Note: The product lines TR und DG will be discontinued and replaced by the new TR2, TRX and TR2 move from 01.10.2024. You can find more information here.
Application
Special characteristics
Nominal sizes
Other dimensions upon request
Variants
Parts and characteristics
Attachments
Construction features
Suitable circular duct diameter
Materials and surfaces
Standards and guidelines
Maintenance
Functional description
Ventilation grilles are air terminal devices for the supply air and extract air of ventilation and air conditioning systems. They direct the supply air into the room. Ventilation grilles with adjustable blades allow for adapting the discharge direction to the local conditions. The result is a mixed flow ventilation in comfort zones and industrial zones, with good overall room ventilation.
Induction slows the airflow down, i.e. the airflow velocity decreases as the distance from the grille increases. The distance at which the airflow velocity reaches a certain defined value, e.g. 0.2 m/s, is called throw distance. The supply air jet from wall grilles that are installed near the ceiling achieves a larger throw distance than a free jet (from a grille that is not installed near the ceiling). Single grilles, groups of grilles and continuous horizontal runs all achieve different throw distances.
In cooling mode it is necessary to take account of the jet deviation towards the occupied zone, which increases as the supply air to room air temperature difference increases and the discharge velocity decreases. In heating mode the supply air jet deviates towards the ceiling. This has no negative effect on the airflow velocity in the occupied zone, but it may affect the complete ventilation of the room.
Nominal sizes | 225 × 75 to 1225 × 225 mm |
Minimum volume flow rate | 11 – 275 l/s or 40 – 990 m³/h |
Maximum volume flow rate, with LWA max. 40 dB(A) without attachments | 62 – 930 l/s or 223 – 3348 m³/h |
Supply air to room air temperature difference | –12 to +4 K |
Volume flow rates apply to supply air
Geometric free area
75 | 0.007 | 0.011 | 0.015 | 0.018 | 0.022 | 0.029 | 0.036 | 0.043 |
125 | 0.015 | 0.022 | 0.030 | 0.037 | 0.044 | 0.059 | 0.074 | 0.089 |
225 | 0.045 | 0.060 | 0.075 | 0.090 | 0.119 | 0.149 | 0.179 |
Effective air discharge area (supply air)
75 | 0.007 | 0.011 | 0.014 | 0.018 | 0.021 | 0.029 | 0.036 | 0.043 |
125 | 0.014 | 0.021 | 0.029 | 0.036 | 0.043 | 0.057 | 0.072 | 0.086 |
225 | 0.043 | 0.057 | 0.072 | 0.086 | 0.114 | 0.142 | 0.172 |
Effective air discharge area
75 | 0.006 | 0.009 | 0.011 | 0.014 | 0.016 | 0.022 | 0.028 | 0.033 |
125 | 0.011 | 0.016 | 0.022 | 0.028 | 0.033 | 0.044 | 0.055 | 0.066 |
225 | 0.033 | 0.044 | 0.055 | 0.066 | 0.090 | 0.110 | 0.134 | |
325 | 0.066 | 0.083 | 0.100 | 0.134 | 0.170 | 0.200 | ||
425 | 0.134 | 0.180 | 0.220 | 0.270 | ||||
525 | 0.280 | 0.340 |
Ventilation grilles, rectangular, made of galvanised sheet steel, for supply and extract air. Aesthetic sloped border with chamfered inside edge Installation preferably in circular ducts.
Ready-to-install component which consists of a border and individually adjustable, vertical blades.
Countersunk holes for fixing the grille to the installation surface.
Sound power level of the air-regenerated noise measured according to EN ISO 5135.
Special characteristics
Materials and surfaces
Technical data
Sizing data
Air-regenerated noise
This specification text describes the general properties of the product. Texts for variants can be generated with our Easy Product Finder design programme.
Order example: TRS-R-R5/825×225/P1-RAL 9010
Attachments | Damper unit, special hit and miss damper and air control blades |
Nominal size | 825 × 225 mm |
Exposed surface | Powder-coated RAL 9010, pure white |
The weight table shows the available nominal sizes
TRS-R-RA
mm HN | mm |
TRS-R-RD
mm HN | mm |
TRS-R-RA
75 | 0.4 | 0.5 | 0.7 | 0.8 | 0.9 | 1.2 | 1.5 | 1.8 |
125 | 0.5 | 0.7 | 0.8 | 1.0 | 1.2 | 1.6 | 1.9 | 2.3 |
225 | 1.0 | 1.2 | 1.5 | 1.8 | 2.3 | 2.8 | 3.3 |
Weights apply to ventilation grilles without attachments
TRS-R-RD
75 | 0.5 | 0.6 | 0.8 | 1.0 | 1.1 | 1.4 | 1.8 | 2.2 |
125 | 0.6 | 0.9 | 1.0 | 1.3 | 1.6 | 2.1 | 2.5 | 3.0 |
225 | 1.4 | 1.8 | 2.2 | 2.6 | 3.4 | 4.2 | 5.0 |
Weights apply to ventilation grilles without attachments
Circular duct dimensions
75 | TRSR | 150 | 400 |
75 | TRSR-5 from L = 825 mm | 224 | 400 |
125 | All | 300 | 900 |
225 | All | 600 | 2400 |
Installation and commissioning
Volume flow rate balancing
When several ventilation grilles are installed on the same duct, it may be necessary to balance the volume flow rates.
Air pattern
Principal dimensions
L [mm]
Nominal length of the ventilation grille
H [mm]
Nominal height of the ventilation grille
m [kg]
Weight
Nomenclature
LWA [dB(A)]
Sound power level of the air-regenerated noise
V [m³/h] and [l/s]
Volume flow rate
Δpt [Pa]
Total differential pressure
lS [m]
Distance from single grille or horizontal run section (throw distance)
Share page
Recommend this page
Recommend this page by sending a link by mail.
Share page
Thank you for your recommendation!
Your recommendation has been sent and should arrive shortly.
Contact
We are here for you
Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
We are here for you
Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265