

1 – 3,000

Factory setting: 10

WR
DeltaPnom_Pa

AV[122]

Nominal differential pressure in Pa 

The nominal differential pressure depends on the selected pressure sensor (D3, M1, M1R).

Depending on the selected application, the nominal differential pressure serves as dp@Vnom or as the maximum pressure limitation

If ApplicationSel MV[2] = 1 (flow control), then display = nominal differential pressure

If ApplicationSel MV[2] = 2 (pressure control) or 3 (room pressure control), then display = max. pressure limitation

D3: 0 – 500

M1: 0 – 600

M1R: 0 – 75

1 – 600

Factory setting: 1

RD
DeltaPnom_UnitSel

AV[129]

Nominal differential pressure in selected unit as per UnitSelPressure MV[127]

More infos: see AV[122].

0.01 – 1000

Factory setting: 1

RD
BusWatchdogAV[130]

Time until the release bus timeout monitoring in s 


If BusWatchdog AV[130] ≠ 0, then monitoring of SpRel AO[1] and override MO[1] for change.
If changes in SpRel AO[1] and override MO[1], then reset the bus timeout monitoring. 
If SpSource MV[122] = 1 (analogue), then BusWatchdog AV[130] only takes account of override MO[1].  

0 – 3600 s

Factory setting: 0 (bus timeout monitoring deactivated)

0.01 – 1000

Factory setting: 1

WR
Sens1SwitchBI[20]

Switch status of the switch at the sensor input 

If SenType MV[220] = 5 (switch), then Sens1Switch BI[20] = active.

Status flags: (*6)

0: Inactive

1: Active

RD
BusTerminationBI[99]

Terminal resistor 

Shows whether the terminal resistor (120 Ω) has been activated via the service tools.

0: Deactivated

1: Activated

RD
SummaryStatusBI[101]

Condensed status 


Groups together the status of the objects: 

"StatusSensor" MI[103] 
"StatusFlow" MI[104] 
"StatusActuator" MI[106] 
"StatusPressure" MI[109] 
"StatusDevice" MI[110]  

Not equal to 1: OK

1: Not OK

RD
RmPCasacade

MV [10]

Room pressure cascade 

If RmPCascade MV[10] = 2 (active) or 3 (active fast), then sensor1 is the input for the room cascade (0 – 10 V).

If ApplicationSel MV[2] =1 (volume flow control) or 3 (room pressure control), then RmPCascade MV [10] = active.

Status flags: (*7)

1: Inactive

2: Active

3: Active fast (for M1R only) 

RD
InternalActivity

MI[100]

Internal status 

1: None

2: –

3: Adaption

4: Synchronisation

RD
StatusSensor

MI[103]

Status of the differential pressure sensor 

If status end = automatic reset

1: OK

2: dP sensor not OK

3: dP sensor outside of measuring range

4: dP sensor incorrectly connected

RD
StatusFlow

MI[104]

Volume flow rate status 


If there is no volume flow rate within 600 s, then StatusFlow MI[104] = 3.

1: OK

2: –

3: No airflow detected

RD
StatusActuator

MI[106]

Status of the actuator 

Status flags: (*2)

1: OK

2: Actuator cannot be moved

3: Gear release active

4: Mechanical travel exceeded

5: Actuator not suitable for application

RD
StatusPressure

MI[109]

Differential pressure status 

If the differential pressure is not reached within 180 s, then StatusPressure MI[109] = 3.

1: OK

2: –

3: Pressure not reached

RD
StatusDevice

MI[110]

Status of the device during bus monitoring 


According to BusWatchdog AV[130].

1: OK

2: Bus timeout monitoring activated

RD
Override

MO[1]

Override control 

Overwrites the setpoint value with a forced command.

Status flags: (*8)

1: None

2: OPEN

3: CLOSED

4: qvmin/Δpmin

5: –

6: qvmax/Δpmax

Factory setting: None (1)

C
ApplicationSel

MV[2]

Display of application 

VRU-D3-M/B TR, VRU-M1-M/B TR

- Flow control
- Pressure control
- Flow measurement

VRU-M1R-M/B TR
- Room pressure control

1: Flow control

2: Pressure control

3: Room pressure control

4: Flow measurement

RD
ControlMode

MV[100]

Control mode

Status flags: (*9)

1: PosCtrl

2: FlowCtrl

Factory setting: FlowCtrl

RD
OperationMode

MV[102]

Operating mode 

Only relevant for VRU-M1R-BAC.

Status flags: (*10)

1: Negative pressure

2: Positive pressure

WR
Command

MV[120]

Release test functions

Status flags: (*2)

1: None

2: Adaption

3: –

4: Reset

Factory setting: None 

WR
UnitSelAirFlow

MV[121]

Selection of the volume flow unit 

The selected unit is indicated in AI[19] and AV[104]

1: –

2: m³/h

3: l/s

4: –

5: –

6: –

7: cfm

WR
SpSource

MV[122]

Selection of the setpoint value setting 

If SpSource MV[122] = 1 (analogue), then SpAnalog AI[6] = active.

If SpSource MV[122] = 2 (bus), then SpRel AO [1] = active.

1: Analogue (0 – 10 V, 2 – 10 V)

2: Bus (Modbus, BACnet, MP-Bus)

Factory setting: Analogue

WR
UnitSelPressure

MV[127]

Selection of the pressure unit

The selected unit is indicated in DeltaP_UnitSel AI[18] and DeltaPnom_UnitSel AV[129].

1: Pascal

3: Water column

Factory setting: pascal 

WR
UnitSelTemp

MV[128]

Selection of temperature unit

The selected unit is located in AI[20].

1: K

2: °C

3: °F

Factory setting: °C (2)

W
Sens1Type

MV[220]

Definition of the sensor type 

If Sens1Type MV[220] = 2 (active) or 3 (passive), then Sens1Analog AI[20] active.

If Sens1Type MV [220] = 5 (switch), then Sens1Schalter BI[20] active. 

1: None

2: Active sensor (in hybrid mode)

3: Passive sensor 

4: –

5: Switch

Factory setting: None 

WR

RD = Register can only be read
WR = Register can be read and written
C = Commendable with priority array


Status flags: 


(*1) If the gear latch is pressed, then Overridden = 1


(*2) If ApplicationSel MV[2] = 3 (room pressure control) or 4 (flow measurement), then Out of Service = 1


(*3) If SpSource MV[122] = 2 (Bus), then Out of Service = 1


(*4) If ApplicationSel MV[2] = 2 (pressure control) or 3 (room pressure control), then Out of Service = 1


(*5) If Sens1Type MV[220] = 1 (none), then Out of Service = 1


(*6) If Sens1Type MV[220] ≠ 5, then Out of Service = 1


(*7) If ApplicationSel MV[2] = 2 (pressure control) or 4 (flow measurement), then Out of Service = 1


(*8) If ApplicationSel MV[2] = 4 (flow measurement), then Out of Service = 1


(*9) If ApplicationSel MV[2] ≠ 1 (volume flow control), then Out of Service = 1


(*10) If ApplicationSel MV[2] ≠ 3 (room pressure control), then Out of Service = 1


This specification text describes the general properties of the product.

Category

  • Universal controller for volume flow rate


Application

  • Control of a constant or variable volume flow rate setpoint
  • Electronic controller for connecting a controlled variable and tapping an actual value signal
  • The actual value signal relates to the nominal volume flow rate such that commissioning and subsequent adjustment are simplified
  • Stand-alone operation or integration in central building management system


Area of application

  • Differential pressure transducer with dynamic measuring principle for clean air in ventilation and air conditioning systems


Actuator

  • Actuator slow-running; Running time 120s for 90°


Installation orientation

  • Either direction


Connection

  • Pluggable connection terminals; no additional terminal box required


Supply voltage

  • 24 V AC/DC


Interface/signalling

Analogue signal

  • 0 – 10 V DC or 2 – 10 V DC

Bus interface

  • MP bus
  • Modbus RTU
  • BACnet MS/TP


Interface information

Analogue

  • Volume flow rate setpoint and actual value

Bus interface

  • Volume flow rate setpoint and actual value
  • Damper blade position
  • Fault status


System connections

  • MP-Bus for optional extensions
  • Suitable for TROX X-AIRCONTROL zone module X-AIRZMO- MP
  • Gateways for LonWorks, Modbus, BACnet, KNX e.g. Belimo UK24EIB
  • Fan optimiser, e.g. Belimo COU24-A-MP

Modbus RTU for optional extensions

  • Suitable for TROX X-AIRCONTROL zone module X-AIRZMO- MOD, e.g. in conjunction with X-SENS-SPLITTER


Special functions

  • Activation qvmin, qvmax, Closed, Open, Control Stop by means of external switching contacts/wiring or bus communication


Parameter setting

Parameters specific to VAV terminal unit set at the factory

  • Operating values qvmin, qvmax factory set
  • Signal characteristic factory set

Subsequent adjustment

  • Via TROX FlowCheck app (NFC or Bluetooth with optional adapter)
  • Via PC software


Factory condition

  • Electronic controller factory-mounted on the terminal unit
  • Factory parameter settings
  • Functional test under air; certified with sticker
  • Controller in OPEN position

TVRD/200/D2/BUDN/V    0/qvmin – qvmaxm³/h
||||||     |||
125678     91011


1 Type

TVR VAV terminal unit

2 Acoustic cladding

No entry: none

D with acoustic cladding

3 Material

Galvanised sheet steel (Standard construction)

P1 Powder-coated RAL 7001, silver grey

A2 Stainless steel construction

4 Duct connection

5 Nominal size [mm]
100, 125, 160, 200, 250, 315, 400

6 Accessories
No entry: none
D2 Double lip seal both sides

G2 Matching flanges for both ends

7 Attachments (control component)

BUDN Universal controller with dynamic transducer

8 Operating mode

F Constant value (a setpoint value)

V variable (setpoint value range)

9 Signal voltage range

0 0 – 10 V DC

2 2 – 10 V DC

10 Operating values for factory setting

Volume flow rates in m³/h or l/s

qvconst (only with operating mode F)

qvmin (only with operating mode V)

qvmax (only with operating mode V)

11 Volume flow unit
m³/h

l/s


Order example: TVR/100/D2/BUDN/V0/50-354 m³/h

Acoustic calddingNone
Materialgalvanised sheet steel
Nominal size100 mm
AccessoriesDouble lip seal both sides
AttachmentVARYCONTROL Universal controller, dynamic transducer
Signal voltage ranger0 – 10 V DC
Operating valueqvmin= 50 m³/h
qvmax= 354 m³/h

Variants, Product details

  • VARIANTS
  • PRODUCT DETAILS


Analogue interface 0 – 10 V DC or 2 – 10 V DC

In the delivery state, the setpoint must be specified via the analogue interface. If the setpoint value is specified via a digital communication interface, this can be changed to Modbus, BACnet or MP-Bus at any time via the TROX FlowCheck App. The analogue interface can be set for the signal voltage range 0 - 10 V DC or 2 - 10 V DC through the TROX FlowCheck App. The assignment of the volume flow setpoint or actual value to the voltage signal is shown in the characteristic diagrams.


Setpoint value setting

Variable operation

  • In the variable operating mode, the setpoint is specified with an analogue signal at terminal 3. Setpoint specifications via the respective bus system are rejected
  • The selected signal voltage range 0 – 10 V or 2 – 10 V DC is assigned to the volume flow rate range qvmin – qvmax assigned to
  • Volume flow rate range qvmin – qvmax set at the factory according to the order code details
  • Subsequent adjustment of qvmin or qvmax possible via adjustment device, TROX FlowCheck app or PC tool

Constant value mode

  • In the operating mode fixed value operation, no analogue signal is required at terminal 3
  • The value given by qvmin is controlled through the fixed volume flow rate value
  • Volume flow qvmin set at the factory according to the order code details
  • Subsequent adjustment of qvmin possible via adjustment device, TROX FlowCheck app or PC tool


Actual value as feedback for monitoring or tracking control

  • The actual volume flow rate measured by the controller can be captured as a voltage signal at terminal 5
  • Selected signal voltage range 0 - 10 V DC or 2 - 10 V DC is applied to the volume flow range 0 - qvnom shown
  • In analogue mode, there is the parallel option of querying operating data via the Modbus interface (hybrid mode)


Override control

  • For special operating situations, the volume flow controller can be set to a special operating state (override control). The following modes are possible: control qvmin, control qvmax, damper blade open (OPEN), damper blade closed (CLOSED) or control stop.


Override controls via signal input Y or override control inputs z1, z2

  • Through suitable wiring of the inputs Y, z1, z2, the override controls can be activated according to the wiring diagrams via wiring with external switching contacts/relays (see wiring examples).


Override control CLOSED via command signal at signal input Y

With signal voltage range 0 - 10 V DC and setting value qvmin = 0

  • Flap CLOSED: Y < 0.45 V DC
  • Modulating duty: Y > 0.55 V DC

With signal voltage range 0 - 10 V DC and qvmin > 0

  • If override control CLOSED is not possible via the command signal. The control process takes place over the entire signal voltage range

With signal voltage range 2 - 10 V DC and setting value qvmin = 0

  • Flap CLOSED: Y < 2.36 V DC
  • Modulating duty: Y > 2.44 V DC

With signal voltage range 2 - 10 V DC and setting value qvmin > 0

  • Flap CLOSED: Y < 0.3 V DC
  • Regulation qvmin: Y > 0.3 V DC
  • Modulating duty: Y > 2.44 V DC


Digital communication interface

For a setpoint value specification via the bus interface, an on-site conversion with the TROX FlowCheck App is necessary. The bus interface can be set to Modbus, BACnet and MP-Bus. For smooth data exchange in the on-site bus network, it is necessary to set the communication parameters and the participant address for the bus interface. The communication parameters of the bus systems (address, baud rate, etc.) can be set using the TROX FlowCheck app. The interface provides standardised bus register/object access to the available data points.

Setpoint value setting

  • In Modbus RTU operating mode (factory setting), the setpoint is specified by entering the volume flow setpoint [%] in Modbus register 0
  • In the BACnet MS/TP operating mode, the setpoint is specified by specifying the volume flow setpoint [%] in the BACnet object AI[1]
  • The percentage value refers to the volume flow rate range specified by qvmin – qvmax defined volume flow range
  • Volume flow rate range qvmin – qvmax set at the factory according to the order code details
  • Subsequent adjustment of qvmin or qvmax possible via setting device, TROX FlowCheck App, PC tool or via Modbus/BACnet interface


Actual value as feedback for monitoring or tracking control

  • Both Modbus and BACnet show actual values in m³/h (factory setting). Other units such as l/s and cfm can also be selected.
  • In addition to the volume flow rate actual value, other information can be read out using other Modbus registers/BACnet objects
  • Overview of the registers/objects in the communication tables
  • In bus mode the actual volume flow rate can be captured at terminal 5
  • The volume flow rate range 0 – qvnom always corresponds to the signal voltage range (0)2 – 10 V DC


Override control

  • For special operating situations, the volume flow controller can be set to a special operating state (override control). The following
  • modes are possible: control qvmin, control qvmaxthe control damper is in the open position (OPEN), control damper closed (CLOSED) or control stop.


Priority control via the bus

Specifications are made via Modbus register 1 or via BACnet object type MO[1].

Override control by bus failure monitoring (Modbus)

In case of failure of the Modbus communication for a defined period of time, a predefined operating state qvmin, qvmax, OPEN or CLOSED can be activated.

  • The override to be activated in case of bus failure is defined via Modbus register 108 or 109
  • The determination after which bus failure time the override control is activated is made via Modbus register 109 or 110
  • Any Modbus communication resets the bus failure monitoring timeout


Override control by bus failure monitoring (BACnet)

If BACnet communication fails for a specified period of time, a predefined operating state can be activated.

  • The setpoint to be activated in the event of bus failure is determined via the Reliquish_Default of SpRel (Object AO1)
  • Bus failure time is defined via BusWatchdog (object type AV [130])
  • Communication on the data points SpRel (Object AO[1] and Override (Object MO[1]) resets the timeout of bus failure monitoring


Override controls for diagnosis

Activation via bus systems, external/on-site switching contacts (bridges), and TROX FlowCheck App.

Prioritisation of different default options

Specifications for override controls via switching contacts are prioritised over Modbus/BACnet specifications.
  • Highest priority: Preset via override control by external wiring (switching contact, relay)
  • Medium priority: Specifications via the service plug (TROX FlowCheck App) for test purposes
  • Lowest priority: Default via Modbus/BACnet/MP bus

Downloads

product information

certificates

production {"X-Frame-Options"=>"SAMEORIGIN", "X-XSS-Protection"=>"1; mode=block", "X-Content-Type-Options"=>"nosniff", "X-Download-Options"=>"noopen", "X-Permitted-Cross-Domain-Policies"=>"none", "Referrer-Policy"=>"strict-origin-when-cross-origin", "Strict-Transport-Security"=>"max-age=31536000; includeSubDomains", "Content-Type"=>"text/html; charset=utf-8"}

Share page

Recommend this page

Recommend this page by sending a link by mail.

Fields marked with an (*) are required fields.

Share page

Thank you for your recommendation!

Your recommendation has been sent and should arrive shortly.

Contact

We are here for you

Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

Contact

We are here for you

Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

Attachment (max. 10MB)

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265