XB0

CONTROL COMPONENTS FOR VAV TERMINAL UNIT WITH DYNAMIC TRANSDUCER

Compact device for use with VAV terminal units

  • Controller, dynamic differential pressure transducer and actuator in one casing
  • Use in ventilation and air conditioning systems, only with clean air
  • Suitable for constant and variable volume flow rates
  • Activation of override controls by means of external switch contacts
  • Volume flow rates qvmin and qvmax are factory-set and stored in the controller
  • Change of operating parameters by means of adjustment device
  • Service access for manual adjustment devices and PC configuration software
  • Simple terminal connection without using additional junction boxes (for types TVE and TVE-Q)
Product successfully added to cart

General information

Application

  • All-in-one control engineering device for VAV terminal units
  • Dynamic differential pressure transducer, electronic controller and actuator are fitted together in one casing
  • For clean air in ventilation and air conditioning systems
    • The standard filtration enables use in the supply air without additional dust protection measures
    • Application examples: Offices and classrooms
  • In the event of a strong occurrence of dust, install appropriate extract air filters upstream, as a partial volume flow is routed through the transducer for volume flow rate measurement.
  • If the air is heavily contaminated with dust, fluff, sticky, moist components, an attachment with a static differential pressure transducer must be used, e.g. XD0 or XS0.
    • Application examples: Extract air from changing rooms and shower areas, hospital bedrooms
    • XS0 (for types TVE and TVE-Q)
    • XD0 (for TVR, TVJ, TVT, TZ-Silenzio, TA-Silenzio, TVZ, TVA, TVRK)
  • Various control options based on setpoint value default setting
  • Room temperature controllers, building automation, air quality controllers and others control the variable volume flow control by specifying setpoint values via an analogue signal
  • Override controls for the activation of qvmin, qvmax, shutoff and open position possible via switch contacts or relay
  • The actual volume flow rate value is available as a linear voltage signal


Control strategy

  • The volume flow controller works independent of the duct pressure
  • Differential pressure fluctuations do not result in permanent volume flow rate changes
  • To prevent the control from becoming unstable, a dead band (hysteresis) is maintained which is not moved by the damper blade
  • The flow rate range for the controller is set at the factory
    • qvmin: minimum volume flow rate
    • qvmax: maximum volume flow rate
  • Operating parameters are set at the factory according to the order code


Operating modes

  • Variable or constant value

Variable operation (V)

  • Setpoint value default setting via analogue interface
  • Signal voltage range corresponds to qvmin to qvmax

Constant value mode (F)

  • A setpoint signal is not required, setpoint value corresponds to qvmin


Interface

Analogue interface with adjustable signal voltage range

  • Analogue signal for volume flow rate setpoint value
  • Analogue signal for volume flow rate actual value


Signal voltage ranges

  • 0 – 10 V DC
  • 2 – 10 V DC


Parts and characteristics

  • Transducer based on dynamic measuring principle. It can only be used with clean air, as a partial volume flow is passed through the transducer
  • Actuators with overload protection
  • Release button to allow for manual operation (only 227V-024-10-DD3)
  • Connecting cable with 4 wires, approx. 0.9 m, halogen-free (only 227V-024-10-DD3)
  • Terminals with cover (only TR0V-024T-05I-DD15)
  • Service interface


Construction

  • Type 227V-024-10-DD3 for TVR
  • Type 227V-024-10-DD3 for TVJ
  • Type 227V-024-10-DD3 for TVT up to1000 × 300 or 800 × 400
  • Type 227V-024-10-DD3 for TZ-Silenzio, TA-Silenzio
  • Type 227V-024-10-DD3 for TVZ, TVA
  • Type 227V-024-10-DD3 for TVM
  • Type TR0V-024T-10I-DD15 for TVE and TVE-Q


Commissioning

  • Due to the volume flow rates set at the factory, always ensure that the terminal units are only installed at the specified locations
  • After successful installation and wiring, the controller is ready for use
  • Operating parameters can be adjusted by the customer (via the adjustment device)


Useful additions

  • Adjustment device GUIV-A (order code AT-VAV-G) for 227V-024-10-DD3
  • Adjustment device GUIV3-M (order code AT-VAV-G3) for TR0V-024T-10I-DD15

Technical information

  • Function
  • TECHNICAL DATA
  • SPECIFICATION TEXT
  • ORDER CODE

Air terminal units control the volume flow in a closed loop, which means: measurement – comparison – adjustment. The volume flow rate is obtained by measuring a differential pressure. This is done with a differential pressure sensor. An integrated differential pressure transducer converts differential pressure into a voltage signal. The actual volume flow rate is available as a voltage signal. The factory setting is such that 10 V DC always corresponds to the nominal flow rate (qvnom). The volume flow setpoint value is specified by a higher-level controller (e.g. room temperature controller, air quality controller, central BMS). Variable volume flow control can be set between qvmin and qvmax. It is possible to override the room temperature control by forced switching, e.g. for a shut-off The controller compares the volume flow setpoint with the current actual value and adjusts the internal actuator according to the control deviation.

Compact controllers for VAV terminal units

Part number

Type of installation component

VAV terminal units

A00000041355

227V-024-10-DD3

TVR, TVJ, TVT, TZ-Silenzio, TA-Silenzio,

TVZ, TVA, TVM

A00000082302

TR0V-024T-10I-DD15

TVE, TVE-Q


Compact controller XB0, 227V-024-10-DD3

Type of measurement/installation orientation

Dynamic measurements, any installation orientation

Supply voltage (AC)

24 V AC, ± 20 %, 50/60 Hz

Supply voltage (DC)

24 V DC ± 20 %

Power rating (AC)

5 VA max.

Power rating (DC)

2.5 W max.

Torque

10 Nm

Power consumption (when running/when idle)

1.5 W

Run time for 90°

Approx. 120 s

Setpoint value signal input

0 – 10 V DC, Ra > 100 kΩ or 2 – 10 V DC, Ra > 50 kΩ

Actual value signal output

0 - 10 V DC or 2 - 10 V DC; maximum 0.5 mA

Connection

Approx. 0.9 m cable, 4 × 0.75 mm²

IEC protection class

III (Protective extra-low voltage)

Protection level

IP 42

EC conformity

EMC to 2014/30/EU

Weight

0.46 kg

Weight

0.57 kg


Compact controller XB0, TR0V-024T-10I-DD15

Supply voltage (AC)

24 V AC, ± 20 %, 50/60 Hz

Type of measurement/installation orientation

Dynamic measurements, any installation orientation


Power rating

Rating

TVE NW 100 - 160: 4 WTVE NW 200 - 400: 6 WTVE-Q up to

height 200: 4 WTVE-Q up to height 300: 6 W Power consumption (during operation)

TVE NW 100 - 160: 2.5 WTVE NW 200 - 400: 3.5 WTVE-Q up to

height 200: 2.5 WTVE-Q up to height 300: 3.5 W Power consumption (during idle state)

1 W

Torque

5 - 10 Nm depending on dimensions

Run time for 90°

100 s

Setpoint value signal input

0 – 10 V DC, Ra > 100 kΩ or 2 – 10 V DC, Ra > 50 kΩ

Actual value signal output

0 - 10 V DC or 2 - 10 V DC; maximum 5 mA

Connection

Screw terminals (maximum cable cross-section 1.5 mm²)

IEC protection class

III (Protective extra-low voltage)

Protection level

IP 42 (with attached terminal cover)

EC conformity

EMC to 2014/30/EU

Weight

0.65 kg


Description of status LEDs and error messages regarding control components for terminal unit TVE, TVE-Q

Flashing signal of LED button

Flashing signal in words

Status

LED off

No supply voltage

LED lights up permanently.

Regulated. Signalled as long as the actuator does not rotate to readjust the setpoint value.


LED flashes 1 time in a 2-second interval.

Setpoint value or override control position not yet reached.


LED flashes 2 times in a 2-second interval.

Override control position reached.


LED flashes once briefly at 2-second intervals.

Synchronisation drive after Power Up


LED flashes once briefly at 2-second intervals.

Test mode activated


LED flashes 2 times in quick succession at 2-second intervals.

Overpressure sensor (overpressure)


LED flashes 2 times in quick succession at 3-second intervals.

Actuator overload detected (block)


LED flashes 4 times in quick succession at 2-second intervals.

Inform TROX service technicians

The signal spans 2 seconds. 1 = LED is illuminated, 0 = LED is not illuminated


Release of a test function

Pressing the LED push button for > 2 seconds activates the test drive.

This specification text describes the general properties of the product.

Category

  • Compact controller for volume flow rate
  • Control of a constant or variable volume flow rate setpoint
  • Electronic controller for applying a reference value and capturing an actual value
  • The actual value relates to the nominal volume flow rate so that commissioning and subsequent adjustment are simplified
  • Stand-alone operation or integration with a central BMS


Application

  • Dynamic transducer for clean air in ventilation and air conditioning systems


Supply voltage

  • 24 V AC/DC


Actuator

  • Integral; slow-running (run time <150s for 90°)


Installation orientation

  • Either direction


Connection

  • Terminals with rubber cap cover, therefore no additional terminal box required (control components for TVE and TVE-Q)

  • Connecting cable with 4 wires (control components for other types)


Interface information

Analogue:

  • Volume flow rate setpoint and actual volume flow rate value


Special functions

  • Activation qvmin, qvmax, closed, open by external switch contacts


Parameter setting

  • Specific parameters for VAV terminal unit are factory-set
  • Operating values: qvmin, qvmax and interface type are factoryset
  • Subsequent adjustment by means of optional tools: Adjustment tool, PC software (each wired)


Factory condition

  • Functional test under air using reference measurement on a regularly validated test bench in accordance with EN ISO 9001 to check the function and control accuracy of the complete volume flow controller

  • Adjustment of the device-specific parameters under air by reference measurement on a regularly validated test bench in accordance with EN ISO 9001
  • The test report of the factory parameterisation, functional test and adjustment must be made available after delivery of the volume flow controller


Equivalence criteria

  • For basic device types TVE and TVE-Q: Electrical connections with screw terminals, no additional terminal boxes required

  • The test report of the factory parameterisation, functional test and adjustment under air by reference measurement on a regularly validated test bench in accordance with EN ISO 9001 is made available

TVED / P1 / FL / 100 / G2 / XB0 / V 0/200 – 900 [m³/h]
||||||||  |
 |
12345678  9
10

1 Type
TVE VAV air terminal unit

2 Acoustic cladding
No entry: without acoustic cladding

D with acoustic cladding

3 Material

No entry: Galvanised sheet steel

P1 Surface powder-coated, RAL 7001 (silver grey)

A2 Stainless steel construction

4 Air duct connection

No entry: Push-fit end, suitable for air ducts according to EN

1506; with groove for optional sealing

FL Flanges on both ends

5 Nominal size [mm]

100, 125, 160, 200, 250, 315, 400

6 Accessories

No entry: without accessories

D2 Double lip seal both ends (with groove: only for push-fit end)

G2 Matching flange for every flange (only with FL)

7 Attachment (control component)

XB0 Dynamic volume flow controller, analogue interface

8 Operating mode

F Constant value mode, one setpoint value (no external switch contact)

V Variable operation (default setpoint value from analogue signal)

9 Signal voltage range

Only with operating mode F or V

0 0 – 10 V DC

2 2 – 10 V DC

10 Operating values for factory setting

Volume flow rate [m³/h or l/s]

qvconst (with operating mode F)

qvmin – qvmax (with operating mode V)


Order example: TVE-D-P1-FL/100/G2/XB0/V0/200-900 [m³/h]

Type TVE: VAV terminal unit
Acoustic claddingwith acoustic cladding
MaterialSurface powder-coated, RAL 7001 (silver grey)
Air duct connection Flanges on both ends
Nominal size [mm]100
AccessoriesMatching flange for each flange
Attachment (control component)Dynamic volume flow controller, analogue interface
Operating modeVariable operation (default setpoint value from analogue signal)
Signal voltage range 0 – 10 V DC
Operating values for factory setting 200 – 900 [m³/h]

Downloads

product information

certificates

production {"X-Frame-Options"=>"SAMEORIGIN", "X-XSS-Protection"=>"1; mode=block", "X-Content-Type-Options"=>"nosniff", "X-Download-Options"=>"noopen", "X-Permitted-Cross-Domain-Policies"=>"none", "Referrer-Policy"=>"strict-origin-when-cross-origin", "Strict-Transport-Security"=>"max-age=31536000; includeSubDomains", "Content-Type"=>"text/html; charset=utf-8"}

Share page

Recommend this page

Recommend this page by sending a link by mail.

Fields marked with an (*) are required fields.

Share page

Thank you for your recommendation!

Your recommendation has been sent and should arrive shortly.

Contact

We are here for you

Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

Contact

We are here for you

Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

Attachment (max. 10MB)

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265