FK2-DV  

For diverse applications

Pressure relief dampers Type FK2-DV for use in gaseous fire suppression systems, with 6 bar pneumatic actuator (no thermal release)

Updating order code
Save configuration
Calculate price
Updating technical data
  • Media
Specification text:
Updating specification text
Show complete text Hide complete text
Initialize order code

General information

Application

The construction of the FK2-DV pressure relief damper is based on the FK2-EU fire damper. This damper is not a fire damper with thermal release mechanism, but a pressure relief damper for use in gaseous fire suppression systems (used primarily for server rooms and other IT rooms).


Special features

  • Pressure relief dampers do not require a building certificate, and they have no rating plate or CE marking

  • Approval of this pressure relief damper has to be covered by the approval of the gaseous fire suppression system; in other words, whoever builds or designs the gaseous fire suppression system has to make sure that the required pressure relief damper is included in the design and in the approval procedure

  • To ensure that the required fire resistance is achieved, the pressure relief damper has to be installed in compliance with the installation and operating manual for the FK2-EU fire damper

  • 2 inspection accesses with bayonet fixing for single hand operation

  • Meets the hygiene requirements of VDI 6022-1, VDI 3803-1, DIN 1946-4, EN 3779, of Ö-Norm H 6020 and H 6021, and of SWKI

  • Corrosion protection according to EN 15650 in connection with EN 60068-2-52

  • Closed blade air leakage to EN 1751, class 2

  • Casing air leakage to EN 1751, class C; (B + H) ≤ 700, class B

  • Low differential pressure and sound power level

  • Any airflow direction


Classification

There is no building certificate for the pressure relief damper. If the installation is carried out according to the FK2-EU installation and operating manual, the stated fire resistance class applies to the closed pressure relief damper.


Nominal sizes

  • B × H: 200 × 100 – 1500 × 800 mm (in increments of 1 mm)

  • L: 305 mm or 500 mm


Attachments

  • Pneumatic actuator, 6 bar, including limit switch subassembly for damper blade positions OPEN and CLOSED


Accessories

  • Installation kit ES for dry mortarless installation in lightweight partition walls, compartment walls, safety partition walls and radiation protection walls with metal support structure or steel support structure and cladding on both sides

  • Installation kit ES for dry mortarless installation in timber stud walls, half-timbered constructions, solid wood walls and CLT walls

  • Installation kit ES for dry mortarless installation in shaft walls with metal support structure or steel support structure as well as in shaft walls without metal support structure

  • Installation kit ES for dry mortarless installation in wooden beam ceilings and solid wood ceilings

  • Installation kit E3 for dry mortarless installation in solid walls in an existing FK-K90 or FK-EU installation subframe E1/E2

  • Installation kit EW for dry mortarless installation with installation subframe in solid walls

  • Installation kit GM for installation into solid non-load-bearing walls with flexible ceiling joint

  • Installation kit WA for dry mortarless installation on the face of solid walls and ceiling slabs

  • Installation kit WE for dry mortarless installation remote from solid walls and ceiling slabs, also remote from lightweight partition walls with metal support structure and cladding on both sides

  • Installation kit GL for dry mortarless installation in lightweight partition walls with metal support structure, cladding on both sides and a flexible ceiling joint

  • Cover grille

  • Flexible connectors

  • Circular spigots

  • Connecting subframe


Construction features

  • Rectangular or square construction, rigid casing, both flanges with fixing holes

  • Suitable for the connection of ducts, cover grilles, spigots, flexible connectors or a connecting subframe

  • The actuator is accessible and can be tested from the outside

  • Two inspection access panels, Ø110 mm, which can be opened without any tools


Materials and surfaces

Casing:

  • Galvanised sheet steel

Damper blade:

  • Special insulation material

  • Special insulation material with impregnation

Other components:

  • Damper blade shafts and drive linkage made of galvanised steel

  • Plastic plain bearings

  • EPDM and TPE seals


Supply package

Attachments and accessories that are factory mounted and supplied together with these pressure relief dampers have already been included in the order code. Depending on the installation situation, additional materials such as mortar, screws or mineral wool may be required for correct installation. Such materials are not usually included in the supply package (unless stated otherwise). Attachments and accessories have to be selected by people involved in the building project; these people also have to select and provide any additionally required installation or fixing materials and make sure that the required classifications are met.


Maintenance

General

Regular care and maintenance ensure operational readiness, functional reliability and long service life of the pressure relief dampers. The system owner is responsible for the maintenance of the dampers. The system owner is responsible for creating a maintenance plan, for defining the maintenance goals, and for the functional reliability of the equipment.


Functional test

The functional reliability of the pressure relief damper should be tested at least every six months; this has to be arranged by the system owner. If two consecutive tests, one 6 months after the other, are successful, the next test can be conducted one year later. The functional test should be done with compressed air (6 bar), not with fire suppression gas.


Maintenance

The pressure relief damper and the pneumatic actuator are not subject to wear and hence maintenance-free, but the damper should still be cleaned if necessary.


Cleaning

Pressure relief dampers may be cleaned with a dry or damp cloth. Sticky dirt or contamination may be removed with a commercial, non-aggressive cleaning agent. Do not use abrasive cleaners or tools (e.g. brushes).


Inspection

Pressure relief dampers should be inspected before commissioning. This should be followed by regular functional tests; the tests should be arranged by the system owner and should be documented. If the requirements are not fully met, suitable remedial action must be taken.


Repair

For safety reasons, repair work must only be carried out by expert qualified personnel or the manufacturer. Only original replacement parts are to be used. A functional test is required after any repair.

For more information on maintenance see the FK2-EU installation and operating manual.


Technical data

  • Nominal sizes: 200 × 100 to 1500 × 800 mm

  • Casing lengths: 305 and 500 mm

  • Volume flow rate range: up to 12000 l/s (43200 m³/h)

  • Differential pressure range: up to 2000 Pa

  • Temperature range: -20 to 50 °C

  • Upstream velocity*: ≤ 10 m/s

* Applies to uniform upstream and downstream conditions for the pressure relief damper


Technical information

  • Function
  • TECHNICAL DATA
  • QUICK SIZING
  • SPECIFICATION TEXT
  • ORDER CODE

The construction of the FK2-DV pressure relief damper is based on the FK2-EU fire damper.

The pressure relief damper is fitted with a single acting pneumatic actuator without thermal release mechanism. The damper is normally closed. If fire suppression is required, first the suppression gas pressure is reduced to 6 bar with a pressure regulator, then the gas is applied to the pneumatic actuator. The damper opens so that when the fire suppression gas is released, the excess air can escape. Two limit switches (supply package) can be used for indicating end positions OPEN and CLOSED.

Nominal sizes

200 × 100 – 1500 × 800 mm 3

Casing lengths305 and 500 mm
Volume flow rate rangeUp to 12000 l/s or 43200 m³/h
Differential pressure rangeUp to 2000 Pa

Temperature range 2

-20 – 50 °C

Upstream velocity 1

≤ 10 m/s


1
* Applies to uniform upstream and downstream conditions for the pressure relief dampers.
2 Condensation and the intake of humid air have to be avoided as otherwise operation will be impaired or not possible.
3 Damper blade with lip seal for sizes 1 and 2, damper blade with travel stop seal for size 3.


 


 


For sizes see the functional description.

Free area and resistance coefficient, width 200 – 800 mm

H(1)B
200250300350400450500550600650700750800
100A [m²]0.0130.0160.020.0230.0270.030.0340.0370.0410.0440.0480.0510.055
100ζ1.050.960.880.830.780.750.710.690.660.640.620.610.59
125A [m²]0.01750.02220.0270.03170.03650.04120.0460.05070.05550.06020.0650.06970.0745
125ζ0.930.850.780.730.690.660.630.610.590.570.550.540.52
150A [m²]0.02210.02810.03410.04010.04610.05210.05810.06410.07010.07610.08210.08810.0941
150ζ0.850.770.710.670.630.60.580.550.540.520.50.490.48
160A [m²]0.0240.030.0370.0430.050.0560.0630.0690.0760.0820.0890.0950.102
160ζ0.660.60.550.520.490.470.450.430.410.40.390.380.37
200A [m²]0.0310.040.0480.0570.0650.0740.0820.0910.0990.1080.1160.1250.133
200ζ0.740.670.620.580.550.520.50.480.470.450.440.430.41
250A [m²]0.03970.05070.06170.07270.08370.09470.10570.11670.12770.13870.14970.16070.1717
250ζ0.670.610.560.530.50.470.450.440.420.410.40.380.37
300A [m²]0.04890.06240.07590.08940.10290.11640.12990.14340.15690.17040.18390.19740.2109
300ζ0.620.560.520.490.460.440.420.40.390.380.360.350.34
350A [m²]0.05810.07410.09010.10610.12210.13810.15410.17010.18610.20210.21810.23410.2501
350ζ0.580.520.480.450.430.410.390.380.360.350.340.330.32
400A [m²]0.06730.08580.10430.12280.14130.15980.17830.19680.21530.23380.25230.27080.2893
400ζ0.540.490.460.430.40.390.370.350.340.330.320.310.3
450A [m²]0.07650.09750.11850.13950.16050.18150.20250.22350.24450.23550.25480.27410.2934
450ζ0.570.510.470.430.410.390.370.350.340.330.320.310.3
500A [m²]0.08570.10920.13270.15620.17970.20320.22670.25020.27370.2660.28780.30960.3314
500ζ0.540.480.440.410.390.370.350.340.330.310.30.30.29
550A [m²]0.12640.15070.1750.19930.22360.24790.27220.29650.32080.34510.3694
550ζ0.420.40.370.350.340.320.310.30.290.280.28
600A [m²]0.13940.16620.1930.21980.24660.27340.30020.3270.35380.38060.4074
600ζ0.410.380.360.340.320.310.30.290.280.270.27
650A [m²]0.15240.18170.2110.24030.26960.29890.32820.35750.38680.41610.4454
650ζ0.390.370.350.330.310.30.290.280.270.260.26
700A [m²]0.16540.19720.2290.26080.29260.32440.35620.3880.41980.45160.4834
700ζ0.380.350.330.320.30.290.280.270.260.250.25
750A [m²]0.17840.21270.2470.28130.31560.34990.38420.41850.45280.48710.5214
750ζ0.370.340.320.310.290.280.270.260.250.250.24
800A [m²]0.19140.22820.2650.30180.33860.37540.41220.4490.48580.52260.5594
800ζ0.360.330.320.30.290.270.260.260.250.240.23

(1) Parameters




Free area and resistance coefficient, width 850 – 1500 mm

H(1)B
900100011001200130014001500
200A [m²]0.1170.16650.14420.15780.17140.1850.1986
200ζ0.440.420.40.390.380.360.35
250A [m²]0.160.21570.19720.21580.23440.2530.2716
250ζ0.390.370.350.340.330.320.31
300A [m²]0.2030.26490.25020.27380.29740.3210.3446
300ζ0.350.340.320.310.30.290.28
350A [m²]0.2460.27460.30320.33180.36040.3890.4176
350ζ0.320.310.30.290.280.270.26
400A [m²]0.2890.32260.35620.38980.42340.4570.4906
400ζ0.30.290.280.270.260.250.25
450A [m²]0.3320.37060.40920.44780.48640.5250.5636
450ζ0.290.280.260.260.250.240.23
500A [m²]0.3750.41860.46220.50580.54940.5930.6366
500ζ0.270.260.250.240.240.230.22
550A [m²]0.4180.46660.51520.56380.61240.6610.7096
550ζ0.260.250.240.230.230.220.21
600A [m²]0.4610.51460.56820.62180.67540.7290.7826
600ζ0.250.240.230.220.220.210.2
650A [m²]0.5040.56260.62120.67980.73840.7970.8556
650ζ0.240.230.220.220.210.20.2
700A [m²]0.5470.61060.67420.73780.80140.8650.9286
700ζ0.240.230.220.210.20.20.19
750A [m²]0.590.65860.72720.79580.86440.9331.0016
750ζ0.230.220.210.20.20.190.19
800A [m²]0.6330.70660.78020.85380.92741.011.0746
800ζ0.220.210.20.20.19

0.19

0.18


(1) Parameters

Quick sizing tables provide a good overview of the volume flow rates with different sound power levels as well as of differential pressures of up to 35 Pa. Approximate intermediate values can be interpolated. Precise intermediate values can be calculated with our Easy Product Finder design program. You will find the Easy Product Finder on our website: www.trox.de/mytrox/auslegungsprogramm-easy-poduct-finder-182e16348fac3d33

Volume flow rate qv in [m³/h] at differential pressure Δpst < 35 Pa
200 – 650 mm

HLWA [dB(A)]B
200250300350400450500550600650

100

35390484577668759849938102711161205

125

3550762774586297810931208132214351548

150

356197649071048118813261464160117371873

160

3572889710631227139015501710186920272185

200

35835102812161402158617691950213023092487

250

351026126414961725195121742396261628353053

300

351232151217862056232125842844310333603615

350

351434175720712379268329843281357738704161

400

351634199723512698303933773710404143694696

450

351474185622252585293832863629396943054640

500

351647207124802878326936524031440647785146

550

3527333169359540154429483852435645

600

3529833456391943744823526657046139

650

3532323742424147305213568961606627

700

3534794026456050845600610966137112

750

3537254308487754355984652670627592

800

3539704589519357846367694175088070


Volume flow rate qv in [m³/h] at differential pressure Δpst < 35 Pa
700 – 1500 mm

HLWA [dB(A)]B
700750800900100011001200130014001500
10035129313801468
12535166017721883
15035200821422276
16035234124972653
200352664284130172633291531963476375440314308
250353270348637013422378541474506486452215576
300353869412243744172461150485482591563456774
350354451473950274895540659146419692274237922
400355020534356645597617767537327789784659031
4503549725302563062826929757282118847948010110
50035551258756237695576678374907797761047111164
550356044644068347616839291629926106871144412198
6003565706998742482699107993810763115841240113214
6503570917551800889149813107041158912469133414216
700357606809885859553105111146112405133431427615204
7503581188640915910186112031221113213142081519716181
8003586269178972710813118891295514013150641610917149



Volume flow rate qv in [m³/h] at differential pressure Δpst < 35 Pa
200 – 650 mm

HLWA [dB(A)]B
200250300350400450500550600650
10045525690841975110712391369149916291758
1254571087010881258142715951762192820942258
15045880111513231529173319352136233625342732
160451063130915521791202822622496272729583188
200451219149917752046231425802845310733683628
250451498184421832517284631733496381841374455
300451797220726072999338737704150452749025274
350452092256330223472391543544788521856466071
400452384291534313937443549275413589663756851
450452151270932473772428747945295579062826769
500452404302236194200476953295882642969717508
5504539874623524658586462705976508237
6004543535043571863827036768383228957
6504547155460618769027605830089889669
70045507658746653741881708913964810376
750455435628671167930873195221030311077
8004557926695757684409289101271095411774


Volume flow rate qv in [m³/h] at differential pressure Δpst < 35 Pa
700 – 1500 mm

HLWA [dB(A)]B
700750800900100011001200130014001500
10045188620142142
12545242225852748
15045292931263322
16045341636443871
200453887414544023842425446635071547758826285
250454771508654004993552360506575709776178136
300455645601463826088672873657999863092589884
350456494691573347142788886299366101001083011558
4004573247795826481669012985310690115221235113177
450457254773582149166101101104811980129081383114751
5004580428572910010147111861221713243142631527816289
5504588189397997111113122441336714483155931669717797
600459586102111083212065132871449915704169021809319280
6504510345110161168313006143171561716908181921947020741
7004511098118141252613938153361672218099194672082822183
7504511844126061336214861163451781619277207292217223609
8004512586133911419115777173461890120444219782350325020


The Easy Product Finder allows you to size products using your project-specific data. You will find the Easy Product Finder on our website.

Specification text

Pressure relief damper for use in gaseous fire suppression systems, construction based on the construction of FK2-EU fire dampers, square or rectangular, with two large inspection access panels that can be opened without a tool.

Pressure relief damper for installation in fire-resistant walls or ceilings, to prevent the penetration of heat, flames and smoke for up to 240 minutes.

Ready-for-operation unit, which contains a fire-resistant damper blade and a 1.2 bar pneumatic actuator (pressure off to close), without a thermal release mechanism and without building certificate. If the installation is carried out according to the FK2-EU installation and operating manual, the stated fire resistance class applies to the closed pressure relief damper.

Suitable for:

Mortar-based installation

  • In solid walls, walls made from gypsum wall boards, lightweight partition walls, compartment walls, safety partition walls and walls to provide radiation protection
  • In solid walls with partial mortaring
  • In solid walls with installation kit for flexible ceiling joints in solid walls
  • In lightweight partition walls, compartment walls, safety partition walls and radiation protection walls with metal support structure or steel support structure
  • In shaft walls with metal support structure or steel support structure
  • In timber stud walls, half-timbered constructions, solid wood walls and CLT walls
  • In and on solid ceiling slabs and in conjunction with wooden beam ceilings, solid wood ceilings and modular ceilings (Cadolto system)
  • In solid wood ceilings, wooden beam ceilings and historic wooden beam ceilings
  • Mortar-based installation into a concrete base on solid ceiling slabs
  • In hollow concrete block ceilings, hollow core slabs, ribbed ceilings and composite ceilings

Dry mortarless installation

  • In lightweight partition walls, compartment walls, safety partition walls and radiation protection walls with metal support structure or steel support structure
  • In lightweight partition walls with metal support structure and cladding on both sides, and with flexible ceiling joint
  • In timber stud walls, half-timbered constructions, solid wood walls and CLT walls
  • In solid walls with installation kit E3 in an existing FK-K90 or FK-EU installation subframe E1/E2
  • In solid walls with installation kit EW and installation subframe
  • With fire-rated gypsum board or plasterboard in lightweight partition walls with metal support structure
  • With mineral wool in lightweight partition wall with metal support structure, timber stud walls, half-timbered constructions and solid wood walls
  • In shaft walls with metal support structure or steel support structure as well as in shaft walls without metal support structure
  • In solid wood ceilings and wooden beam ceilings
  • On the face of and remote from solid walls and ceiling slabs, with an installation kit
  • Remote from lightweight partition walls (wall penetration)

Fire batt installation

  • In solid walls and ceiling slabs
  • In lightweight partition walls, compartment walls, safety partition walls and radiation protection walls with metal support structure or steel support structure
  • In timber stud walls, half-timbered constructions, solid wood walls and CLT walls

Sizes (B × H) from 200 mm × 100 mm to 1500 mm × 800 mm, intermediate sizes in increments of 1 mm. Optimised low-leakage casing, up to leakage class C to EN 1751 with low differential pressure and low sound power level.

Casing made of galvanised sheet steel.

Damper blade made of special insulation material; impregnated as an option.

Corrosion protection according to EN 15650 in connection with EN 60068-2-52 Meets the hygiene requirements of VDI 6022-1, VDI 3803-1, DIN 1946-4, EN 13779, of Ö-Norm H 6020 and H 6021, and of SWKI.

Casing length 305 mm or 500 mm with 30 mm (L = 500 mm) flange for the connection to ducts made of non-combustible or combustible materials.


Technical data

  • Nominal sizes: 200 × 100 to 1500 × 800 mm
  • Casing lengths: 305 and 500 mm
  • Volume flow rate range: up to 12000 l/s (43200 m³/h)
  • Differential pressure range: up to 2000 Pa
  • Temperature range: -20 to 50 °C
  • Upstream velocity: ≤ 10 m/s



Materialien

Casing

  • Galvanised sheet steel

Damper blade

  • Special insulation material
  • Special insulation material with impregnation

Other components

  • Damper blade shafts and drive linkage made of galvanised steel
  • Plastic plain bearings
  • EPDM and TPE seals


Technical data



  • Pressure relief damper for use in gas fire extinguishing systems, construction based on the construction of FK2-EU fire dampers
  • Meets the hygiene requirements of VDI 6022-1, VDI 3803-1, DIN 1946-4, EN 13779, of Ö-Norm H 6020 and H 6021, and of SWKI
  • Mortar-based installation with ≥ 60 mm gap between two fire dampers (flange-to-flange installation)
  • Can be installed together with FKRS-EU and FKR-EU in solid walls and ceiling slabs, lightweight partition walls, shaft walls, timber stud walls and halt-timbered constructions up to 1.2 m² total fire damper surface area
  • Two inspection access panels, Ø110 mm, with bayonet fixing (can be opened without any tools)


FK2-DV7/DE/600 × 400 × 500/ES/A0/Z38DV
|||||||
1234567
1 Type
FK2-DV
Pressure relief damper

2 Construction
No entry: standard construction
7 Galvanised casing, impregnated damper blade
3 Country of destination
DE
Germany
Other destination countries upon request

4 Nominal size [mm]
Specify width × height × length

5 Accessories 1
No entry: without accessories
ES2
E31
EW2
GM2
WA2
WE2
GL1002
GL1252
GL1502
GL1752

6 Accessories 2
No entry: without accessories
0A FR

7 Attachments
Z38DV Pneumatic spring return actuator, 6 bar

1 Only for FK2-DV with L = 305 mm2 Only for FK2-DV with L = 500 mm


Order example: FK2-DV–7/DE/600×200×500/ES/A0/Z38DV

TypeFK2-DV
ConstructionGalvanised casing, impregnated damper blade
Country of destinationGermany
Nominal size [mm]Width 600, height 400, length 500
Accessories 1ES
Accessories 2A0
AttachmentPneumatic spring return actuator, 6 bar

Downloads

product information

production {"X-Frame-Options"=>"SAMEORIGIN", "X-XSS-Protection"=>"1; mode=block", "X-Content-Type-Options"=>"nosniff", "X-Download-Options"=>"noopen", "X-Permitted-Cross-Domain-Policies"=>"none", "Referrer-Policy"=>"strict-origin-when-cross-origin", "Strict-Transport-Security"=>"max-age=31536000; includeSubDomains", "Content-Type"=>"text/html; charset=utf-8"}

Share page

Recommend this page

Recommend this page by sending a link by mail.

Fields marked with an (*) are required fields.

Share page

Thank you for your recommendation!

Your recommendation has been sent and should arrive shortly.

Contact

We are here for you

Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

Attachment (max. 10MB)

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

Contact

We are here for you

Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

Attachment (max. 10MB)

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265