Air terminal units control the volume flow in a closed loop, which means: measurement – comparison – adjustment.
The volume flow rate is obtained by measuring a differential pressure. This is effected via a differential pressure sensor. The integrated differential pressure transducer converts the differential pressure into a voltage signal. The actual volume flow value is available as a data point. Du to the factory adjustment, 100% always equals the nominal volume flow rate (qvNom).
The volume flow setpoint value is specified by a higher-level controller (e.g. room temperature controller, air quality controller, central BMS). Variable volume flow control can be set betweenvmin and qvmax. It is possible to override the room temperature control by forced switching, e.g. for a shut-off
The controller compares the volume flow setpoint with the current actual value and adjusts the internal actuator according to the control deviation.
Category
Application
Supply voltage
Actuator
Installation orientation
Interface/signalling
Connection
Interface information
Special functions
Parameter setting
Factory condition
TVE | – | D – P1 | – | FL | / | 100 | / | G2 | / | XM0-J6 | / | M | / | 20 – 350 [m³/h] | |
| | | | | | | | | | | | | | | | | ||||||||
1 | 2 3 | 4 | 5 | 6 | 7 | 8 | 10 | ||||||||
1 Type
TVE VAV terminal unit
2 Acoustic cladding
No entry: without acoustic cladding
D with acoustic cladding
3 Material
No entry: Galvanised sheet steel
P1 Surface powder-coated, RAL 7001 (silver grey)
A2 Stainless steel construction
4 Air duct connection
No entry: Push-fit end, suitable for air ducts according to EN
1506; with groove for optional seal
FL Flanges on both ends
5 Nominal size [mm]
100, 125, 160, 200, 250, 315, 400
6 Accessories
No entry: without accessories
D2 Double lip seal both ends (only for push-fit end with groove)
G2 Matching flange for every flange (only with FL)
7 Attachment (control component)
XM0-J6 Volume flow controller with dynamic transducer, display,
Modbus RTU interface, RJ12 socket (for X-AIRCONTROL)
8 Operating mode
M Modbus RTU interface, variable operation (default setpoint value via Modbus register)
10 Operating values for factory setting
Volume flow rate [m³/h or l/s]
qᵥmin – qᵥmax
Acoustic cladding | without |
Material | galvanised sheet steel |
Nominal size | 100 mm |
Accessories | Double lip seal both ends |
Attachment (control components) | Compact controller volume flow, dynamic transmitter, Interface Modbus RTU, display, RJ12 connection socket (for X-AIRCONTROL) |
Operating mode | Modbus RTU |
Volume flow rate | 20 – 350 m³/h |
Compact controllers for VAV terminal units
Part number | Type of installation component | VAV terminal units |
A00000069230 | TR0VM-024T-05I-DD15-MB | TVE, TVE-Q |
Compact controller TR0VM-024T-05I-DD15-MB with RJ12 connection socket
Type of measurement/installation orientation | Dynamic measurements, any installation orientation |
Supply voltage (AC) | 24 V AC, ± 20 %, 50/60 Hz |
Supply voltage (DC) | 24 V DC ± 20 % |
Power rating (AC) | NW 100 – 160: maximum 4 VA NW 200 – 400: maximum 7 VA TVE-Q up to height 200: maximum 4 VA TVE-Q from height 300: maximum 7 VA |
Power rating (DC) | NW 100 – 160: maximum 2.5 W NW 200 – 400: maximum 4 W TVE-Q up to height 200: maximum 2.5 W TVE-Q from height 300: maximum 4 W |
Power consumption (when running/when idle) | 1 W |
Run time for 90° | 100 s |
IEC protection class | III (Protective extra-low voltage) |
Protection level | IP 42 (with attached terminal cover) |
EC conformity | EMC to 2014/30/EU |
Bus connection | Modbus RTU, RS485 |
Number of nodes | 128 |
Adjustable communication parameters | 1200 – 115,200 Bd Start bit: 1 Data bits: 8 Stop bits: 1 or 2 Parity: None, Even, Odd |
Setpoint / actual value interface (Modbus) | Via X-AIRCONTROL/Modus register list |
Cable termination | externally required |
Interface configuration of the control component
The communication interface for the control component is pre-set to Modbus at the factory for use with the X-AIRCONTROL zone module. Only the Modbus address must be set by the customer, depending on the use in the supply air and extract air. For other applications, data transmission speed and format must be adapted on site according to the network environment.
XM0–J6 | Setpoint value default setting via: | Actual values via: | corresponds to order key option | Menu configuration (Mode) |
Analogue operation * | analogue 0 - 10 V | analogue 0 - 10 V | V or F | CA0 |
Analogue operation * | analogue 2 - 10 V | analogue 2 - 10 V | V or F | CA2 |
Modbus operation | Modbus register setpoint | Modbus register actual value or analogue 2 - 10 V | M | CB |
* It is not possible to use the analogue interface in combination with the RJ12 connection socket provided with the XM0-J6 variant. Therefore, the configuration register 122 (interface mode) must not be changed on site. To use an analogue interface, type XM0 must be installed.
Share page
Recommend this page
Recommend this page by sending a link by mail.
Share page
Thank you for your recommendation!
Your recommendation has been sent and should arrive shortly.
Contact
We are here for you
Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
We are here for you
Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265