Application
Dynamic effective pressure transducer, electronic controller and actuator are fitted together in one casing
For clean air in ventilation and air-conditioning systems; the standard filtering enables use in the supply air without additional dust protection measures
Application examples: Offices and classrooms
In the event of a strong occurrence of dust, install appropriate extract air filters upstream, as a partial volume flow is routed through the transducer for volume flow rate measurement.
If the air is heavily contaminated with dust, fluff, sticky, moist components, use attachment group with static differential pressure transducer, e.g. XSMB0
Application examples: Extract air from changing rooms and shower areas, hospital bed rooms
Various control options based on setpoint value default setting
Volume flow rate control is based on setpoint values received from room temperature controller, MCE, air quality controller or other devices as an analogue signal or via communication interface
Override controls for activating qvmin, qvmax, shut-off, open position via Modbus/BACnet register or switch or relay possible
The actual volume flow rate is available as a network data point or as a linear voltage signal
Damper position, e.g. for fan optimisation, is available as a network data point
Control strategy
Operating modes
BACnet (B):
Analogue - variable operation (V):
Analogue - fixed value operation (F):
Alternative adjusting possible on site:
Interface
Communication interfaces
Analogue interface with adjustable signal voltage range
Note:
Parts and characteristics
Menu navigation for adjusting operating parameters
Menu navigation for customising the communication interface
Construction
Operating modes
BACnet (B):
Analogue - variable operation (V):
Analogue - fixed value operation (F):
Alternative adjusting possible on site:
VAV terminal units control the volume flow in a closed loop, i.e. measurement – comparison – correction.
For volume flow rate measurement the effective pressure is measured first. This is done with a differential pressure sensor. The integral differential pressure transducer transforms the effective pressure into a voltage signal. The actual volume flow rate is available as a voltage signal. The factory setting is such that 10 V DC always corresponds to the nominal flow rate (qvnom).
The volume flow rate setpoint value comes from a higher-level controller (e.g. room temperature controller, air quality controller, central BMS). Variable volume flow control results in a value between qvmin and qvmax. It is possible to override the room temperature control, e.g. by a complete shut-off of the duct.
The controller compares the differential pressure setpoint value to the actual value and controls the actuator accordingly if there is a difference.
Part number | Type of installation component | VAV terminal units |
AOOOOOO823O5 | TROVM-O24T-1Ol-DD15-BN | TVE, TVE-Q |
Type of measurement/installation orientation | Dynamic measurements, any installation orientation |
Supply voltage (AC) | 24 V AC, ± 2O %, 5O/6O Hz |
Supply voltage (DC) | 24 V DC ± 2O % |
Power rating (AC) | TVE NW 1OO - 16O: maximum 4 VA TVE NW 2OO - 4OO: maximum 6 VA TVE-Q up to height 2OO: maximum 4 VA TVE-Q from height 3OO: maximum 6 VA |
Power rating (DC) | TVE NW 1OO - 16O: maximum 2.5 W TVE NW 2OO - 4OO: maximum 3 W TVE-Q up to height 2OO: maximum 2.5 W TVE-Q from height 3OO: maximum 3 W |
Power consumption (when running/when idle) | 1 W |
Setpoint value signal input (analogue optional) | 0 - 10 V DC, input resistance > 100 kΩ or 2 - 10V DC Ra> 50 kΩ |
Actual value signal output | O - 1O V DC or 2 - 1O V DC; maximum 5 mA |
lEC protection class | lll (Protective extra-low voltage) |
Protection level | lP 42 (with attached terminal cover) |
EC conformity | EMC to 2O14/3O/EU |
Bus connection | RS485, BACnet MS/TP or Modbus RTU |
Number of nodes (bus participants) | 128 |
BACnet communication parameters to be set | Baud rate adjustable: 96OO, 192OO, 384OO, 576OO, 768OO, 1152OO baud Start bit: 1 Data bits: 8 Stop bits: 1 no parity |
Adjustable communication parameters for Modbus | Baud rate adjustable: 12OO, 24OO, 48OO, 96OO, 192OO, 384OO, 768OO, 1152OO baud Start bit: 1 Data bits: 8 Stop bits adjustable: 1 or 2 Parity: adjustable: None, Even, Odd |
Setpoint / actual value interface | BACnet operation: via BACnet objects Modbus operation: via Modbus register list |
Bus termination | externally required (120 Ω) |
This specification text describes the general characteristics of the product.
Category
Application
Area of application
Actuator
Installation orientation
Connection
Supply voltage
Interface/signalling
Interface information
Special functions
Parameter setting
Factory condition
TVE | – | D | / | P1 | / | 100 | / | D2 | / | XDMB0 | / | V | 0 | / | 20 - 350 [m³/h] |
| | | | | | | | | | | | | | | | | | |||||||
1 | 2 | 3 | 5 | 6 | 7 | 8 | 9 | 10 |
Type | TVE: VAV terminal unit |
Acoustic cladding | with acoustic cladding |
Material | Powder-coated RAL 7001 (silver grey) |
Nominal size [mm] | 100 |
Accessories | Double lip seal both ends |
Attachment (control component) | Volume flow controller with dynamic measuring principle, display and digital Bus interface for BACnet MS/TP, Modbus RTU and analogue interface |
Operating mode | variable operation, control with analogue signal |
Signal voltage range | 0 – 10 V DC |
Operating values for factory setting | 20 – 350 [m³/h] |
Share page
Recommend this page
Recommend this page by sending a link by mail.
Share page
Thank you for your recommendation!
Your recommendation has been sent and should arrive shortly.
Contact
We are here for you
Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
We are here for you
Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265