TJN with swirl unit and cap for throw distance reduction
Application
Special features
Nominal sizes
Variants
Connection
Actuator
Parts and characteristics
Attachments
Accessories
Construction features
Materials and surfaces
Standards and guidelines
Maintenance
Jet nozzles are the preferred solution wherever the supply air has to travel large distances from the point of discharge to the occupied zone. It is possible to adapt the discharge angle, and consequently the direction of the airflow, to heating or cooling mode. The supply air to room air temperature difference can be -12 - +20 K.
Cooling mode
Cooling mode is possible with a positive discharge angle of up to 30°. The supply air jet is directed towards the ceiling, but the higher density of cold air results in an increasing deflection of the air jet towards the floor as the distance from the jet nozzle increases. When the supply air jet reaches the occupied zone, both the supply air to room air temperature difference and the airflow velocity have been reduced to comfortable levels. This principle of operation allows for long throw distances.
Heating mode
Heating operation is possible with a negative discharge angle of -30° or less. The supply air jet is directed towards the occupied zone. Due to the lower density of warm air, the jet becomes buoyant. When the supply air jet reaches the occupied zone, both the supply air to room air temperature difference and the airflow velocity should ideally have been reduced.
The discharge angle can be changed manually or with a thermal or electric actuator.
A swirl unit and cap (optional) allow for reducing the throw distance to 65 % or 75 %.
Nominal sizes | 160, 200, 250, 315, 400 mm |
Volume flow rate range | 20 – 1000 l/s or 72 – 3600 m³/h |
Adjustable discharge angle | -30 – +30° |
Supply air to room air temperature difference | -12 to +20 K |
Quick sizing tables provide a good overview of the volume flow rates and corresponding sound power levels and differential pressures.
Exact values for all parameters can be determined with our Easy Product Finder design program.
Sound power level and total differential pressure
NS | qv [l/s] | qv (m³/h) | Δpt [Pa] | LWA [dB(A)] | vL | |
---|---|---|---|---|---|---|
0.5 m/s | 1.0 m/s | |||||
L [m] | L | |||||
160 | 20 | 72 | 9 | < 15 | < 5 | < 5 |
40 | 144 | 34 | < 15 | 8 | < 5 | |
60 | 216 | 76 | 15 | 13 | 6 | |
80 | 288 | 135 | 26 | 17 | 8 | |
200 | 35 | 126 | 9 | < 15 | 6 | < 5 |
70 | 252 | 35 | < 15 | 11 | 6 | |
105 | 378 | 78 | 19 | 17 | 9 | |
140 | 504 | 138 | 30 | 23 | 11 | |
250 | 55 | 198 | 8 | < 15 | 7 | < 5 |
110 | 396 | 33 | < 15 | 14 | 7 | |
165 | 594 | 75 | 21 | 21 | 11 | |
220 | 792 | 132 | 33 | 28 | 14 | |
315 | 90 | 324 | 8 | < 15 | 9 | < 5 |
185 | 666 | 35 | < 15 | 18 | 9 | |
265 | 954 | 71 | 24 | 26 | 13 | |
360 | 1296 | 132 | 36 | > 30 | 18 | |
400 | 155 | 558 | 8 | < 15 | 12 | 6 |
310 | 1116 | 33 | < 15 | 24 | 12 | |
465 | 1674 | 75 | 27 | > 30 | 18 | |
620 | 2232 | 133 | 38 | > 30 | 24 |
All values apply to discharge angle 0°
L: Throw distance with isothermal operation, no throw distance reduction
Adjustable jet nozzles for the ventilation of large internal spaces such as halls and assembly rooms. Air discharge with long throw distance, excellent acoustic properties. Nozzles tilt vertically from –30 - +30° for horizontal air discharge. Discharge angle indication, discharge angle limiting and setting on a concealed scale.
Consists of a casing for the spherical discharge nozzle, flange, face cover ring and nozzle.
For push fitting directly onto circular ducts or as a branch off circular or rectangular ducts.
Special features
Maintenance
Materials and surfaces
TJN | – | R | – | E7 | / | 160 | – | 315 | / | C | / | D | / | S1 |
| | | | | | | | | | | | | | | | |||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | |||||||
Type | TJN |
Connection piece | For rectangular ducts |
Actuator | Modulating, 2 – 10 V DC, 24 V AC |
Nominal size | 250 mm |
Attachments | Outer casing |
Accessories | Swirl unit and cap for throw distance reduction |
Exposed surface | White aluminium, similar to RAL 9006 |
NS | TJN | TJN-E* | TJN-T1 | ||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
L2 | m [kg] | L2 | m [kg] | L2 | m [kg] | ØD1 | L1 | ØD4 | ØD | C | |
160 | 192 | 1.9 | 192 | 2.1 | 252 | 2.3 | 258 | 15 | 227 | 158 | 50 |
200 | 200 | 2.3 | 200 | 2.5 | 260 | 2.8 | 298 | 14 | 263 | 198 | 50 |
250 | 210 | 3.1 | 210 | 3.3 | 270 | 3.7 | 348 | 14 | 315 | 248 | 50 |
315 | 225 | 4.0 | 225 | 4.2 | 285 | 4.8 | 413 | 15 | 379 | 313 | 50 |
400 | 235 | 4.6 | 235 | 4.8 | 295 | 5.5 | 501 | 16 | 468 | 398 | 50 |
TJN/.../C
NS | TJN/.../C | TJN-E*/.../C | TJN-T1/.../C | ||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
L2 | m [kg] | L2 | m [kg] | L2 | m [kg] | ØD1 | L1 | ØD3 | ØD | C | |
160 | 192 | 2.7 | 192 | 2.9 | 252 | 3.4 | 258 | 15 | 228 | 158 | 50 |
200 | 200 | 3.4 | 200 | 3.6 | 260 | 4.2 | 298 | 14 | 265 | 198 | 50 |
250 | 210 | 4.4 | 210 | 4.6 | 270 | 5.3 | 348 | 14 | 316 | 248 | 50 |
315 | 225 | 5.8 | 225 | 6.0 | 285 | 7.0 | 413 | 15 | 381 | 313 | 50 |
400 | 235 | 8.0 | 235 | 8.2 | 295 | 9.5 | 501 | 16 | 469 | 398 | 50 |
NS | TJN-K | TJN-K-T1 | TJN-E*/.../C | ||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
L2 | m [kg] | L2 | m [kg] | L2 | m [kg] | ØD1 | L1 | ØD4 | ØD | C | |
160 | 248 | 2.1 | 308 | 2.5 | 248 | 2.3 | 258 | 15 | 227 | 158 | 50 |
200 | 257 | 3.2 | 317 | 3.7 | 257 | 3.4 | 298 | 14 | 263 | 198 | 50 |
250 | 265 | 3.4 | 325 | 4.0 | 265 | 3.6 | 348 | 14 | 315 | 248 | 50 |
315 | 281 | 4.6 | 341 | 5.4 | 281 | 4.8 | 413 | 15 | 379 | 313 | 50 |
400 | 292 | 6.5 | 352 | 7.4 | 292 | 6.7 | 501 | 16 | 468 | 398 | 50 |
NS | TJN-K/.../C | TJN-K-E*/.../C | TJN-K-T1/.../C | ||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
L2 | m [kg] | L2 | m [kg] | L2 | m [kg] | ØD1 | L1 | ØD3 | ØD | C | |
160 | 258 | 3.5 | 258 | 3.7 | 318 | 4.2 | 258 | 15 | 228 | 158 | 50 |
200 | 267 | 4.3 | 267 | 4.5 | 327 | 5.1 | 298 | 14 | 265 | 198 | 50 |
250 | 276 | 5.5 | 276 | 5.7 | 336 | 6.4 | 348 | 14 | 316 | 248 | 50 |
315 | 291 | 7.2 | 291 | 7.4 | 351 | 8.4 | 413 | 15 | 381 | 313 | 50 |
400 | 302 | 9.9 | 302 | 10.1 | 362 | 11.4 | 501 | 16 | 469 | 398 | 50 |
NS | TJN-R | TJN-R-E* | TJN-R-T1 | ||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
L2 | m [kg] | L2 | m [kg] | L2 | m [kg] | ØD1 | L1 | ØD4 | ØD | C | |
160 | 248 | 2.1 | 248 | 2.3 | 308 | 2.5 | 258 | 15 | 227 | 158 | 50 |
200 | 257 | 3.2 | 257 | 3.4 | 317 | 3.7 | 298 | 14 | 263 | 198 | 50 |
250 | 265 | 3.4 | 265 | 3.6 | 325 | 4.0 | 348 | 14 | 315 | 248 | 50 |
315 | 281 | 4.6 | 281 | 4.8 | 341 | 5.4 | 413 | 15 | 379 | 313 | 50 |
400 | 292 | 6.5 | 292 | 6.7 | 352 | 7.4 | 501 | 16 | 468 | 398 | 50 |
NS | TJN-R/.../C | TJN-R-E*/.../C | TJN-R-T1/.../C | ||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
L2 | m [kg] | L2 | m [kg] | L2 | m [kg] | ØD1 | L1 | ØD3 | ØD | C | |
160 | 261 | 3.5 | 261 | 3.7 | 321 | 4.2 | 258 | 15 | 228 | 158 | 50 |
200 | 270 | 4.3 | 270 | 4.5 | 330 | 5.1 | 298 | 14 | 265 | 198 | 50 |
250 | 279 | 5.5 | 279 | 5.7 | 339 | 6.4 | 348 | 14 | 316 | 248 | 50 |
315 | 294 | 7.2 | 294 | 7.4 | 354 | 8.4 | 413 | 15 | 381 | 313 | 50 |
400 | 305 | 9.9 | 305 | 10.1 | 365 | 11.4 | 501 | 16 | 469 | 398 | 50 |
NS | 315 | 500 | 630 | 800 |
---|---|---|---|---|
160 | + | + | + | + |
200 | + | + | + | |
250 | + | + | + | |
315 | + | + | + | |
400 | + | + |
Installation and commissioning
The illustrations are schematic and serve to create a better understanding of the installation details.
TJN
NS | ØD1 | ØD2 | Aeff [m2] |
---|---|---|---|
160 | 258 | 82 | 0.00500 |
200 | 298 | 108 | 0.00850 |
250 | 348 | 136 | 0.0135 |
315 | 413 | 174 | 0.0225 |
400 | 501 | 231 | 0.0385 |
Share page
Recommend this page
Recommend this page by sending a link by mail.
Share page
Thank you for your recommendation!
Your recommendation has been sent and should arrive shortly.
Contact
We are here for you
Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
We are here for you
Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265