Application
Electronic controller Type TROX UNIVERSAL, for the control of volume flow rate, room pressure or duct pressure, suitable for supply air and extract air and also as an attachment to VAV terminal units
For use in clean rooms in the pharmaceutical and semiconductor industries, operating theatres, intensive care units, and offices with very demanding control and data transparency requirements
Fast and stable control of the supply air and extract air flow rates as well as of room pressure and duct pressure
For supply air led areas such as clean rooms, offices and patient rooms in hospitals
Options for the integration of additional volume flows into the room balance
Room pressure and duct pressure control; supply air or extract air flow rate measurement as an option (expansion module)
Controllers can be used individually or combined with other controllers for a complete room solution
System solution for the volume flow control in rooms (room balance)
Central BMS interface, 0 – 10 V voltage signals, digital inputs and outputs, expansion modules for LonWorks, BACnet, Modbus
Plug and play communication system with automatic controller identification, no component addressing required
Connections and status displays on the outside of the controller casing
Project-specific adjustments with adaptable room control panel
Project-specific adjustments can be achieved with configurable special functions, monitoring, and alarm signalling
Permanent function monitoring of the system and the connected sensors
Very simple commissioning with software wizard for configuration changes, maintenance and diagnosis
Centralised configuring and permanent signalling of room settings (room management function)
EasyConnect configuration software enables interactive navigation (with optional BlueCon adapter, wireless controller configuration)
Factory tested and configured with projectspecific parameters
Parts and characteristics
Static differential pressure transducer for rapid actual value measurement
Microprocessor system with programme and system data stored in nonvolatile memory
Double-stack terminal block for supply voltage connection
Connection of communication cable to plug socket or screw terminals
Digital inputs with screw terminals or plug socket
Analogue inputs with screw terminals or plug socket
Analogue outputs with screw terminals or plug socket (actuator)
Control input signal for various actuators: standard actuator with 150 s running time, actuator with 150 s running time and safe position (spring return), fast-running 3 s actuator; all actuators for 90° damper blade position
Integral terminal resistor for the communication cable
Alarm indicator lights on both sides of the casing
Status indicator lights (heartbeat, communication and terminal resistor)
Attachments
Expansion modules are factory mounted or can be fitted at a later stage
T: EM-TRF, power supply unit for connecting the controller to the 230 V AC mains voltage
U: EM-TRF-USV, power supply unit for connecting the controller to the 230 V AC mains voltage, including uninterruptible power supply (with battery backup, 4 h), volume flow rate measurement for room and duct pressure controllers
Z: EM-AUTOZERO, automatic zero point correction for long-term stable volume flow rate measurement and hence reduced maintenance.
B: EM-BAC-MOD-01, interface for BACnet MS/TP
M: EM-BAC-MOD-01, interface for Modbus RTU
I: EM-IP, BACnet-IP, Modbus-IP, web server interface
R: EM-IP, BACnet-IP, Modbus-IP, web server interface with real time clock
Useful additions
BE-LCD: Room control panel
Static differential pressure transducer for room pressure control
Static differential pressure transducer for duct pressure control, including tube and pressure tap
EasyConnect: Configuration software for the commissioning and diagnosis of TROX UNIVERSAL and EASYLAB systems; BlueCon Bluetooth adapter module available as an option
EasyCon Android app for maintenance and diagnosis as well as for reading and writing certain parameters (only with TROX BlueCon adapter module)
Construction features
Control unit complete with all expansion modules in a plastic casing and attached to the air terminal unit
Controller casing can be opened without tools, except for controllers with with EM-TRF or EMTRF- USV
Expansion modules can be easily retrofitted (automatic recognition, plug and play)
Pin header socket for the connection of expansion modules
Plug sockets for the most important connections on the outside of the casing
Static differential pressure transducer with room air induction to protect the sensor
Materials and surfaces
Casing made of ABS plastic, UL94, V0, lower part in grey (RAL 7037), with blue cover (RAL 5002)
Maintenance
Zero point correction of the static differential pressure transducer should be carried out once per year (recommendation)
If you use expansion module EM-AUTOZERO for automatic zero point correction, no manual correction is required
Volume flow control
Application
Extract air and supply air volume flow rate control and volume flow rate measurement
Can be combined with galvanised sheet steel VAV terminal units Type TVR, TVJ, TVT, TVA, TVZ, TZ-Silenzio or TA-Silenzio, and with plastic VAV terminal units Type TVRK
Can be combined with stainless steel volume flow rate measuring units Type VMR or VME, and with plastic volume flow rate measuring units of Type VMRK
Variable volume flow control to save energy while providing maximum safety and data transparency
Controllers can be easily expanded (optional expansion modules) for use with Modbus, BACnet or LonWorks systems
Monitoring and alarm function
Monitoring of the volume flow rate can be configured
Alarm thresholds can be individually configured, independently of deviation
Alarms can be individually configured, e.g. no alarm during reduced operation
Optical alarms on the outside of the controller casing
Alarm signalling to switch contact and communication modules (expansion)
Optical and acoustic alarms are emitted on the optional room control panel
Display of volume flow rate actual and setpoint values on the control panel
Operating modes
Standard mode, variable flow rate default setting or constant setpoint value
Special operating modes: Increased operation (max), reduced operation (min), shut-off and OPEN position
Shut-off is possible if 2 – 10 V signal voltage range is used and signal is below 1 V
Three levels for setting operating mode defaults (central BMS, control panel BE-LCD, digital inputs on the controller)
Operating mode default setting for all controllers in the room
Configuration options for prioritisation and shut-off
Volume flow rate setting with voltage signal (0 – 10 V or 2 – 10 V DC)
Volume flow rate setting via central BMS (standard protocol LonWorks, Modbus or BACnet) using optional interface modules
Operating mode default setting with integral timer and expansion module EM-IP
Room pressure contro
Application
Monitoring and alarm function
Operating modes
Standard mode, variable pressure default setting or constant setpoint value
Special operating modes: Shut-off and OPEN position
Operating mode default setting
Supply air and extract air control with a master-slave setup
Application
Use the controller with the RMF to set the room parameters. The master controller sends the volume flow rate actual value (and other values) via the communication cable to the slave controller. The slave controller uses this value to determine the flow rate setpoint value. In case of air transfer a constant supply air to extract air difference will be maintained.
Room management function
Order example – Supply air led system
Supply air led systemSupply air control, extract air control and room pressure control with a master-slave setup
Application
The master controller sends the volume flow rate actual value (and other values) via the communication cable to the slave controller. The slave controller uses this value to determine the flow rate setpoint value. The room pressure controller maintains the variable or constant setpoint pressure by opening the control damper blade to a greater or lesser degree. Use the controller with the RMF to set the room parameters.
Room management function
Connection to higher-level systems
The controller can be connected to higher level systems with expansion modules for open bus systems (LonWorks, Modbus, BACnet). The function varies according to the controller equipment function.
controller
Order example
Supply air led systemSupply air control, extract air control and room pressure control with a master-slave setup, combined with duct pressure control
Application
System setup
The system consists of a VAV terminal unit with a TROX UNIVERSAL controller for supply air, a VAV terminal unit with a TROX UNIVERSAL controller for extract air, and a room pressure controller. In the room there is also an enclosure that is to be provided with supply air. A VAV terminal unit maintains a constant duct pressure in the supply air duct. A plug-in communication cable connects the controllers. The system can be expanded: Up to 24 TROX UNIVERSAL controllers can be connected to a communication cable. Whether room pressure control is based on supply air or on extract air depends on the project. Use the room pressure controller to activate the room management function. The controller with the RMF then acts as the master controller for the room.
Use the controller with the RMF to set the room parameters. Room pressure and duct pressure values can be configured with the respective pressure controller and are output on that same controller. The room pressure controller is used to maintain the variable or constant setpoint pressure by opening the control damper blade to a greater or lesser degree. The master controller sends the volume flow rate actual value via the communication cable to the slave controller. The slave controller uses this value to determine the flow rate setpoint value. In case of air transfer a constant supply air to extract air difference will be maintained. The duct pressure controller maintains the constant or variable setpoint pressure; the duct pressure controller can also be fitted with an optional volume flow rate measuring point. The controller then transmits the volume flow rate actual value to the system such that it can be used for room balancing. Control of the damper blade of VAV terminal units with a a pressure controller is a closed loop.
Room management function
Connection to higher-level systems
Expansion modules for open bus systems (LonWorks, Modbus, BACnet) can be used to connect the controller to higher-level systems; these modules can be used as follows:
Order example
VAV terminal unit for extract air
TVR/200/TUN/RE/S/2/TZ
VAV terminal unit for the supply pressure control in ducts
TVR/125/TUN/PDS/SFP/2/TVZ/150 Pa
Share page
Recommend this page
Recommend this page by sending a link by mail.
Share page
Thank you for your recommendation!
Your recommendation has been sent and should arrive shortly.
Contact
We are here for you
Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
We are here for you
Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265