Plug and play connection of components
Application
Special features
Alternatives
Parts and characteristics
Accessories
Construction features
Materials and surfaces
Useful additions
1 Zone module
2 Module for zone expansion
3 Volume flow control
4 Heating, e.g. with a heating coil
5 Cooling, e.g. with an active chilled beam
6 Room control panel
7 Temperature sensor
8 Air quality sensor
9 Motion detector
10 Humidity sensor
Note:
Components 2 to 10 are optional (maximum equipment).
Functional description
Zone modules are electronic control components for single room control. They control temperature, air quality and humidity, based on demand and based on occupancy.
A zone module controls the air terminal units for supply air and extract air, and a heating valve and a cooling valve.
A room control panel is used to operate a zone module.
A single room control system can be expanded by centralised functions if a zone master is used. One zone master module and up to 25 zone modules form a segment. Up to 5 cascading zone master modules form a section with up to 125 zone modules.
There are two ways to configure and operate the system:
Volume flow control
The X-AIR-ZMO-MP zone module activates up to 4 electronic volume flow controllers (2 for supply air, 2 for extract air) and provides the volume flow rate setpoint value. The actual volume flow control is handled by a volume flow controller.
The volume flow rate setpoint value depends on the operating mode, the number of air terminal units and the respective nominal volume flow rates. Parameters that are stored in the volume flow controller, e.g. qVmin and qVmax, are automatically read and evaluated by a zone module.
The operating mode default can be set either on the zone master module (i.e. centrally) or on the room control panel.
Operating modes
Operating modes set on the X-AIR-CP-2T control panel apply only for a defined period of time. After this period has elapsed, the zone returns to Automatic mode. Shut-off remains active until a user changes the operating mode again.
Damper blade positions and volume flow rate actual values of the air terminal units are signalled to the zone module and then forwarded to higher-level systems; the purpose is energy-efficient fan control.
Temperature control
A sensor measures the room temperature or extract air temperature, which is constantly compared to the setpoint value. In case of any deviation, the system controls airflows and/or water flows in such a way that the required room temperature is achieved (again). Variants:
It is also possible to combine room temperature control and supply air temperature control (cascade). With this type of control, the deviation from the room temperature is used to determine the supply air temperature setpoint. In addition, the supply air temperature is limited by a minimum value and a maximum value (can be configured).
Larger zones can be equipped with another 2 temperature sensors. The target value will then be the average value.
Air quality control
The air quality is measured with an air quality sensor (VOC or CO2) placed in the room or in the extract air. If the measured contaminant content exceeds a certain value, the system keeps increasing the supply and extract air flows until the air quality improves. If a zone is fitted with heating or cooling valves, the system activates these valves in order to control the room temperature.
Humidity control
A sensor measures the relative humidity of the extract air; the value is then compared to a threshold value. If the relative humidity exceeds the threshold value, the system keeps increasing the supply and extract air flows in order to decrease the humidity in the room.
If a zone is fitted with heating or cooling valves, the system activates these valves in order to control the room temperature.
Window contact and frost protection
The zone module has a volt-free digital input for the connection of a window contact or a frost protection sensor. It is possible to connect a dew point sensor instead of a window contact. Users can choose how to use the digital input:
The damper blades of the air terminal units, the heating valve and the cooling valve close.
The cooling valve closes so that condensation is prevented. Volume flow control remains unaffected.
The heating valve opens fully to protect the heat exchangers. Volume flow control remains unaffected.
Motion detector
Another volt-free digital input is available for the connection of a motion detector (X-SENS-PIR-SM, X-SENS-PIR-FM). The volume flow rate is controlled as long as a room is occupied. If the room becomes unoccupied, volume flow control ends after a set switch-off delay, which can be configured.
Operating mode
1 Connection for the supply voltage
2 Analogue inputs for sensors
3 Analogue input for setpoint value adjuster
4 digital inputs
5 Zone modules, Modbus out
6 Modbus sensors
7 Display
8 Analogue input for temperature sensor
9 MP bus actuators
10 Zone modules, Modbus in
Share page
Recommend this page
Recommend this page by sending a link by mail.
Share page
Thank you for your recommendation!
Your recommendation has been sent and should arrive shortly.
Contact
We are here for you
Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
We are here for you
Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265