Application
Special features
Nominal sizes
Variants
Parts and characteristics
Accessories
Construction features
Materials and surfaces
Maintenance
1 Casing with flange holes (KUL-G)
2 Blades (closed)
3 Mullion from B = 997 mm
4 Travel stop (angle section)
5 Blades (open)
6 Blade restrictor
7 Blade tip seals
8 Side bar
Non-return dampers open and close automatically. When the system is in operation, the blades open when air flows. When the system is shut down, the blades close due to their weight. They safely prevent air from flowing against the intended airflow direction.
Flow cross section to calculate the airflow velocity
Unit of measure for B and H: m
Weight [kg]
H | B | |||||||||
---|---|---|---|---|---|---|---|---|---|---|
200 | 300 | 400 | 500 | 600 | 800 | 1000 | 1200 | 1400 | 1600 | |
215 | 2 | 3 | 3 | 4 | 4 | 5 | 6 | 8 | 10 | 11 |
315 | 2 | 3 | 4 | 4 | 5 | 6 | 7 | 9 | 10 | 11 |
415 | 3 | 4 | 4 | 5 | 6 | 7 | 8 | 10 | 11 | 13 |
515 | 3 | 4 | 5 | 6 | 6 | 7 | 9 | 11 | 12 | 15 |
615 | 4 | 5 | 5 | 6 | 7 | 8 | 10 | 12 | 13 | 17 |
715 | 4 | 5 | 6 | 7 | 8 | 8 | 11 | 13 | 15 | 18 |
815 | 5 | 6 | 6 | 8 | 9 | 9 | 13 | 16 | 17 | 19 |
1015 | 5 | 6 | 7 | 9 | 10 | 11 | 15 | 18 | 19 | 20 |
1215 | 6 | 7 | 7 | 10 | 11 | 13 | 17 | 20 | 20 | 22 |
1415 | 6 | 7 | 8 | 11 | 12 | 15 | 18 | 21 | 22 | 24 |
1615 | 7 | 8 | 8 | 11 | 13 | 17 | 19 | 22 | 24 | 26 |
B | No. of holes n |
---|---|
200 – 346 | 2 |
347 – 496 | 3 |
497 – 646 | 4 |
647 – 796 | 5 |
797 – 946 | 6 |
947 – 1096 | 7 |
1097 – 1246 | 8 |
1247 – 1396 | 9 |
1397 – 1546 | 10 |
1547 – 1600 | 11 |
KUL_G: Height, no. of flange holes
H | No. of holes n |
---|---|
215 – 362 | 2 |
363 – 512 | 3 |
513 – 662 | 4 |
663 – 812 | 5 |
813 – 962 | 6 |
963 – 1112 | 7 |
1113 – 1262 | 8 |
1263 – 1412 | 9 |
1413 – 1562 | 10 |
1563 – 1615 | 11 |
Installation and commissioning
The airflow downstream of a fan is characterised by strong turbulence, and there is no uniform velocity profile. As a consequence, the blades of the non-return dampers are not uniformly subject to the airflow, and this may result in individual blades becoming subject to forces that might lead to mechanical damage.
Safe operation requires a straight upstream section of at least B + H.
Share page
Recommend this page
Recommend this page by sending a link by mail.
Share page
Thank you for your recommendation!
Your recommendation has been sent and should arrive shortly.
Contact
We are here for you
Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
We are here for you
Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265