Energy label
SEH Single room exhaust air
SET Single room extract air
SRO Single room outdoor air
SRS Single room supply air
SEC Secondary air
1 Casing
2 Recuperative heat exchanger inspection access panel
3 Inspection access panel for extract air filter ISO coarse 55 %
4 Inspection access panel for outdoor air filter ISO ePM1 65 %
5 Valves including valve actuators
6 Lockshields
7 Condensate drip tray including drain
8 Supply air temperature sensor (optional)
9 Heat exchanger
10 Controls, inspection access panel
11 Connection options for control system by others
12 Levelling feet
13 Fixing brackets
14 Outdoor air temperature sensor (optional)
15 Outdoor air opening including seal
Functional description
Decentralised supply and extract air units with secondary air addition for room ventilation. They cover the cooling and heating load in accordance with the technical data. An EC centrifugal fan takes in the outdoor air and this then flows through the maintenance-free and mechanical self-powered type VFL volume flow limiter, which is pre-set at the factory to the maximum volume flow rate. This ensures maximum limitation of the outdoor air flow rate to a pre-set value for all façade positive pressure situations without an electrical external power supply. The air then flows through the motorised shut-off damper, the self-powered non-return damper and the outdoor air filter. The self-powered non-return dampers in the outdoor air intake and exhaust air outlet prevent the return flow of the conditioned air or undesired airflow directions. Then the outdoor air flows through the cross-flow heat recovery unit, which can be bypassed in energetically sensible operating situations and for unit protection. If necessary, the air is heated or cooled by the heat exchanger before it is supplied into the room as a displacement flow. To increase the heating and cooling capacity, indoor air is added to the supply air by the secondary air fan, thus increasing the supply air flow rate. The extract air first passes through the outdoor air filter, then flows through the heat recovery unit, the extract air fan, the non-return damper and the motorised shut-off damper before it is discharged to the outside as exhaust air. If the indoor air quality is sufficient, the FSL-CONTROL III control system switches to energy-efficient secondary air mode by closing the outdoor air dampers. The control system compares the room air quality setpoint value to the actual value measured by the CO2 sensor and switches automatically between outdoor air and secondary air operation. In case of a power failure, the outdoor air and exhaust air dampers are closed to ensure fire protection, frost protection and to avoid draughts. This is ensured by a capacitor in each actuator. Near the external wall, the supply air is discharged into the room with a medium velocity between 0.5 and 0.8 m/s. Due to the induction effect, the supply air velocity is rapidly reduced so that, in cooling mode, the supply air displaces the room air over the entire floor area. Near heat sources such as people or equipment, a lift current is formed by natural convection, so that the air is exchanged primarily in these areas.
Width | 1150 mm |
Height | 670 mm |
Depth | 320 mm |
Outdoor air flow rate | 60 – 150 m³/h |
Supply air flow rate | 140 – 300 m³/h |
Supply air flow rate | 200 m³/h |
Sound power level | 33 – 50 dB(A) |
Heat recovery efficiency | 60 % |
Maximum operating pressure, water side | 6 bar |
Maximum operating temperature | 75 °C |
Supply voltage | 230 V AC ±10 %, 50/60 Hz |
Supply voltage | 255 VA |
Weight | 75 kg |
Total supply air flow rate | m³/h | 140 | 170 | 200 | 240 | 300 |
Outdoor air flow rate | m³/h | 60 | 90 | 120 | 120 | 150 |
Secondary air volume flow rate | m³/h | 80 | 80 | 80 | 120 | 150 |
Total cooling capacity | W | 490 | 630 | 760 | 850 | 1000 |
Room cooling capacity | W | 374 | 454 | 534 | 625 | 711 |
Air temperature after heat recovery | °C | 28.6 | 29.2 | 29.6 | 29.0 | 29.0 |
Relative humidity | % | 45 | 44 | 44 | 45 | 45 |
Water content of the dry air | g/kg | 11.1 | 11.2 | 11.3 | 11.2 | 11.2 |
Supply air temperature | °C | 18.0 | 18.0 | 18.0 | 18.2 | 18.9 |
Condensate | g/h | 0 | 0 | 0 | 0 | 0 |
Chilled water flow rate | l/h | 115 | 140 | 180 | 200 | 200 |
Water temperature, inlet | °C | 16 | 16 | 16 | 16 | 16 |
Water temperature, outlet | °C | 19.7 | 19.9 | 19.7 | 19.7 | 20.3 |
Water side pressure drop | kPa | 1.5 | 2.0 | 3.0 | 4.0 | 4.0 |
Total heating capacity | W | 1550 | 2050 | 2420 | 2580 | 2990 |
Room heating capacity | W | 706 | 784 | 741 | 922 | 922 |
Air temperature after heat recovery | °C | 5.1 | 1.4 | -1.2 | 2.5 | 2.5 |
Supply air temperature | °C | 36.1 | 34.8 | 32.1 | 32.5 | 30.2 |
Hot water flow rate | l/h | 90 | 140 | 160 | 180 | 200 |
Water temperature, inlet | °C | 60 | 60 | 60 | 60 | 60 |
Water temperature, outlet | °C | 45.0 | 47.2 | 46.8 | 47.5 | 47.0 |
Water side pressure drop | kPa | 1.0 | 2.5 | 3.0 | 3.5 | 4.0 |
Sound power level LWA | dB(A) | 33 | 35 | 38 | 44 | 50 |
Sound pressure level with 8 dB system attenuation | dB(A) | 25 | 27 | 30 | 36 | 42 |
Active power Pel | W | 19 | 20 | 24 | 28 | 38 |
X-CUBE ROOMAIR-B-ZAB+SEK-4-KM/1150x670x320/C3
Under sill units for horizontal assembly on the façade
Please note:
The specification text describes an under sill ventilation unit variant with a single room control system arranged in the unit for autonomous room operation.
The supplied controllers contain the standard control parameters for operation according to our control system description.
FSL-B-ZAB+SEK supply and extract air unit with addition of secondary air - MASTER UNIT
Under sill ventilation unit TROX FSL-B-ZAB+SEK with supply and extract air function and secondary air operation, heat recovery as well as heating and cooling function for installation on an external wall below the window sill:
The front of the device must be completely accessible after disassembly of the outer casing
Units, dimensions and weight:
FSL-CONTROL III controller
Including control system FSL-CONTROL III, as described below:
FSL-CONTROL III is described as a stand-alone single room control system with a simple timer. Optional expansions, such as integration into an on-site MCE/BACS via Modbus TCP, Modbus RTU, BACnet MS/TP or BACnet IP, humidity sensors, return temperature sensors, electromotive valve actuators or pressure-independent control valves, are included in the delivery programme, but must be exchanged for the standard components in the following description. A room temperature signal is also required. Various room control panels and sensors are available to provide this signal. Suitable optional equipment can be found after the following standard equipment for stand-alone operation. - please refer to: Optional control accessories. We recommend commissioning by TROX. You will find related text modules below.
TROX control module FSL-CONTROL III (order code ...-C3-MA ...):
Real time clock (RTC)
Real Time Clock (RTC/real time clock) (order code ...-T/...):
CO2 sensor
CO2 sensor (order code…/C/…):
Supply air temperature sensor
Supply air temperature sensor (order code .../Z/...):
Fresh air temperature sensor
Outdoor air temperature sensor (order code .../A/...):
Water side components
Water-side components (order code…/HV-R-…/KV-R-…):
Valve actuators:
Straight-way valves:
Lockshields:
Optional control accessories
Optional equipment to increase the comfort of the FSL-CONTROL III:
TROX room control panels for FSL-CONTROL III:
At least one room temperature signal is required per room. There are several variants of TROX room control panels available, optionally with or without selector switch. Additionally, we offer a room temperature sensor RTF without control elements. Alternative on-site room control panel must be connected via bus communication.
Digital room control panels for surface mounting:
For operation and adjustment of the ventilation units.
Control panels with selector switch for surface mounting
Control panel with selector switch, type Thermokon, for surface mounting:
Control panels without selector switch for surface mounting
Control panel without selector switch, type Thermokon, for surface mounting:
Room temperature sensor for surface mounting
Room temperature sensor TROX RTF, surface mounting:
Control panels without selector switch for flush mounting:
Manual operation of the ventilation units, high-quality appearance, matching design frames from various switch ranges. The units are particularly suitable for design-oriented interiors.
Control panel without selector switch, type Thermokon, for flush mounting, switch programme Berker S.1, polar white
Control panel without selector switch, type Thermokon, for flush mounting, switch programme Berker Q.3, white
Control panel without selector switch, for flush mounting, type Thermokon, switch from Busch Jäger future linear range, white
Control panels without selector switch and without setpoint value adjuster, for flush mounting:
Control panel without selector switch and without setpoint value adjuster, type Thermokon, for flush mounting, switch programme Gira E2
Electromotive valve actuators as an alternative to the thermoelectric actuators installed as standard:
Pressure-independent control valves as an alternative to the small straight-way valves installed as standard:
Interface for integration into an on-site MCE/BACS:
Modbus TCP interface including web server (order code .../MT/...)
To increase convenience, we recommend integration into an on-site MCE/BACS or visualisation with X-TAIRMINAL. FSL-CONTROL III can be integrated into an on-site MCE/BACS via the Modbus TCP protocol. Additionally including web server for simplified configuration, commissioning and remote monitoring of the unit. The MCE/BACS is not included in the supply package from TROX GmbH, only the interfaces listed above are available here.
BACnet IP interface including web server (order code .../BI/...):
To increase convenience, we recommend integration into an on-site MCE/BACS. FSL-CONTROL III offers the option of being integrated into an on-site MCE/BACS via the BACnet IP protocol. Additionally including web server for simplified configuration, commissioning and remote monitoring of the unit. The MCE/BACS is not included in the supply package from TROX GmbH, only the interfaces listed above are available here.
Modbus RTU (order code .../MR/...)
To increase convenience, we recommend integration into an on-site MCE/BACS. FSL-CONTROL III offers the option of being integrated into an on-site MCE/BACS via Modbus RTU. The MCE/BACS is not included in the supply package from TROX GmbH, only the interfaces listed above are available here.
BACnet MS/TP (order code .../BM/...)
To increase convenience, we recommend integration into an on-site MCE/BACS. FSL-CONTROL III offers the option of being integrated into an on-site MCE/BACS via BACnet MS/TP. The MCE/BACS is not included in the supply package from TROX GmbH, only the interfaces listed above are available here.
Version as SLAVE DEVICE
Identical to the MASTER DEVICE, as described above, but with the following deviations:
Commissioning of the decentralised ventilation units
Commissioning/parameterisation of the decentralised ventilation units without integration into an on-site MCE/BACS
Commissioning/parameterisation of the decentralised ventilation units with integration into an on-site MCE/BACS
Instruction in operation and maintenance
RA-B-ZAB+SEK | – | 4 | – | 1 | – | KR | / | 1150 × 670 × 320 | / | C3 | – | MA | – | T | / | MR | / | C | / | Z | / | A | / | HV | – | R | – | 0.40 | / | KV | – | R | – | 0.40 |
| | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |||||||||||||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 15 | 16 | 17 | 18 | |||||||||||||||||
1 Type
RA-B-ZAB+SEK horizontal decentralised sill ventilation unit with 3 fans X-CUBE/ROOMAIR-B-ZAB+SEK
2 Heat exchanger
2 2-pipe
4 4-pipe
3 Heat recovery construction
Specify design (technical design with TROX EPF or TROX CONFIGURATOR)
4 Construction
KR with condensate drain and water connection right
5 Nominal size [mm]
Width × height × depth
1150 × 670 × 320
6 Control system
OR without control system
C3 with FSL-CONTROL III
7 Control function
MA Master
SL Slave
8 Real time clock
Only with control function MA
No entry: without real time clock
T with real time clock
9 Interface
No entry: without interface
MT with Modbus TCP
MR with Modbus RTU (only with control function MA)
BI with BACnet IP
BM with BACnet MS/TP (only with control function MA)
10 Air quality sensor
Only with control function MA
No entry: without air quality sensor
C with CO2 sensor
V with VOC sensor
11 Supply air temperature sensor
Z with supply air temperature sensor
12 Outdoor air temperature sensor
Only with control function MA
No entry: without outdoor air temperature sensor
A with outdoor air temperature sensor
13 Heating valve
HV with thermoelectric actuator
HVE with electromotive actuator
14 Lockshield – heating circuit
R with lockshield
15 kVS value – heating valve
0.25 (straight-way valve)
0.40 (straight-way valve)
0.63 (straight-way valve)
1.00 (straight-way valve)
F0.50 (pressure-independent control valve)
16 Cooling valve
With heat exchanger '4' only
KV with thermoelectric actuator
KVE with electromotive actuator
17 Lockshield – cooling circuit
With heat exchanger '4' only
R with lockshield
18 kVS value – cooling valve
With heat exchanger '4' only
0.25 (straight-way valve)
0.40 (straight-way valve)
0.63 (straight-way valve)
1.00 (straight-way valve)
F0.50 (pressure-independent control valve)
Type | RA-B-ZAB+SEK – horizontal decentralised sill ventilation unit with 3 fans X-CUBE/ROOMAIR-B-ZAB+SEK | |
Heat exchanger | 4-pipe | |
Heat exchanger construction | Heat exchanger type 1 | |
Construction | with condensate drain and water connection right | |
Nominal size [mm] | Width 1150, height 670, depth 320 | |
Control system | with FSL-CONTROL III | |
Control function | Master | |
Real time clock | with real time clock | |
Interface | with Modbus RTU | |
Air quality sensor | with CO2sensor | |
Supply air temperature sensor | with supply air temperature sensor | |
Outdoor air temperature sensor | with outdoor air temperature sensor | |
Heating valve | with thermoelectric actuator | |
Lockshield – heating circuit | with lockshield | |
kVS value – heating valve | 0.40 (straight-way valve) | |
Cooling valve | with thermoelectric actuator | |
Lockshield – cooling circuit | with lockshield | |
kVS value – cooling valve | 0.40 (straight-way valve) | |
Share page
Recommend this page
Recommend this page by sending a link by mail.
Share page
Thank you for your recommendation!
Your recommendation has been sent and should arrive shortly.
Contact
We are here for you
Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
We are here for you
Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265