XB0 for TVE
Application
Control strategy
Operating modes
Variable operation (V)
Constant value mode (F)
Interface
Analogue interface with adjustable signal voltage range
Signal voltage ranges
Parts and characteristics
Construction
Commissioning
Useful additions
Air terminal units control the volume flow in a closed loop, which means: measurement – comparison – adjustment. The volume flow rate is obtained by measuring a differential pressure. This is done with a differential pressure sensor. An integrated differential pressure transducer converts differential pressure into a voltage signal. The actual volume flow rate is available as a voltage signal. The factory setting is such that 10 V DC always corresponds to the nominal flow rate (qvnom). The volume flow setpoint value is specified by a higher-level controller (e.g. room temperature controller, air quality controller, central BMS). Variable volume flow control can be set between qvmin and qvmax. It is possible to override the room temperature control by forced switching, e.g. for a shut-off The controller compares the volume flow setpoint with the current actual value and adjusts the internal actuator according to the control deviation.
Compact controllers for VAV terminal units
Part number | Type of installation component | VAV terminal units |
A00000041355 | 227V-024-10-DD3 | TVR, TVJ, TVT, TZ-Silenzio, TA-Silenzio, TVZ, TVA, TVM |
A00000082302 | TR0V-024T-10I-DD15 | TVE, TVE-Q |
Compact controller XB0, 227V-024-10-DD3
Type of measurement/installation orientation | Dynamic measurements, any installation orientation |
Supply voltage (AC) | 24 V AC, ± 20 %, 50/60 Hz |
Supply voltage (DC) | 24 V DC ± 20 % |
Power rating (AC) | 5 VA max. |
Power rating (DC) | 2.5 W max. |
Torque | 10 Nm |
Power consumption (when running/when idle) | 1.5 W |
Run time for 90° | Approx. 120 s |
Setpoint value signal input | 0 – 10 V DC, Ra > 100 kΩ or 2 – 10 V DC, Ra > 50 kΩ |
Actual value signal output | 0 - 10 V DC or 2 - 10 V DC; maximum 0.5 mA |
Connection | Approx. 0.9 m cable, 4 × 0.75 mm² |
IEC protection class | III (Protective extra-low voltage) |
Protection level | IP 42 |
EC conformity | EMC to 2014/30/EU |
Weight | 0.46 kg |
Weight | 0.57 kg |
Compact controller XB0, TR0V-024T-10I-DD15
Supply voltage (AC) | 24 V AC, ± 20 %, 50/60 Hz |
Type of measurement/installation orientation | Dynamic measurements, any installation orientation |
Power rating | Rating TVE NW 100 - 160: 4 WTVE NW 200 - 400: 6 WTVE-Q up to height 200: 4 WTVE-Q up to height 300: 6 W Power consumption (during operation) TVE NW 100 - 160: 2.5 WTVE NW 200 - 400: 3.5 WTVE-Q up to height 200: 2.5 WTVE-Q up to height 300: 3.5 W Power consumption (during idle state) 1 W |
Torque | 5 - 10 Nm depending on dimensions |
Run time for 90° | 100 s |
Setpoint value signal input | 0 – 10 V DC, Ra > 100 kΩ or 2 – 10 V DC, Ra > 50 kΩ |
Actual value signal output | 0 - 10 V DC or 2 - 10 V DC; maximum 5 mA |
Connection | Screw terminals (maximum cable cross-section 1.5 mm²) |
IEC protection class | III (Protective extra-low voltage) |
Protection level | IP 42 (with attached terminal cover) |
EC conformity | EMC to 2014/30/EU |
Weight | 0.65 kg |
Description of status LEDs and error messages regarding control components for terminal unit TVE, TVE-Q
Flashing signal of LED button | Flashing signal in words | Status |
LED off | No supply voltage | |
LED lights up permanently. | Regulated. Signalled as long as the actuator does not rotate to readjust the setpoint value. | |
LED flashes 1 time in a 2-second interval. | Setpoint value or override control position not yet reached. | |
LED flashes 2 times in a 2-second interval. | Override control position reached. | |
LED flashes once briefly at 2-second intervals. | Synchronisation drive after Power Up | |
LED flashes once briefly at 2-second intervals. | Test mode activated | |
LED flashes 2 times in quick succession at 2-second intervals. | Overpressure sensor (overpressure) | |
LED flashes 2 times in quick succession at 3-second intervals. | Actuator overload detected (block) | |
LED flashes 4 times in quick succession at 2-second intervals. | Inform TROX service technicians |
The signal spans 2 seconds. 1 = LED is illuminated, 0 = LED is not illuminated
Release of a test function
Pressing the LED push button for > 2 seconds activates the test drive.
This specification text describes the general properties of the product.
Category
Application
Supply voltage
Actuator
Installation orientation
Connection
Terminals with rubber cap cover, therefore no additional terminal box required (control components for TVE and TVE-Q)
Interface information
Analogue:
Special functions
Parameter setting
Factory condition
Functional test under air using reference measurement on a regularly validated test bench in accordance with EN ISO 9001 to check the function and control accuracy of the complete volume flow controller
Equivalence criteria
For basic device types TVE and TVE-Q: Electrical connections with screw terminals, no additional terminal boxes required
TVE | – | D | / | P1 | / | FL | / | 100 | / | G2 | / | XB0 | / | V 0 | / | 200 – 900 [m³/h] |
| | | | | | | | | | | | | | | | | | | ||||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 9 | 10 | ||||||||
1 Type
TVE VAV air terminal unit
2 Acoustic cladding
No entry: without acoustic cladding
D with acoustic cladding
3 Material
No entry: Galvanised sheet steel
P1 Surface powder-coated, RAL 7001 (silver grey)
A2 Stainless steel construction
4 Air duct connection
No entry: Push-fit end, suitable for air ducts according to EN
1506; with groove for optional sealing
FL Flanges on both ends
5 Nominal size [mm]
100, 125, 160, 200, 250, 315, 400
6 Accessories
No entry: without accessories
D2 Double lip seal both ends (with groove: only for push-fit end)
G2 Matching flange for every flange (only with FL)
7 Attachment (control component)
XB0 Dynamic volume flow controller, analogue interface
8 Operating mode
F Constant value mode, one setpoint value (no external switch contact)
V Variable operation (default setpoint value from analogue signal)
9 Signal voltage range
Only with operating mode F or V
0 0 – 10 V DC
2 2 – 10 V DC
10 Operating values for factory setting
Volume flow rate [m³/h or l/s]
qvconst (with operating mode F)
qvmin – qvmax (with operating mode V)
Order example: TVE-D-P1-FL/100/G2/XB0/V0/200-900 [m³/h]
Type | TVE: VAV terminal unit |
Acoustic cladding | with acoustic cladding |
Material | Surface powder-coated, RAL 7001 (silver grey) |
Air duct connection | Flanges on both ends |
Nominal size [mm] | 100 |
Accessories | Matching flange for each flange |
Attachment (control component) | Dynamic volume flow controller, analogue interface |
Operating mode | Variable operation (default setpoint value from analogue signal) |
Signal voltage range | 0 – 10 V DC |
Operating values for factory setting | 200 – 900 [m³/h] |
Share page
Recommend this page
Recommend this page by sending a link by mail.
Share page
Thank you for your recommendation!
Your recommendation has been sent and should arrive shortly.
Contact
We are here for you
Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
We are here for you
Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265