img_pro_001373.png
Z-line filter, construction NWO
img_pro_001375.png
Z-line filter, construction PLA

Z-line filter, construction PLA

img_pro_001373.png
img_pro_001375.png

ZL

For high dust concentrations or as a prefilter for fine dust filters


Z-line filters for the separation of coarse and fine dust, used as the first stage in ventilation and air handling units or as prefilters for high-quality filter stages

  • Filter groups ISO Coarse (coarse dust filter) and ePM10 (fine dust filter)
  • Large filter area due to folding
  • Low differential pressures at high volume flow rates
  • Moisture-resistant, frame made of non-woven fibres
  • Optional frame made of plastic, galvanized steel, aluminum
  • Tested to ISO 16890

General information

Application

  • Z-line filter for the separation of coarse and fine dust in ventilation and air conditioning systems
  • Coarse dust filter: Prefilter in ventilation systems
  • Fine dust filter: Prefilter or final filter in ventilation systems

Special features

  • High dust holding capacity at low initial differential pressure
  • Long filter life
  • Quick fitting and removal
  • Low weight and small transport volume
  • Can be easily and safely disposed of in municipal refuse incineration plants as emissions are low in harmful substances

Nominal sizes

  • B × H × T [mm]

Filter classes

Filter groups

  • ISO Coarse to ISO 16890
  • ISO ePM10 to ISO 16890

Filter classes

  • Coarse 90 %
  • ePM10 50 %

Construction

  • NWO: Frame made of non-woven fibres
  • PLA: Frame made of plastic
  • PLAF: Frame made of plastic with 25 mm flange
  • GAL: Frame made of galvanised steel
  • ALU: Frame made of aluminium

Copy of Useful additions

  • Standard cell frame (SCF-B)

Construction features

  • Folded filter media
  • Moisture-resistant, sturdy filter frame made of nonwoven fabric
  • Available in various filter classes and sizes, including commercial installation depths and cross-sections

Materials and surfaces

  • Filter media made of synthetic fibres
  • Frame made of non-woven fibres
  • Optional frame made of plastic, galvanized steel, aluminum

Standards and guidelines

  • Test according to ISO 16890; international standard for general ventilation and air conditioning; classification of arrestance efficiency based on the measured fractional arrestance efficiency, which is processed into a reporting system for the fine dust arrestance efficiency (ePM)
  • For coarse dust filters, the gravimetric separation is measured with synthetic dust
  • The filters are classified into filter group ISO Coarse depending on the tested values
  • For fine dust filters, the fractional arrestance efficiency of a certain size range is determined by aerosols (DEHS and KCl)
  • The filters are classified into filter groups ISO ePM10, ISO ePM2.5 and ISO ePM1 depending on the tested values

TECHNICAL INFORMATION

Technical data, Specification text, Order Code

  • TECHNICAL DATA
  • SPECIFICATION TEXT
  • ORDER CODE

Gravimetric efficiency Coarse [%] according to ISO 1689090
Fractional efficiency ePM10 [%] to ISO 1689050
Nominal face velocity [m/s]2.52.5
Initial differential pressure [Pa] at nominal volume flow rate for T = 48 mm5090
Initial differential pressure [Pa] at nominal volume flow rate for T = 96 mm3570
Maximum operating temperature [°C]8080
Maximum relative humidity [%]100100


Z-line filters type ZL for the separation of coarse dust when used as prefilters, and for the separation of fine dust when used as prefilters or final filters in ventilation systems. Available in various filter classes and sizes, including common installation depths and cross-sections, filter groups ISO Coarse and ISO ePM10 according to ISO 16890. Filter media is folded; this increases the dust holding capacity and extends the filter life.



Special features

  • High dust holding capacity at low initial differential pressure
  • Long filter life
  • Quick fitting and removal
  • Low weight and small transport volume
  • Can be easily and safely disposed of in municipal refuse incineration plants as emissions are low in harmful substances


Materials and surfaces

  • Filter media made of synthetic fibres
  • Frame made of non-woven fibres
  • Optional frame made of plastic, galvanized steel, aluminum


Construction

  • NWO: Frame made of non-woven fibres
  • PLA: Frame made of plastic
  • PLAF: Frame made of plastic with 25 mm flange
  • GAL: Frame made of galvanised steel
  • ALU: Frame made of aluminium


Sizing data

  • Filter group [ISO 16890]
  • Efficiency [%]
  • Volume flow rate [m³/h]
  • Initial differential pressure [Pa]
  • Nominal size [mm]

ZL Coarse90%NWO/592 × 592 × 47
|||||
12345

1 Type
ZL Z-line filters
 
2 Classification
Coarse Gravimetric efficiency according to ISO 16890
ePM10 Fractional efficiency ePM10 according to ISO 16890
 
3 Efficiency [%]
According to ISO 16890
 
4 Construction
NWO Frame made of non-woven fibres
PLA Frame made of plastic
PLAF Frame made of plastic with 25 mm flange
GAL Frame made of galvanised steel
ALU Frame made of aluminium
 
5 Nominal size [mm]
B × H × T

ZL–Coarse–90%–PLA/592×592×48
ClassificationISO Coarse to ISO 16890
Efficiency90 %
ConstructionPlastic frame
Nominal size592 × 592 × 48 mm

Dimensions

  • Dimesions

(1)

Filter class

(2)

(3)

(4)

(5)

B [mm]

H [mm]

T [mm]

qv [l/s]

qv [m³/h]

ΔpA [Pa]

[kg]

394

495

47

Coarse 90 %

488

1755

50

0.7

0.5

495

495

47

Coarse 90 %

613

2205

50

0.9

0.6

287

592

47

Coarse 90 %

432

1555

50

0.7

0.5

592

592

47

Coarse 90 %

885

3185

50

1.4

0.8

394

622

47

Coarse 90 %

613

2205

50

0.9

0.6

495

622

47

Coarse 90 %

769

2770

50

1.2

0.7

394

495

92

Coarse 90 %

488

1755

35

1.5

0.9

495

495

92

Coarse 90 %

613

2205

35

1.9

1.1

287

592

92

Coarse 90 %

432

1555

35

1.3

0.8

592

592

92

Coarse 90 %

885

3185

35

2.7

1.5

394

622

92

Coarse 90 %

613

2205

35

1.9

1.1

495

622

92

Coarse 90 %

769

2770

35

2.4

1.3

394

495

47

ePM10 50 %

488

1755

90

0,7

0.5

495

495

47

ePM10 50 %

613

2205

90

0.9

0.6

287

592

47

ePM10 50 %

432

1555

90

0.7

0.4

592

592

47

ePM10 50 %

885

3185

90

1.4

0.8

394

622

47

ePM10 50 %

613

2205

90

0.9

0.6

495

622

47

ePM10 50 %

769

2770

90

1.2

0.7

394

495

92

ePM10 50 %

488

1755

70

1.5

0.9

495

495

92

ePM10 50 %

613

2205

70

1.9

1.1

287

592

92

ePM10 50 %

432

1555

70

1.3

0.8

592

592

92

ePM10 50 %

885

3185

70

2.7

1.5

394

622

92

ePM10 50 %

613

2205

70

1.9

1.1

495

622

92

ePM10 50 %

769

2270

70

2.4

1.3

Downloads

product information

certificates

production {"X-Frame-Options"=>"SAMEORIGIN", "X-XSS-Protection"=>"1; mode=block", "X-Content-Type-Options"=>"nosniff", "X-Download-Options"=>"noopen", "X-Permitted-Cross-Domain-Policies"=>"none", "Referrer-Policy"=>"strict-origin-when-cross-origin", "Strict-Transport-Security"=>"max-age=31536000; includeSubDomains", "Content-Type"=>"text/html; charset=utf-8"}

Share page

Recommend this page

Recommend this page by sending a link by mail.

Fields marked with an (*) are required fields.

Share page

Thank you for your recommendation!

Your recommendation has been sent and should arrive shortly.

Contact

We are here for you

Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

Attachment (max. 10MB)

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

Contact

We are here for you

Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

Attachment (max. 10MB)

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265