For square diffuser faces
Application
Special features
Variants
Parts and characteristics
Attachments
Accessories
Construction features
Materials and surfaces
Maintenance
Parts and characteristics
Accessories
Construction features
Variants
Plenum boxes are used to connect ceiling diffusers to circular ducts and to fix the diffuser face. Type AK-Uni plenum boxes are fitted with an equalising element that ensures that the air is evenly distributed to the room. A damper blade (optional) simplifies volume flow rate balancing for commissioning. Pressure tap and cord-operated damper blade (optional) allow for volume flow rate balancing with the diffuser face in place.
The following technical data applies for supply air. The K values can be used to calculate the corresponding reference pressure drops for the volume flow rate to be set.
Supply air
Plenum boxes for square diffuser faces
Standard combinations
Variant | Diffuser face variant | |||||||
---|---|---|---|---|---|---|---|---|
VDW-Q | TDV-SA-Q | FD-Q | TDF-SA-Q | |||||
Nominal size | K value | Nominal size | K value | Nominal size | K value | Nominal size | K value | |
AK-Uni-001 | 300 × 8 | 36.9 | 300 | 47.7 | 300 | 36.5 | 300 | 47.7 |
AK-Uni-002 | 400 × 16 | 70.7 | 400 | 82.1 | 400 | 70.7 | 400 | 82.1 |
AK-Uni-003 | 500 × 24 | 87.1 | 500 | 100.5 | 500 | 92.7 | 500 | 100.5 |
AK-Uni-004 | 600 × 24 | 125.8 | 600 625 | 145.5 | 600 625 | 125.8 | 600 625 | 145.5 |
AK-Uni-005 | 600 × 48 | 154.8 | 158.9 | |||||
AK-Uni-006 | 625 × 54 | 158.9 | ||||||
AK-Uni-007 | 825 × 72 | 262.2 |
Standard combinations
Variant | Diffuser face variant | |||||
---|---|---|---|---|---|---|
ADD-Q | ADLQ DLQ | ADLR-Q | ||||
Nominal size | K value | Nominal size | K value | Nominal size | K value | |
AK-Uni-002 | 400 | 108.2 | ||||
AK-Uni-008 | 250 | 36.2 | ||||
AK-Uni-009 | 300 | 53.4 | ||||
AK-Uni-011 | 600 | 260.0 | ||||
AK-Uni-010 | 500 | 173.7 | ||||
AK-Uni-019 | 250 | 27.4 | 1 | 29.8 | ||
AK-Uni-020 | 300 | 52.2 | 2 | 53.3 | ||
AK-Uni-021 | 400 | 79.9 | 3 | 86.2 | ||
AK-Uni-022 | 450 | 128.7 | 4 | 128.7 | ||
AK-Uni-023 | 500 | 143.4 | 5 | 150.6 | ||
AK-Uni-024 | 6 | 206.8 | ||||
AK-Uni-025 | 600 625 | 245.7 | 7 | 231.9 | ||
AK-Uni-026 | 8 | 254.7 |
Alternative combinations
Variant | Diffuser face variant | |||||
---|---|---|---|---|---|---|
VDW-Q | FD-Q | ADLQ DLQ | ||||
Nominal size | K value | Nominal size | K value | Nominal size | K value | |
AK-Uni-004 | 600< | 182.4 | ||||
AK-Uni-005 | 600 × 24 625 × 24 | 125.8 | 600 625 | 125.8 | 600< 625< | 182.4 |
AK-Uni-006 | 625 × 24 | 125.8 | 625 | 125.8 | 625< | 182.4 |
AK-Uni-010 | 500 × 24> | 104.1 | 500> | 103.5 | ||
AK-Uni-011 | 600 × 24> 625 × 24> | 141.9 | 600> 625> | 141.9 | ||
AK-Uni-012 | 600 × 24> 625 × 24> | 141.9 | 600< 625< | 141.9 | 600 625 | 260.0 |
AK-Uni-012 | 600 × 48> | 182.0 | ||||
AK-Uni-027 | 625 × 24> | 141.9 | 625> | 141.9 | 625 | 260.0 |
AK-Uni-027 | 625 × 54> | 191.4 | 82.1 |
< Spigot smaller than in the case of the standard plenum box
< Spigot larger than in the case of the standard plenum box
Plenum boxes for circular diffuser faces
Standard combinations
Variant | Diffuser face variant | |||
---|---|---|---|---|
TDV-SA-R | ADLR | |||
Nominal size | K value | Nominal size | K value | |
AK-Uni-013 | 300 | 47.7 | ||
AK-Uni-014 | 400 | 82.1 | ||
AK-Uni-015 | 500 | 100.5 | ||
AK-Uni-016 | 600 625 | 145.5 | ||
AK-Uni-019 | 1 | 29.8 | ||
AK-Uni-020 | 2 | 53.3 | ||
AK-Uni-021 | 3 | 86.2 | ||
AK-Uni-022 | 4 | 128.7 | ||
AK-Uni-023 | 5 | 150.6 | ||
AK-Uni-024 | 6 | 206.8 | ||
AK-Uni-025 | 7 | 231.9 | ||
AK-Uni-026 | 8 | 254.7 |
Alternative combinations
Variant | Diffuser face variant | |||||||
---|---|---|---|---|---|---|---|---|
VDW-R | FD-R | TDF-SA-R | ADLR | |||||
Nominal size | K value | Nominal size | K value | Nominal size | K value | Nominal size | K value | |
AK-Uni-013 | 300 × 8 | 33.8 | 300 | 36.5 | 300 | 47.7 | 2 | 53.3 |
AK-Uni-014 | 400 × 16 | 70.7 | 400 | 70.7 | 400 | 82.1 | 4> | 112.6 |
AK-Uni-015 | 500 × 24 | 83.0 | 500 | 94.4 | 500 | 100.5 | ||
AK-Uni-016 | 600 × 24 625 × 24 | 124.3 | 600 625 | 124.3 | 600 625 | 145.5 | 7< | 184.1 |
AK-Uni-017 | 600 × 48 | 158.3 | ||||||
AK-Uni-017 | 600 × 24 625 × 24 | 124.3 | 600 625 | 124.3 | 7 | 184.1 | ||
AK-Uni-018 | 625 × 24 | 122.5 | 625 | 122.5 | 8< | 183.9 | ||
AK-Uni-022 | 400 × 16> | 67.1 | 400> | 67.1 | ||||
AK-Uni-024 | 500 × 24> | 101.3 | 500> | 111.8 | ||||
AK-Uni-025 | 600 × 24> 625 × 24> | 131.4 | 600> 625> | 131.4 | ||||
AK-Uni-025 | 600 × 48> | 186.0 | ||||||
AK-Uni-026 | 625 × 24> | 129.9 | 625> | 129.9 |
< Spigot smaller than in the case of the standard plenum box
< Spigot larger than in the case of the standard plenum box
Plenum boxes for Type RFD diffuser faces
Standard combinations
Variant | Nominal size | RFD without discharge nozzle | RFD with discharge nozzle |
---|---|---|---|
K value | |||
AK-Uni-028 | 125 | 12.4 | 17.9 |
AK-Uni-029 | 160 | 18.7 | 26.3 |
AK-Uni-030 | 200 | 25.5 | 43.9 |
AK-Uni-031 | 250 | 46.4 | 68.4 |
AK-Uni-032 | 315 | 82.0 | 103.0 |
AK-Uni-033 | 400 | 124.3 | 134.4 |
This specification text describes the general properties of the product. Texts for variants can be generated with our Easy Product Finder design program.
Specification text
Square plenum boxes for the connection of square and to some extent circular diffuser faces to circular ducts, suitable for supply air or extract air applications. For installation into all kinds of suspended ceilings. Ready-to-install component which consists of the plenum box, permanent equalising element (only supply air variants), side entry spigot, cross bar, and suspension holes. The diffuser face is fixed to the cross bar with a central screw, concealed by a decorative cap. Spigot suitable for ducts to EN 1506 or EN 13180.
Special features
Materials and surfaces
AK-Uni | – | 002 | – | ZL | – | M | – | L |
| | | | | | | | | | ||||
1 | 2 | 3 | 4 | 5 | ||||
1 Type
AK-Uni Plenum box
2 Variant
001 – 033
3 System
ZL Supply air
AL Extract air
4 Damper blade for volume flow rate balancing
No entry required: None
M With
MN With cord and pressure tap
5 Accessories
No entry required: None
L with lip seal
Variant | 003 |
Air conditioning system | Supply air |
Damper unit for volume flow rate balancing | Volume flow rate adjustment with cords and pressure tap |
Accessories | With lip seal |
Variant | ØD | □Q3 | H3 | A | C | m |
---|---|---|---|---|---|---|
mm | kg | |||||
AK-Uni-001 | 158 | 290 | 250 | 139 | 50 | 3.0 |
AK-Uni-002 | 198 | 372 | 295 | 164 | 50 | 4.5 |
AK-Uni-003 | 198 | 476 | 295 | 164 | 50 | 6.0 |
AK-Uni-004 | 248 | 567 | 345 | 199 | 48 | 8.2 |
AK-Uni-005 | 248 | 590 | 345 | 189 | 48 | 8.6 |
AK-Uni-006 | 248 | 615 | 345 | 189 | 48 | 9.0 |
AK-Uni-007 | 313 | 806 | 410 | 222 | 50 | 16.0 |
AK-Uni-008 | 158 | 216 | 250 | 139 | 50 | 2.2 |
AK-Uni-009 | 158 | 266 | 250 | 139 | 50 | 2.7 |
AK-Uni-010 | 248 | 476 | 345 | 189 | 48 | 6.6 |
AK-Uni-011 | 313 | 567 | 410 | 222 | 50 | 9.2 |
AK-Uni-012 | 313 | 590 | 410 | 222 | 50 | 9.6 |
AK-Uni-027 | 313 | 615 | 410 | 222 | 50 | 10.2 |
AK-Uni for circular diffuser faces
Variant | □Q3 | H3 | ØD4 | H4 | ØD | A | C | m |
---|---|---|---|---|---|---|---|---|
mm | kg | |||||||
AK-Uni-013 | 290 | 285 | 278 | 250 | 158 | 174 | 50 | 3.4 |
AK-Uni-014 | 372 | 330 | 362 | 295 | 198 | 199 | 50 | 5.1 |
AK-Uni-015 | 476 | 330 | 460 | 295 | 198 | 199 | 50 | 6.9 |
AK-Uni-016 | 567 | 380 | 557 | 345 | 248 | 234 | 48 | 9.3 |
AK-Uni-017 | 590 | 380 | 578 | 345 | 248 | 224 | 48 | 9.7 |
AK-Uni-018 | 615 | 380 | 590 | 345 | 248 | 224 | 48 | 10.3 |
AK-Uni-019 | 266 | 255 | 202 | 220 | 123 | 161 | 48 | 2.9 |
AK-Uni-020 | 290 | 285 | 258 | 250 | 158 | 174 | 50 | 3.5 |
AK-Uni-021 | 372 | 330 | 314 | 295 | 198 | 199 | 50 | 5.2 |
AK-Uni-022 | 476 | 380 | 362 | 345 | 248 | 224 | 48 | 7.8 |
AK-Uni-023 | 476 | 380 | 426 | 345 | 248 | 224 | 48 | 7.6 |
AK-Uni-024 | 567 | 445 | 482 | 410 | 313 | 257 | 50 | 10.5 |
AK-Uni-025 | 590 | 445 | 578 | 410 | 313 | 257 | 50 | 10.8 |
AK-Uni-026 | 615 | 445 | 590 | 410 | 313 | 257 | 50 | 11.4 |
AK-Uni for type RFD and TID diffuser faces
Variant | □Q3 | H3 | ØD4 | H4 | ØD | A | C | m |
---|---|---|---|---|---|---|---|---|
mm | kg | |||||||
AK-Uni-028 | 216 | 255 | 125 | 195 | 98 | 170 | 50 | 2.5 |
AK-Uni-029 | 266 | 280 | 160 | 220 | 123 | 182 | 48 | 3.0 |
AK-Uni-030 | 290 | 310 | 200 | 250 | 158 | 194 | 50 | 3.5 |
AK-Uni-031 | 476 | 355 | 250 | 295 | 198 | 219 | 50 | 7.5 |
AK-Uni-032 | 567 | 395 | 315 | 345 | 248 | 244 | 48 | 10.0 |
AK-Uni-033 | 615 | 470 | 400 | 410 | 313 | 277 | 50 | 12.0 |
For low construction heights in the suspended ceiling, plenum boxes with 2 smaller spigots are also available, which have a lower
installation height
Commissioning
Volume flow rate balancing
When several diffusers are connected to just one volume flow controller, it may be necessary to balance the volume flow rates.
Volume flow rate measurement
Ceiling diffusers with square plenum box, damper unit and pressure tap (variant -MN) enable volume flow rate balancing with the diffuser face in place.
A characteristic is included with each AK-Uni plenum box.
These are only schematic diagrams to illustrate installation details.
Share page
Recommend this page
Recommend this page by sending a link by mail.
Share page
Thank you for your recommendation!
Your recommendation has been sent and should arrive shortly.
Contact
We are here for you
Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
We are here for you
Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265