BACnet interface
Application
The expansion module EM-BAC-MOD supports the following interface functions on an EASYLAB controller TCU3 or an adapter module TAM if the BACnet protocol has been selected:
- Native BACnet, i.e. the BACnet interface is implemented on the field module (EASYLAB volume flow controller)
- External hardware components such as physical gateways are not required
- BACnet interface documentation includes the following documents: Protocol Implementation Conformance Statement (PICS), BACnet Interoperability Building Blocks Supported (BIBBS), as well as a description of the device object and the supported objects
- For more information on each data point see the Details section
BACnet PICS (Protocol Implementation Conformance Statement) – Overview
Principal categories
|
Values
|
Date
|
2014-01-21
|
Vendor name
|
TROX GmbH
|
Vendor identifier
|
329
|
Product name
|
EM-BAC-MOD
|
Model no.
|
M536HD7
|
Application
|
4.0
|
Firmware Revison
|
4.0
|
BACnet Protocol Revision
|
12
|
Standarised Device Profile
|
BACnet Application Specific Controller (B-ASC)
|
Segmentation Capability
|
No
|
Data Link Layer Options
|
MS/TP master (Clause 9), Baudrates 9600, 19200, 38400, 76800
|
Device Address Binding
|
No
|
Network Security Options
|
Non-secure Device - is capable of operating without BACnet Network Security
|
Character Sets Supported
|
ISO 10646 (UTF-8)
|
Configuration switches
Hexadecimal Switches X, Y
|
Network address
|
|
|
|
|
|
DIP Switch 1
|
OFF
|
ON
|
|
|
Controller
|
EASYLAB TCU3
|
Other
|
|
|
|
|
|
|
|
DIP Switch 2
|
OFF
|
ON
|
OFF
|
ON
|
DIP Switch 3
|
OFF
|
OFF
|
ON
|
ON
|
Baud rate
|
9600
|
19200
|
38400
|
76800
|
BIBBS - BACnet Interoperability Building Blocks Supported
Data Sharing-ReadProperty-B
|
DS-RP-B
|
Data Sharing-WriteProperty-B
|
DS-WP-B
|
Data Sharing-COV-Unsolicited-B
|
DS-COVU-B
|
Device Management-Dynamic Device Binding-B
|
DM-DDB-B
|
Device Management-Dynamic Object Binding-B
|
DM-DOB-B
|
Device Management-Device Communication Control-B
|
DM-DCC-B
|
Device Management-ReinitialiseDevice-B
|
DM-RD-B
|
DeviceObject
Property
|
Value
|
Access
|
Object identifier
|
Device instance; default instance = 32900 + set network address
|
WR, RD; E
|
Object name
|
Default="EM-BACnet"; project-specific description can be entered, 62 characters max.
|
WR, RD; E
|
Object type
|
Device (8)
|
RD
|
System_Status
|
OPERATIONAL (0)
|
RD
|
Vendor_Name
|
"TROX GmbH"
|
RD
|
Vendor_Identifier
|
329
|
RD
|
Model_Name
|
"EM-BAC-MOD"
|
RD
|
Description
|
Default = “EASYLAB”; description can be entered, 126 characters max.
|
WR, RD; E
|
Location
|
Default = ""; description can be entered, 62 characters max.
|
WR, RD; E
|
Firmware_Revision
|
“4.0” (EASYLAB)
|
RD
|
Application_Software_Version
|
“4.0” (EASYLAB)
|
RD
|
Protocol_Version
|
1
|
RD
|
Protocol_Revision
|
12
|
RD
|
Protocol Services Supported
|
Who-is, Who-has, Read-Property, Write-Property, Device-communication-control, Reinitialize-device
|
RD
|
Protocol_Object_Types_Supported
|
DEVICE, ANALOG_VALUE, BINARY_VALUE, MULTISTATE_VALUE
|
RD
|
Object_List
|
EASYLAB: device, analog-value 1…36, binary-value 1…30, multistate-value 1…8
|
RD
|
Max_ADPU_Length_Accepted
|
480
|
RD
|
Segmentation_Supported
|
NO_SEGMENTATION (3)
|
RD
|
APDU_Timeout
|
10000
|
RD
|
Number_Of_APDU_Retries
|
3
|
RD
|
Device_Address_Binding
|
–
|
RD
|
Database_Revision
|
0
|
RD
|
Description
|
Controller Type “EASYLAB”
|
RD
|
Max_Master
|
Default 127
|
WR, RD; E
|
Max_Info_Frames
|
Default 1
|
WR, RD; E
|
Multistate Value Objects
Instance
|
Designation
|
Unit
|
Access
|
TCU3
|
TAM
|
Access
|
Instance
|
Designation
|
Available with equipment function
|
Access
|
FH
|
RR
|
RR RMF
|
EC, SC
|
TAM
|
TAM RMF
|
Access
|
1
|
COVU mode
|
x
|
x
|
x
|
x
|
x
|
x
|
WR, RD
|
2
|
Mode
|
x1
|
|
x
|
|
|
x
|
WR, RD
|
3
|
ModeAct
|
x
|
x
|
x
|
x
|
|
|
RD
|
4
|
RoomModeAct
|
|
|
x
|
|
|
x
|
RD
|
5
|
SwitchPos
|
x
|
|
|
|
|
|
RD
|
6
|
Sunblind
|
|
|
x
|
|
|
x
|
WR, RD
|
7
|
SC_SetLockHighPrio
|
|
|
|
|
|
|
WR, RD
|
8
|
SC_GetLockHighPrio
|
|
|
|
|
|
|
RD
|
1 only for individually selected operating mode (stand-alone operation)
FH: Fume cupboard controller
RR: Room controller for supply air or extract air (RS, RE, PC)
RR RMF: Room controller with active room management function
EC, SC: Single controller for supply air or extract air (EC, SC)
TAM: Adapter module
TAM RMF: Adapter module with active room management function
Analogue Value Objects
Instance
|
Designation
|
Unit
|
Access
|
TCU3
|
TAM
|
Access
|
Instance
|
Designation
|
Unit
|
Available with equipment function
|
Access
|
FH
|
RR
|
RR RMF
|
EC, SC
|
TAM
|
TAM RMF
|
Access
|
1
|
VolflowSet
|
l/s (87)
|
x
|
x
|
x
|
x
|
|
x
|
RD
|
2
|
VolflowAct
|
l/s (87)
|
x
|
x
|
x
|
x
|
|
x
|
RD
|
3
|
VolTotalExh
|
l/s (87)
|
x
|
x
|
x
|
x
|
x
|
x
|
RD
|
4
|
VolTotalSup
|
l/s (87)
|
x
|
x
|
x
|
x
|
x
|
x
|
RD
|
5
|
PressSet
|
Pa (53)
|
|
|
x
|
|
|
x
|
RD
|
6
|
PressAct
|
Pa (53)
|
|
|
x
|
|
|
x
|
RD
|
7
|
VelocitySet
|
m/s (74)
|
x
|
|
|
|
|
|
RD
|
8
|
VelocityAct
|
m/s (74)
|
x
|
|
|
|
|
|
RD
|
9
|
WireSensorPos
|
percent (98)
|
x
|
|
|
|
|
|
RD
|
10
|
DampPos
|
percent (98)
|
x
|
x
|
x
|
x
|
|
|
RD
|
11
|
DampPosMax_FH
|
percent (98)
|
x
|
x
|
x
|
x
|
x
|
x
|
RD
|
12
|
DampPosMin_FH
|
percent (98)
|
x
|
x
|
x
|
x
|
x
|
x
|
RD
|
13
|
DampPosMax_RE
|
percent (98)
|
x
|
x
|
x
|
x
|
x
|
x
|
RD
|
14
|
DampPosMin_RE
|
percent (98)
|
x
|
x
|
x
|
x
|
x
|
x
|
RD
|
15
|
DampPosMax_TE
|
percent (98)
|
x
|
x
|
x
|
x
|
x
|
x
|
RD
|
16
|
DampPosMin_TE
|
percent (98)
|
x
|
x
|
x
|
x
|
x
|
x
|
RD
|
17
|
DampPosMax_RS
|
percent (98)
|
x
|
x
|
x
|
x
|
x
|
x
|
RD
|
18
|
DampPosMin_RS
|
percent (98)
|
x
|
x
|
x
|
x
|
x
|
x
|
RD
|
19
|
VolOffset_T
|
percent (98)
|
|
|
x
|
|
|
x
|
WR, RD
|
20
|
VolOffset_P
|
percent (98)
|
|
|
x
|
|
|
x
|
WR, RD
|
21
|
SystemDevices
|
no units (95)
|
x
|
x
|
x
|
x
|
x
|
x
|
RD
|
22
|
VolflowExh
|
l/s (87)
|
x
|
x
|
x
|
|
x
|
x
|
WR, RD
|
23
|
VolflowSup
|
l/s (87)
|
x
|
x
|
x
|
|
x
|
x
|
WR, RD
|
24
|
SC_SetPos
|
percent (98)
|
|
|
|
|
|
|
WR, RD
|
25
|
SC_GetPos
|
percent (98)
|
|
|
|
|
|
|
RD
|
26
|
DampPosMax_EC
|
percent (98)
|
x
|
x
|
x
|
x
|
x
|
x
|
RD
|
27
|
DampPosMin_EC
|
percent (98)
|
x
|
x
|
x
|
x
|
x
|
x
|
RD
|
28
|
DampPosMax_SC
|
percent (98)
|
x
|
x
|
x
|
x
|
x
|
x
|
RD
|
29
|
DampPosMin_SC
|
percent (98)
|
x
|
x
|
x
|
x
|
x
|
x
|
RD
|
30
|
DampPosMax_TS
|
percent (98)
|
x
|
x
|
x
|
x
|
x
|
x
|
RD
|
31
|
DampPosMin_TS
|
percent (98)
|
x
|
x
|
x
|
x
|
x
|
x
|
RD
|
32
|
VolflowSet_R
|
l/s (87)
|
|
|
|
|
|
|
WR, RD
|
33
|
PressSet
|
pascal (57)
|
|
|
|
|
|
|
WR, RD
|
34
|
Volt_AI2
|
volt (5)
|
x
|
x
|
x
|
x
|
x
|
x
|
RD
|
35
|
Volt_AI3
|
volt (5)
|
x
|
x
|
x
|
x
|
x
|
x
|
RD
|
36
|
Volt_AO2
|
volt (5)
|
x
|
x
|
x
|
x
|
x
|
x
|
WR, RD
|
FH: Fume cupboard controller
RR: Room controller for supply air or extract air (RS, RE, PC)
RR RMF: Room controller with active room management function
EC, SC: Single controller for supply air or extract air (EC, SC)
TAM: Adapter module
TAM RMF: Adapter module with active room management function
Binary Value Objects
Instance
|
Designation
|
Unit
|
Access
|
TCU3
|
TAM
|
Access
|
Instance
|
Designation
|
Available with equipment function
|
Access
|
FH
|
RR
|
RR RMF
|
EC, SC
|
TAM
|
TAM RMF
|
Access
|
1
|
LocalAlarm (COVU)
|
x
|
x
|
x
|
x
|
x
|
x
|
RD
|
2
|
SummaryAlarm (COVU)
|
|
|
x
|
|
|
x
|
RD
|
3
|
PressAlarm (COVU)
|
|
|
x
|
|
|
x
|
RD
|
4
|
ManOP_Disable
|
x1
|
|
x
|
|
|
x
|
WR, RD
|
5
|
PressSetSel
|
|
|
x
|
|
|
x
|
WR, RD
|
6
|
DI1
|
x
|
x
|
x
|
x
|
x
|
x
|
RD
|
7
|
DI2
|
x
|
x
|
x
|
x
|
x
|
x
|
RD
|
8
|
DI3
|
x
|
x
|
x
|
x
|
x
|
x
|
RD
|
9
|
DI4
|
x
|
x
|
x
|
x
|
x
|
x
|
RD
|
10
|
DI5
|
x
|
x
|
x
|
x
|
x
|
x
|
RD
|
11
|
DI6
|
x
|
x
|
x
|
x
|
x
|
x
|
RD
|
12
|
DO1
|
x
|
x
|
x
|
x
|
x
|
x
|
RD
|
13
|
DO2
|
x
|
x
|
x
|
x
|
x
|
x
|
RD
|
14
|
DO3
|
x
|
x
|
x
|
x
|
x
|
x
|
RD
|
15
|
DO4
|
x
|
x
|
x
|
x
|
x
|
x
|
RD
|
16
|
DO5
|
x
|
x
|
x
|
x
|
x
|
x
|
RD
|
17
|
DO6
|
x
|
x
|
x
|
x
|
x
|
x
|
RD
|
18
|
SC_Alarm
|
|
|
|
|
|
|
RD
|
19
|
DO1_Set
|
x
|
x
|
x
|
x
|
x
|
x
|
WR, RD
|
20
|
DO2_Set
|
x
|
x
|
x
|
x
|
x
|
x
|
WR, RD
|
21
|
DO3_Set
|
x
|
x
|
x
|
x
|
x
|
x
|
WR, RD
|
22
|
DO4_Set
|
x
|
x
|
x
|
x
|
x
|
x
|
WR, RD
|
23
|
DO5_Set
|
x
|
x
|
x
|
x
|
x
|
x
|
WR, RD
|
24
|
DO6_Set
|
x
|
x
|
x
|
x
|
x
|
x
|
WR, RD
|
25
|
DO1_SetByLocal
|
x
|
x
|
x
|
x
|
x
|
x
|
RD
|
26
|
DO2_SetByLocal
|
x
|
x
|
x
|
x
|
x
|
x
|
RD
|
27
|
DO3_SetByLocal
|
x
|
x
|
x
|
x
|
x
|
x
|
RD
|
28
|
DO4_SetByLocal
|
x
|
x
|
x
|
x
|
x
|
x
|
RD
|
29
|
DO5_SetByLocal
|
x
|
x
|
x
|
x
|
x
|
x
|
RD
|
30
|
DO6_SetByLocal
|
x
|
x
|
x
|
x
|
x
|
x
|
RD
|
1 only for individually selected operating mode (stand-alone operation)
FH: Fume cupboard controller
RR: Room controller for supply air or extract air (RS, RE, PC)
RR RMF: Room controller with active room management function
EC, SC: Single controller for supply air or extract air (EC, SC)
TAM: Adapter module
TAM RMF: Adapter module with active room management function