TVA_img_07psd.png
VAV terminal unit, variant TVA

Easyregler-Compactregler_img_01_2020_01_DE__2_psd.psd.link
Easy controller, Compact controller

Easy controller, Compact controller

TU-ELAB-Regler_img_01_2020_01_DE__3_psd.psd.link
TROX UNIVERSAL controller, TROX LABCONTROL controller

TROX UNIVERSAL controller,

TROX LABCONTROL controller

TVA_img_08psd.png
Circular connection on the fan end

Circular connection on the fan end

00075106_0psd.psd.link
Rectangular connection on the room end

Rectangular connection on the room end

00073144_0ai.ai.link
Tested to VDI 6022

Tested to VDI 6022

TVA_img_07psd.png
Easyregler-Compactregler_img_01_2020_01_DE__2_psd.psd.link
TU-ELAB-Regler_img_01_2020_01_DE__3_psd.psd.link
TVA_img_08psd.png
00075106_0psd.psd.link
00073144_0ai.ai.link

TVA   

For extract air systems with demanding acoustic requirements

VAV terminal units for extract air control in buildings with variable air volume systems and demanding acoustic requirements

  • Highly effective integral attenuator
  • Box style construction for the reduction of the airflow velocity
  • Electronic control components for different applications (Easy, Compact, Universal, and LABCONTROL)
  • Closed blade air leakage to EN 1751, up to class 4
  • Casing air leakage to EN 1751, up to class C

 

Optional equipment and accessories

  • Acoustic cladding for the reduction of case-radiated noise
  • Secondary silencer Type TS for the reduction of air-regenerated noise

 


 


 

General information

Application
  • Rectangular VAV terminal units for use in ventilation and air conditioning systems
  • For control, inductor and shut-off tasks in the extract air area with high acoustic requirements
  • Integral attenuator
  • Closed-loop volume flow control using an external power supply
  • For variable or constant volume flow systems
  • Shut-off via override control by others
  • Can also be used for duct or room pressure control with suitable control components


Special features
  • Integral attenuator with at least 26 dB insertion loss at 250 Hz
  • Hygiene tested and certified
  • Factory set-up or programming and aerodynamic function testing
  • Setting and subsequent parameterisation on the control component possible, separate setting device may be required


Nominal sizes

125, 160, 200, 250, 315, 400


Variants
  • TVA: Extract air unit
  • TVA-D: Extract air unit with acoustic cladding
  • Units with acoustic cladding and/or secondary silencer Type TS for very demanding acoustic requirements
  • Acoustic cladding cannot be retrofitted


Parts and characteristics
  • Ready-to-commission unit which consists of mechanical parts and control components
  • Averaging effective pressure sensor for volume flow rate measurement
  • Damper blade
  • Integral attenuator
  • Factory assembled control components complete with wiring and tubing
  • Aerodynamic functional testing on a special test rig prior to shipping of each unit
  • Set-up data is given on a label or volume flow rate scale affixed to the unit
  • High control accuracy even in case of unfavourable upstream conditions

Attachments
  • EASY controller: Compact unit consisting of controller with potentiometers, effective pressure transducer and actuator
  • Compact controller: Compact unit consisting of controller with potentiometers, effective pressure transducer and actuator
  • Universal controllers: Controllers, differential pressure transducers and actuators for special applications
  • LABCONTROL: Control components for air management systems


Accessories
  • Double lip seal (factory fitted)

Useful additions
  • Secondary silencer Type TS


Construction features
  • Rectangular casing
  • Spigot on the fan end suitable for circular ducts to EN 1506 or EN 13180
  • Spigot with groove for double lip seal
  • Connection on the room end suitable for ducts
  • Baffle plate is fitted after the damper blade for optimum aerodynamic performance
  • Position of the damper blade indicated externally at shaft extension
  • Thermal and acoustic insulation (lining)


Materials and surfaces
Casing and damper blade made of galvanised sheet steel

  • Damper blade seal made of TPE plastic
  • Lining is mineral wool
  • Effective pressure sensor made of aluminium
  • Plastic plain bearings
  • Shaft and linkage made of galvanised steel

Variant with acoustic cladding (-D)
  • Acoustic cladding made of galvanised sheet steel
  • Lining is mineral wool
  • Rubber elements for the insulation of structure-borne noise

Mineral wool
  • To EN 13501, fire rating Class A1, non-combustible
  • RAL quality mark RAL-GZ 388
  • Non-hazardous to health thanks to being highly biosoluble in accordance with the Ordinance on Hazardous Substances and Note Q of the European Directive (EC) No. 1272/2008
  • Faced with glass fibre fabric as protection against erosion through airflow velocities of up to 20 m/s
  • Inert to fungal and bacterial growth


Standards and guidelines
Fulfils the hygiene requirements of

  • EN 16798, Part 3
  • VDI 6022, Sheet 1
  • DIN 1946, Part 4
  • Further standards, guidelines in accordance with hygiene certificate

Casing leakage: NS 125 – 200
  • EN 1751, Class C

NS 250 – 400
  • EN 1751, Class B

Closed blade air leakage: 
  • EN 1751, Class 4
  • Meets the increased requirements of DIN 1946, Part 4, with regard to the acceptable closed damper blade air leakage


Maintenance
  • Maintenance-free as construction and materials are not subject to wear

Technical information

Function, Technical data, Quick sizing, Specification text, Order code, Related Products

  • Function
  • TECHNICAL DATA
  • QUICK SIZING
  • SPECIFICATION TEXT
  • ORDER CODE
  • RELATED PRODUCTS
TVA_gc_01ai.png

① Integral sound attenuator

② Double lip seal

③ Damper blade

④ Effective pressure sensor

⑤ Control components, e.g. an Easy controller

The VAV terminal unit is fitted with an effective pressure sensor for measuring the volume flow rate. The control components (attachments) include an effective pressure transducer that transforms the effective pressure into an electric signal, a controller, and an actuator; the control functions can be achieved with an Easy controller or with a Compact controller or with individual components (Universal or LABCONTROL). For most applications, the setpoint value comes from a room temperature controller. The controller compares the actual value with the setpoint value and alters the control signal of the actuator if there is a difference between the two values. An integral attenuator reduces the noise that is created by the restriction of the airflow. Due to the larger rectangular cross section at the room end, the airflow velocity is about half the velocity in the circular duct.

Nominal sizes125 – 400 mm
Volume flow rate range

14 – 2007 l/s or 50 – 7228 m³/h

Volume flow rate control range (unit with dynamic effective pressure measurement)Approx. 10 – 100 % of the nominal volume flow rate
Minimum differential pressure

Up to 258 Pa (without circular silencer)

Maximum differential pressure1000 Pa
Operating temperature10 to 50 °C


Quick sizing tables provide a good overview of the minimum differential pressures, the volume flow rate accuracy and the room sound pressure levels that can be expected. Intermediate values may be achieved by interpolation.

The sound power levels for calculating the sound pressure levels were measured in the TROX laboratory according to DIN EN ISO 5135 - see "Basic information and nomenclature".

Precise results and spectral data for all control components can be calculated with our Easy Product Finder design program. The first selection criteria for the nominal size are the actual volume flow rates qvmin and qvmax.

Volume flow rate ranges and minimum differential pressure values
The minimum differential pressure of VAV terminal units is an important factor in designing the ductwork and in rating the fan including speed control. It must be ensured that for all operating conditions and for all terminal units a sufficient pressure differential is applied to each controller (Δpstat,min). The measurement points for fan speed control must be selected accordingly. The volume flow rates given for VAV terminal units depend on the nominal size and on the control component (attachment) that is installed.

Volume flow rate ranges and minimum differential pressure values
Control component dynamic measurement principle - Easy (potentiometer)
Attachment: Easy

NSqv [l/s]qv [m³/h]Δpstmin [Pa]Δqv [±%]
12514502220
1255620121269
1259835365817
1251405041311645
16024832219
1609433922289
16016559566846
1602368511351725
200371332319
20015054027379
200263948811126
20037613551652285
250582082319
25023684822349
2504131488681036
25059121281392115
315963442319
315390140526349
3156852467801046
31598035281632115
4001575632219
400638229822279
4001120403367826
400160257681371675

① Basic unit
② Basic unit with secondary silencer TS

Volume flow rate ranges and minimum differential pressure values
Control component dynamic measurement principle – qv Extended
Attachments: BC0, BL0 **, BM0, BM0-J6

NSqv [l/s]qv [m³/h]Δpstmin [Pa]Δqv [±%]
12514502220
1256824431398
125121437991236
1251756312052565
16024832219
16011441132408
1602057381021296
16029610662112695
200371332319
20018265539548
20032711761241726
20047116982583585
250582082319
250285102733498
25051318471051596
25074026662183305
315963442319
315473170338508
31585130621231596
315122844212563325
4001575632219
400774278532398
400139150061031266
400200772282152625

① Basic unit
② Basic unit with secondary silencer TS

** Control component to be discontinued in the future - please do not plan for new projects.


Volume flow rate ranges and minimum differential pressure values
Control component dynamic measurement principle - qv As standard
Attachments: BUDN, BUDNF, LN0, LK0, XB0, XB4, (B13 *, B1B *)

NSqv [l/s]qv [m³/h]Δpstmin [Pa]Δqv [±%]
12514502220
1255820723289
12510136569866
1251455221411765
16024832219
1609734923299
16017161671906
1602458821451845
200371332319
20015555728399
200272980861196
20039014041772455
250582082319
25024387424369
2504281539731106
25061222051492265
315963442319
315402144828368
3157092553861116
315101536571752275
4001575632219
400658236823298
4001159417372886
400166059781471805

① Basic unit
② Basic unit with secondary silencer TS

* Control component already discontinued

Volume flow rate ranges and minimum differential pressure values
Control component of static measurement principle
Attachments: BUSN, BUSNF, BUSS, XD0, XD4, TUN, TUNF, TUS, TUSD, ELAB (BP3 *, BPG *, BPB *, BB3 *, BBB *)

NSqv [l/s]qv [m³/h]Δpstmin [Pa]Δqv [±%]
12521733416
1256222326328
12510337272896
1251455221411765
160351233416
16010437627348
16017562974946
1602458821451845
200551954516
20016659832458
2002781001901256
20039014041772455
250853063516
25026193927418
2504371572761156
25061222051492265
3151425084515
315433155832428
3157242607891166
315101536571752275
4002318303415
400707254627338
4001184426275926
400166059781471805

① Basic unit
② Basic unit with secondary silencer TS

* Control component already discontinued


Quick sizing table for sound pressure level

The quick sizing tables are based on generally accepted attenuation and insulation levels. If the sound pressure level exceeds the required level, a larger air terminal unit and/or a silencer or acoustic cladding is required. For more information on the acoustic data, see basic information and nomenclature.

Quick sizing table for air-regenerated noise LPA
including sound attenuator variants
(entire volume flow rate range of the type)


NSqv [l/s]qv [m³/h]150 Pa500 Pa
1251450< 15< 1516< 15
1256824424162920
12512143728203324
125175631n.V.n.V.3427
1602483< 15< 1518< 15
16011441129183323
16020573831223728
1602961066n.V.n.V.3830
20037133< 15< 1519< 15
20018265519< 1528< 15
200327117618n.V.2819
2004711698n.V.n.V.2825
25058208< 15< 1520< 15
250285102719< 1527< 15
250513184719n.V.2819
2507402666n.V.n.V.2825
31596344< 15< 1517< 15
315473170324< 153017
315851306226n.V.3322
31512284421n.V.n.V.3526
400157563< 15< 1520< 15
400774278516< 152715
40013915006< 15202922
40020077228n.V.n.V.2928

Air-regenerated noise LPA [dB(A)] with static differential pressure Δpst from 150 or 500 Pa

① Basic unit

② Basic unit with secondary silencer TS

Rqd.: Specified static differential pressure Δpst is smaller than the required minimum differential pressure Δpst min.


Quick sizing table case-radiated noise LPA
including acoustic cladding variants
(entire volume flow rate range of the type)

NSqv [l/s]qv [m³/h]150 Pa500 Pa
125145015< 152116
1256824424183126
12512143727203529
125175631n.V.n.V.3631
1602483< 15< 1518< 15
16011441122173125
16020573825203529
1602961066n.V.n.V.3631
20037133< 15< 1519< 15
20018265523183126
200327117625203531
2004711698n.V.n.V.3733
25058208< 15< 1515< 15
250285102720173127
250513184723203632
2507402666n.V.n.V.3935
31596344< 15< 152116
315473170327223631
315851306229254036
31512284421n.V.n.V.4338
40015756321153024
400774278531254135
4001391500632264438
40020077228n.V.n.V.4539

Case-radiated noise LPA [dB(A)] with static differential pressure Δpst from 150 or 500 Pa

① Basic unit

② Basic unit with acoustic cladding

Rqd.: Specified static differential pressure Δpst is smaller than the required minimum differential pressure Δpst min.

Note:
Information on case-radiated noise for combinations of basic unit and optional acoustic cladding and secondary silencer can be found in the Easy Product Finder design program.

Application

Rectangular VAV terminal units for variable and constant air volume systems, suitable for extract air, available in 6 nominal sizes. High volume flow rate control accuracy. Ready-to-commission unit which consists of the mechanical parts and the electronic control components Each unit contains an averaging effective pressure sensor for volume flow rate measurement, a damper blade, and an integral sound attenuator. Factory-assembled control components complete with wiring and tubing. Effective pressure sensor with 3 mm measuring holes, hence resistant to contamination. Baffle plate is fitted after the damper blade for optimum acoustic and aerodynamic performance. Casing with acoustic and thermal insulation. Position of the damper blade indicated externally at shaft extension. Damper blade is supplied open so that the air flow will be ensured, even without the control function, except variants with defined safe position NC (normally closed). Meets the hygiene requirements of EN 16798, Part 3, of VDI 6022, Sheet 1, and of DIN 1946, Part 4.


Special features
  • Integral attenuator with at least 26 dB insertion loss at 250 Hz
  • Hygiene tested and certified
  • Factory set-up or programming and aerodynamic function testing
  • Setting and subsequent parameterisation on the control component possible, separate setting device may be required


Materials and surfaces
  • Casing and damper blade made of galvanised sheet steel
  • Damper blade seal made of TPE plastic
  • Lining is mineral wool
  • Effective pressure sensor made of aluminium
  • Plastic plain bearings

Mineral wool
  • To EN 13501, fire rating Class A1, non-combustible
  • RAL quality mark RAL-GZ 388
  • Non-hazardous to health thanks to being highly biosoluble in accordance with the Ordinance on Hazardous Substances and Note Q of the European Directive (EC) No. 1272/2008
  • Faced with glass fibre fabric as protection against erosion through airflow velocities of up to 20 m/s
  • Inert to fungal and bacterial growth

 

Connection
Fan side spigot with groove for lip seal, suitable for connecting ducts according to EN 1506 or EN 13180. Room end suitable for the connection of ducts.

Technical data
  • Nominal sizes: 125 to 400 mm
  • Volume flow rate range:  14 – 1602 l/s or 50 – 5768 m³/h
  • Minimum differential pressure: Up to 258 Pa
  • Maximum differential pressure: 1000 Pa
  • Closed blade air leakage to EN 1751, Class 4
  • Casing air leakage according to EN 1751, Class C (nominal sizes 125 - 250, Class B)


Specification text for attachment
Variable volume flow control with electronic Easy controller to connect an external control signal; actual value signal can be integrated into the central BMS.
  • Supply voltage 24 V AC/DC
  • Signal voltages 0 – 10 V DC
  • Possible override controls with external switches using volt-free contacts: CLOSED, OPEN, qᵥmin and qᵥmax
  • Potentiometers with percentage scales to set the volume flow rates qᵥmin and qᵥmax without adjustment device
  • The actual value signal relates to the nominal volume flow rate such that commissioning and subsequent adjustment are simplified
  • Volume flow rate control range: approx. 10 – 100 % of the nominal volume flow rate
  • Clearly visible external indicator light for signalling the functions: Set, not set, and power failure
  • Electrical connections with screw terminals
  • Double terminals for looping the supply voltage, i.e. for the simple connection of voltage transmission to the next controller


Sizing data
  • qᵥ _______________________ [m³/h]
  • Δpst _______________________ [Pa]

Air-regenerated noise
  • LPA _______________________[dB(A)]

Case-radiated noise
  • LPA _______________________[dB(A)]

Equivalence criteria
  • Declaration of hygiene conformity in accordance with VDI 6022, Sheet 1 (01/2018), ÖNORM H 6020 (02/2007) and ÖNORM H 6021 (09/2003)
  • Setting the volume flow rates without adjustment device via Vmin- and Vmax- potentiometer
  • Electrical connections with screw terminals, no additional terminal boxes required
  • Aerodynamic functional testing of each volume flow controller on test rigs at the factory, before a label is affixed to the controller
  • Acoustic data measured to ÖNORM EN ISO 5135:1999



Order code for volume flow control (with Easy attachment)

TVAD / 160 / D1 / Easy
|||||
12345
1 Type
TVA VAV terminal unit, extract air
 
2 Acoustic cladding

No entry required: None
D With acoustic cladding
 
3 Nominal size [mm]
125, 160, 200, 250, 315, 400
 
4 Accessories
No entry required: None
D1 Double lip seal (one side)
 
5 Attachments (control components)
Easy Volume flow controller, dynamic, analogue interface, setting qvmin and qvmax with potentiometers


Order example: TVA-D/400/Easy
Acoustic claddingYes
Nominal size400 mm
Attachments (control units)Easy controller, dynamic, analogue interface,
Adjustment qvmin and qvmax with potentiometers

 

 

Order code for volume flow control (with VARYCONTROL attachment)
TVAD / 160 / D1 / XD4 / V / 0 / 200 – 900 [m³/h] / NO
|||||||||
1234578910
1 Type
TVA VAV terminal unit, extract air
 
2 Acoustic cladding
No entry required: None
D With acoustic cladding
 
3 Nominal size [mm]
125, 160, 200, 250, 315, 400
 
4 Accessories

No entry required: None
D1 Double lip seal (one side)
 
5 Attachments (control components)
for example
BC0 Compact controller
XD4 Universal controller (VARYCONTROL)
 
7 Operating mode
F Constant value (a setpoint value)
V Variable (setpoint value range)
 
8 Signal voltage range
For the actual and setpoint value signals
0 0 – 10 V DC
2 2 – 10 V DC
 
9 Operating values for factory setting

Volume flow rates [m³/h or l/s] 
qᵥconst. (in operating mode F)
qᵥmin – qᵥmax (in operating mode V)
 
10 Damper blade position
Only spring return actuators
NO Power off to OPEN
NC Power off to CLOSE


Order example: TVA-D/160/D1/BC0/V0/200–800 m³/h
Acoustic claddingYes
Nominal size160 mm
AccessoriesDouble lip seal
Attachments (control component)Compact controller
Operating modeVariable
Signal voltage range0 – 10 V DC
Volume flow rateqvmin = 200 m³/h
qvmax = 800 m³/h


Order code for volume flow control (with TROX UNIVERSAL attachment)

TVAD / 160 / D1 / TUNF / RE / M / 0 / UMZ / / NC
|||||||||||
1234567891011
1 Type
TVA VAV terminal unit, extract air
 
2 Acoustic cladding

No entry required: None
D With acoustic cladding
 
3 Nominal size [mm]
125, 160, 200, 250, 315, 400
 
4 Accessories
No entry required: None
D1 Double lip seal (one side)
 
5 Attachments (control components)
TROX UNIVERSAL controller with
TUN Actuator (150 s)
TUNF Spring return actuator (150 s)
TUS Fast-running actuator (3 s)
TUSD Fast-running actuator (3 s), with digital communication interface (TROX HPD)
 
6 Equipment function
Room control
RE Extract air control (Room Exhaust)
 
7 Volume flow rate setting
M Master (RMF function)
S Slave
F Constant flow rate controller
 
8 Signal voltage range
0 0 – 10 V DC
2 2 – 10 V DC
 
9 Expansion of attachments
Option 1: Power supply
No entry required: 24 V AC/DC
T EM-TRF for 230 V AC
U EM-TRF-USV for 230 V AC, provides uninterruptible power supply (UPS)
 
Option 2: Digital communication interface
No entry required: None
B EM-BAC-MOD-01 for BACnet MS/TP
M EM-BAC-MOD-01 for Modbus RTU
I EM-IP for BACnet/IP, Modbus/IP and web server
R EM-IP with real time clock
 
Option 3: Automatic zero point correction
No entry required: None
Z EM-AUTOZERO with solenoid valve
 
10 Operating values for factory setting
Volume flow rates [m³/h or l/s]
Master (RMF function)
qᵥmin: Minimum volume flow rate
qᵥmax: Maximum volume flow rate
qᵥconst_Supply air: Constant supply air
qᵥconst_Extract air: Constant extract air
qᵥDiff: Supply air/extract air difference
Constant value
qᵥconst: Constant volume flow rate
Slave
No entry required
 
11 Damper blade position
Only spring return actuators
NO Power off to OPEN
NC Power off to CLOSE
 
Useful additions
Room control panel
BE-LCD 40-character display


Order example: TVA/250/TUSD/RE/S/0/Z
Nominal size250 mm
Attachments (control component)Controller TROX UNIVERSAL, fast-running actuator (3 s) with digital communication interface (TROX HPD)
Equipment functionExtract air control
Volume flow rate settingSlave
Signal voltage characteristic0 – 10 V DC
Extension of attachmentsWith expansion module EM-AUTOZERO,
solenoid valve for automatic zero point correction

  


Order code for differential pressure control (with VARYCONTROL attachment)
TVAD / 160 / D1 / XF4 / PRE / V / 0 / 30 – 60 [Pa] / NO
||||||||||
12345678910
1 Type
TVA VAV terminal unit, extract air
 
2 Acoustic cladding
No entry required: None
D With acoustic cladding
 
3 Nominal size [mm]
125, 160, 200, 250, 315, 400
 
4 Accessories
No entry required: None
D1 Double lip seal (one side)
 
5 Attachments (control components)
for example
XF0 Compact controller for duct pressure
XF4 Universal controller for duct pressure (VARYCONTROL)
 
6 Equipment function/installation location
PDE Duct pressure control, extract air
PRE Room pressure control, extract air
 
7 Operating mode
F Constant value (a setpoint value)
V Variable (setpoint value range)
 
8 Signal voltage range
For the actual and setpoint value signals
0 0 – 10 V DC
2 2 – 10 V DC
 
9 Operating values for factory setting
For duct pressure control, differential pressure [Pa] always as an absolute value without sign.
∆pconst (in operating mode F)
∆pmin – ∆pmax (in operating mode V)
 
10 Damper blade position
Only spring return actuators
NO Power off to OPEN
NC Power off to CLOSE
 
 
 
Order example: TVA/250/D1/XF0/PDE/V2/100 – 400 Pa
Nominal size250
AccessoriesDouble lip seal on one side (circular spigot)
Attachments (control components)Compact controller duct pressure control
Equipment function/installation locationDuct pressure control, extract air
Operating modeVariable
Signal voltage characteristics2 – 10 V DC
Operating values∆pmin = 100 Pa
∆pmax = 400 Pa
 


Order code for differential pressure control (with TROX UNIVERSAL attachment)
TVAD / 160 / D1 / TUNF / PRE / MFP0 / UMZ / / NC
|||||||||||
1234567891011
1 Type
TVA VAV terminal unit, extract air
 
2 Acoustic cladding
No entry required: None
D With acoustic cladding
 
3 Nominal size [mm]
125, 160, 200, 250, 315, 400
 
4 Accessories
No entry required: None
D1 Double lip seal (one side)
 
5 Attachments (control components)
TROX UNIVERSAL controller with
TUN Actuator (150 s)
TUNF Spring return actuator (150 s)
TUS Fast-running actuator (3 s)
TUSD Fast-running actuator (3 s), with digital communication interface (TROX HPD)
 
6 Equipment function
Differential pressure control
PRE Room pressure control, extract air
PDE Duct pressure control, extract air
 
7 Differential pressure setting
MFP Master, constant pressure control
MVP Master, variable differential pressure control
SFP Slave, constant pressure control
SVP Slave, variable differential pressure control
 
8 Signal voltage range

0 0 – 10 V DC
2 2 – 10 V DC
 
9 Expansion of attachments
Option 1: Power supply
No entry required: 24 V AC/DC
T EM-TRF for 230 V AC
U EM-TRF-USV for 230 V AC, provides uninterruptible power supply (UPS)
 
Option 2: Digital communication interface
No entry required: None
B EM-BAC-MOD-01 for BACnet MS/TP
M EM-BAC-MOD-01 for Modbus RTU
I EM-IP for BACnet/IP, Modbus/IP and web server
R EM-IP with real time clock
 
Option 3: Volume flow rate measurement
No entry required: None
V  EM-V Volume flow rate measurement for differential pressure control
 
Option 4: Automatic zero point correction
No entry required: None
Z EM-AUTOZERO solenoid valve (only with V)
 
10 Operating values for factory setting
Pressure [Pa], volume flow rates [m³/h or l/s]
Slave SVP
Δpmin: Minimum differential pressure
Δpmax: Maximum differential pressure
Slave SFP
Δpconst: Constant differential pressure
 
Master MFP and MVP – same as slave, but additionally:
qᵥmin: Minimum volume flow rate
qᵥmax: Maximum volume flow rate
qᵥconst_Supply air: Constant supply air
qᵥconst_Extract air: Constant extract air
qᵥDiff: Supply air/extract air difference
 
11 Damper blade position
Only spring return actuators
 
NO Power off to OPEN
NC Power off to CLOSE
 
Useful additions
 
Room control panel
BE-LCD 40-character display
 
Order differential pressure transducer for room or duct pressure control separately e.g.
PT-699 for room pressure control
PT-699-DUCT for duct pressure control, including tube and pressure tap


Order example: TVA/125/TUSD/PRE/SFP/0/V/20 Pa
Nominal size125 mm
Attachments (control components)Controller TROX UNIVERSAL; fast-running actuator (3 s) with digital communication interface (TROX HPD)
Equipment functionRoom pressure control, extract air
Effective pressure settingSlave, constant pressure control
Signal voltage characteristics0 – 10 V DC
Extension of attachmentswith expansion module EM-V,
Volume flow rate measurement for differential pressure control
Operating valuesΔpconst = 20 Pa
 


Order code for room control (with EASYLAB attachment)
TVAD/160/D1/ELAB/S/RE/UMZ/LAB/
| | | | | | | | | |
1 2 3 4 5 6 7 9 10 11

1 TypeTVA 

VAV terminal unit, extract air 

2 Acoustic cladding
No entry required: None
D With acoustic cladding 

3 Nominal size [mm]
125
160
200
250
315
400 

4 Accessories
No entry required: None
D1 Double lip seal (one side) 

5 Attachments (control components)
ELAB EASYLAB controller TCU3 

6 Actuators
S Fast-running actuator (3 s)
SD Fast-running actuator (3 s), with digital communication interface (TROX HPD) 

7 Equipment function
Room control
RE Extract air control (Room Supply)
PC Differential pressure control (Pressure Control) 

9 Expansion modules

Option 1: Power supply
No entry required: 24 V AC/DC
T EM-TRF for 230 V AC
U EM-TRF-USV for 230 V AC, provides uninterruptible power supply (UPS) 

Option 2: Digital communication interface
No entry required: None
B EM-BAC-MOD-01 for BACnet MS/TP
M EM-BAC-MOD-01 for Modbus RTU
I EM-IP for BACnet/IP, Modbus/IP and web server
R EM-IP with real time clock

Option 3: Automatic zero point correction
No entry required: None
Z EM-AUTOZERO Solenoid valve for automatic zero point correction 

10 Additional functions

Without room management function
LAB Extract air led system (laboratories)
CLR Supply air led system (clean rooms) 

With room management function
LAB-RMF Extract air led system
CLR-RMF Supply air led system 


11 Operating values for factory setting
Volume flow rates [m3/h, l/s], pressure [Pa](only required when room management function is active) 
Total extract air/supply air of room
qv1: Standard mode
qv2: Reduced operation
qv3: Increased operation
qv4: Constant supply air
qv5: Constant extract air
qv6: Supply air/extract air difference
Δpset: Setpoint pressure (only with differential pressure control) 

Useful additions
Room control panel (only for devices with RMF)
BE-LCD 40-character display

Differential pressure transducer for room pressure control equipment function must be ordered separately, e.g.
PT-699 Measuring range ±50 Pa or ±100 Pa
PT-GB604 Measuring range ±100 Pa


Order example: TVA/200/ELAB/S/RE/TZ/CLR
Acoustic claddingNone
Nominal size200 mm
Attachments (control component)EASYLAB controller TCU3
ActuatorFast-running actuator (3 s)
Equipment functionExtract air control (Room Exhaust)
Expansion modulesWith expansion module EM-TRF
Transformer for 230 V AC supply
With expansion module EM-AUTOZERO
solenoid valve for automatic zero point correction
Additional functionSupply air led system (clean rooms)
Room management function not activated


Order code for single operation (with EASYLAB attachment)
TVAD/160/D1/ELAB/S/ECE0/UMZ/
| | | | | | | | | |
1 2 3 4 5 6 7 8 9 11

1 TypeTVA 

VAV terminal unit, extract air 


2 Acoustic cladding
No entry required: None
D With acoustic cladding 

3 Nominal size [mm]
125
160
200
250
315
400 

4 Accessories
No entry required: None
D1 Double lip seal (one side) 

5 Attachments (control components)
ELAB EASYLAB controller TCU3 

6 Actuators
S Fast-running actuator (3 s)
SD Fast-running actuator (3 s), with digital interface (TROX HPD) 

7 Equipment function 
Single operation
EC Extract air controller 

8 External volume flow rate setting
E0 Voltage signal 0 – 10 V DC
E2 Voltage signal 2 – 10 V DC
2P Switch contacts (provided by others) for 2 switching steps
3P Switch contacts (provided by others) for 3 switching steps
F Volume flow rate constant value, without signalling 

9 Expansion modules

Option 1: Power supply
No entry required: 24 V AC/DC
T EM-TRF for 230 V AC
U EM-TRF-USV for 230 V AC, provides uninterruptible power supply (UPS) 

Option 2: Digital communication interface
No entry required: None
B EM-BAC-MOD-01 for BACnet MS/TP
M EM-BAC-MOD-01 for Modbus RTU
I EM-IP for BACnet/IP, Modbus/IP and web server
R EM-IP with real time clock 

Option 3: Automatic zero point correction
No entry required: None
Z EM-AUTOZERO Solenoid valve for automatic zero point correction 

11 Operating values for factory setting
Volume flow rates [m³/h or l/s]
Depending on external volume flow rate setting
E0, E2: qvmin/qvmax
2P: qv1/qv2
3P: qv1/qv2/qv3
F: qv1



Order example: TVA-D/125/ELAB/S/EC/F/350 m³/h

Acoustic claddingYes
Nominal size125 mm
Attachments (control component)EASYLAB controller TCU3
ActuatorFast-running actuator (3 s)
Equipment functionExtract air controller
External volume flow rate settingVolume flow rate constant value, without signalling
Operating valueqv1 = 350 m³/h

 

Variants, Dimensions and weight, Product details, Further product details

  • VARIANTS
  • DIMENSIONS AND WEIGHT
  • PRODUCT DETAILS
  • FURTHER PRODUCT DETAILS

VAV terminal unit, variant TVA

  • VAV terminal unit for the control of variable extract air volume flows


VAV terminal unit, variant TVA-D

  • VAV terminal unit with acoustic cladding for the control of variable extract air volume flows
  • For rooms where the case-radiated noise of the unit is not sufficiently reduced by a false ceiling
  • The circular ducts for the room under consideration must have adequate acoustic insulation (provided by others) on the fan end
  • For an optimal solution, the customer should also insulate the room-side rectangular ducts
  • Acoustic cladding cannot be retrofitted


Material

Standard construction

Order code detail Part Material
- Casing Galvanised sheet steel
- Effective pressure sensor Aluminium tube
- Damper blade Galvanised sheet steel
- Damper blade seal Thermoplastic elastomer (TPE)
- Shaft and linkage Galvanised steel
- Plain bearings Thermoplastic elastomer (TPE)
- Lining Mineral wool according to EN 13501, building material Class A1, non-combustible


Option double lip seal

Order code detail Part Material
D1 Double lip seal Rubber, EPDM


Option acoustic cladding

Order code detail Part Material
D Acoustic cladding casing Galvanised sheet steel
D Insulation of structure-borne noise  Polyethylene, PE 
D Lining Mineral wool according to EN 13501, fire rating Class A1, non-combustible

Dimensions/Weights for TVA

NS B H L ∅D A B₁ B₃ H₁ H₃ kg
125 198 152 1220 124 185 232 300 186 236 21
160 308 152 1205 159 170 342 410 186 236 25
200 458 210 1460 199 138 492 560 244 281 33
250 598 201 1540 249 97 632 700 235 311 55
315 798 252 1685 314 245 832 900 286 361 73
400 898 354 1995 399 176 932 1000 388 446 118


Dimensions/Weights for TVA

NS B H L ∅D A B₁ B₃ H₁ H₃ kg
125 198 152 1220 124 145 232 380 186 316 41
160 308 152 1205 159 130 342 490 186 316 50
200 458 210 1460 199 98 492 640 244 361 63
250 598 201 1540 249 57 632 780 235 391 95
315 798 252 1685 314 205 832 980 286 441 133
400 898 354 1995 399 136 932 1080 388 526 193




Space required for commissioning and maintenance

Sufficient space must be kept clear near any attachments to allow for commissioning and maintenance. It may be necessary to provide sufficiently sized inspection access openings.

Space required

Attachment

VARYCONTROL












Easy controller: Easy


400 300 300


Compact controller: BC0, BL0 **, BM0, BM0-J6, LK0, LN0, XB0, XD0, XF0


400 300 300


Universal controller: B13 *, B1B *, BP3 *, BPB *, BPG *, BB3 *, BBB *, BR3 *, BRB *, BRG *, BS3 *, BSB *, BSG *, BG3 *, BGB *, BH3 *, BHB *, BUDN, BUDNF, BUPN, BUPNF, BURN, BURNF, BUSN, BUSNF, BUSS, XB4, XD4, XF4


700 300 300

TROX UNIVERSAL












TROX UNIVERSAL: TUN, TUNF, TUS, TUSD


900 350 400

LABCONTROL












EASYLAB: ELAB


900 350 400

* Control components already discontinued

** Control component to be discontinued in the future - please do not plan for new projects


Installation and commissioning

  • Any installation orientation (except units with static effective pressure transducer)
  • Return edges of the casing with drilled holes suitable for M10 threaded rods
  • TVA-D: For constructions with acoustic cladding, ducts on the room side should have cladding up to the acoustic cladding of the controller


Upstream conditions

The volume flow rate accuracy Δqᵥ applies to straight upstream section. Bends, junctions or a narrowing or widening of the duct cause turbulence that may affect measurement. Duct connections, e.g. branches off the main duct, must comply with EN 1505.



Control components VARYCONTROL

AttachmentControlled variableInterfaceEffective pressure transducerActuatorManufacturer
Easy controller, dynamic
Easy

qv

0 – 10 Vintegralslow-running

integral
Compact controller, dynamic
BC0

-


0 – 10 V or 2 – 10 V or MP bus interfaceintegralslow-running

integral

BL0 **

qv

LonWorks FTT 10 interface

integralslow-running

integral
BM0

qv



Modbus RTU/BACnet MS/TP


integralslow-running

integral
BM0-J6

qv



Modbus RTU/BACnet MS/TP with RJ12 socket (for X-AIRCONTROL)


integralslow-running

integral
LN0

qv

0 – 10 V or 2 – 10 Vintegralslow-running

integral
LK0

qv



KNX interface


integralslow-running

integral
XB0

qv

0 – 10 V or 2 – 10 Vintegralslow-running

integral
Compact controller, static
XD0

qv

0 – 10 V or 2 – 10 Vintegralslow-running

integral
XF0Δp0 – 10 V or 2 – 10 Vintegral, control range adjustable 25 - 550 Paslow-running

integral
Universal controller, dynamic

B13 *

qv

0 – 10 V or 2 – 10 Vintegralslow-running

separate

B1B *

qv

0 – 10 V or 2 – 10 Vintegralspring return actuator

separate
BUDN

qv

0 - 10 V or 2 - 10 V or MP bus or Modbus RTU or BACnet MS/TPTPintegralslow-running

separate
BUDNF

qv

0 - 10 V or 2 - 10 V or MP bus or Modbus RTU or BACnet MS/TPTPintegralspring return actuator

separate
XB4

qv

0 – 10 V or 2 – 10 Vintegralspring return actuator

separate
Universal controller, static

BP3 *

qv

0 – 10 V or 2 – 10 V or MP bus interfaceindividual componentslow-running

separate

BPB *

qv

0 – 10 V or 2 – 10 V or MP bus interfaceindividual componentspring return actuator

separate

BPG *

qv

0 – 10 V or 2 – 10 V or MP bus interfaceindividual componentfast-running

separate

BB3 *

qv

2 – 10 Vindividual componentslow-running

separate

BBB *

qv

2 – 10 Vindividual componentspring return actuator

separate

BR3 *

Δp0 – 10 V or 2 – 10 V or MP bus interfaceindividual component

100 Pa
slow-running

separate

BRB *

Δp0 – 10 V or 2 – 10 V or MP bus interfaceindividual component

100 Pa
spring return actuator

separate

BRG *

Δp0 – 10 V or 2 – 10 V or MP bus interfaceindividual component

100 Pa
fast-running

separate

BS3 *

Δp0 – 10 V or 2 – 10 V or MP bus interfaceindividual component

600 Pa
slow-running

separate

BSB *

Δp0 – 10 V or 2 – 10 V or MP bus interfaceindividual component

600 Pa
spring return actuator

separate

BSG *

Δp0 – 10 V or 2 – 10 V or MP bus interfaceindividual component

600 Pa
fast-running

separate

BG3 *

Δp2 – 10 Vindividual component

100 Pa
slow-running

separate

BGB *

Δp2 – 10 Vindividual component

100 Pa
spring return actuator

separate

BH3 *

Δp2 – 10 Vindividual component

600 Pa
slow-running

separate

BHB *

Δp2 – 10 Vindividual component

600 Pa
spring return actuator

separate
BUPNΔp0 - 10 V or 2 - 10 V or MP bus or Modbus RTU or BACnet MS/TPTPintegral

Control range adjustable 25 – 450 Pa
slow-running

separate
BURNFΔp0 - 10 V or 2 - 10 V or MP bus or Modbus RTU or BACnet MS/TPTPintegral

Control range adjustable -50 ... -10 Pa or 10 ... 50 Pa
spring return actuator

separate
BURNΔp0 - 10 V or 2 - 10 V or MP bus or Modbus RTU or BACnet MS/TPTPintegral

Control range adjustable -50 ... -10 Pa or 10 ... 50 Pa
slow-running

separate
BUPNFΔp0 - 10 V or 2 - 10 V or MP bus or Modbus RTU or BACnet MS/TPTPintegral

Control range adjustable 25 – 450 Pa
spring return actuator

separate
BUSN

qv

0 - 10 V or 2 - 10 V or MP bus or Modbus RTU or BACnet MS/TPTPintegralslow-running

separate
BUSNF

qv

0 - 10 V or 2 - 10 V or MP bus or Modbus RTU or BACnet MS/TPTPintegralspring return actuator

separate
BUSS

qv

0 - 10 V or 2 - 10 V or MP bus or Modbus RTU or BACnet MS/TPTPintegralfast-running

separate
XD4

qv

0 – 10 V or 2 – 10 Vintegralspring return actuator

separate
XF4Δp0 – 10 V or 2 – 10 Vintegral, control range adjustable 25 - 550 Paspring return actuator

separate

* Control component already discontinued

** Control component to be discontinued in the future - please do not plan for new projects

qv Volume flow rate
Δp Differential pressure
① TROX, ② TROX/Belimo, ③ TROX/Gruner, ⑤ Siemens



Control components TROX UNIVERSAL

AttachmentControlled variableInterfaceEffective pressure transducerActuatorManufacturer
Universal controller, static
TUNqv, Δp

TROX Plug&Play communication system and 0 - 10 V or 2 - 10 V or with optional accessories: LonWorks, Modbus, BACnet, web server

qv = integral

Δp = separate
slow-running

separate
TUNFqv, Δp

TROX Plug&Play communication system and 0 - 10 V or 2 - 10 V or with optional accessories: LonWorks, Modbus, BACnet, web server

qv = integral

Δp = separate
spring return actuator

separate
TUSqv, Δp

TROX Plug&Play communication system and 0 - 10 V or 2 - 10 V or with optional accessories: LonWorks, Modbus, BACnet, web server

qv = integral

Δp = separate
fast-running

separate
TUSDqv, Δp

TROX Plug&Play communication system and 0 - 10 V or 2 - 10 V or with optional accessories: LonWorks, Modbus, BACnet, Webserver

qv = integral

Δp = separate

fast-running with digital communication interface (TROX HPD), separate


qv Volume flow rate
Δp Differential pressure
① TROX



Control components LABCONTROL EASYLAB

AttachmentControlled variableInterfaceEffective pressure transducerActuatorManufacturer
EASYLAB
ELAB

qv, Δp *

TROX plug and play communication system and 0 - 10 V or 2 - 10 V or with optional accessories: Modbus, BACnet, web server

qv = integral

Δp = separate

fast-running, separate



or



fast-running with digital communication interface (TROX HPD), separate

① TROX

* Controlled variable depending on the VAV terminal unit type


  • TVR, TVRK: Fume cupboard, room supply air, room extract air, room pressure, single controller
  • TVLK: Fume cupboard, single controller
  • TVJ, TVT: Room supply air, room extract air, room pressure, single controller
  • TVZ, TZ-Silenzio: Room supply air, room pressure, single controller
  • TVA, TA-Silenzio: Room extract air, room pressure, single controller

Downloads

product information

certificates

operation manuals

production {"X-Frame-Options"=>"SAMEORIGIN", "X-XSS-Protection"=>"1; mode=block", "X-Content-Type-Options"=>"nosniff", "X-Download-Options"=>"noopen", "X-Permitted-Cross-Domain-Policies"=>"none", "Referrer-Policy"=>"strict-origin-when-cross-origin", "Strict-Transport-Security"=>"max-age=31536000; includeSubDomains", "Content-Type"=>"text/html; charset=utf-8"}

Share page

Recommend this page

Recommend this page by sending a link by mail.

Fields marked with an (*) are required fields.

Share page

Thank you for your recommendation!

Your recommendation has been sent and should arrive shortly.

Contact

We are here for you

Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

Attachment (max. 10MB)

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

Contact

We are here for you

Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

Attachment (max. 10MB)

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265