2 Duct connectionNo entry: spigot
FL Flanges on both ends
3 Nominal size [mm]
125160200250315400
4 AccessoriesNo entry: none
GK Matching flanges for both ends
5 Attachments (control components)
For example
XD4 Universal controller (VARYCONTROL) with static effective pressure transducer
7 Operating mode
F Constant value (one setpoint value)
V Variable (setpoint value range)
8 Signal voltage range
For the actual and setpoint value signals
0 0 – 10 V DC
2 2 – 10 V DC
9 Operating values for factory setting
Volume flow rates [m3/h or l/s]
qᵥconst. (with operating mode F)
qᵥmin – qᵥmax (with operating mode V)
10 Damper blade position
Only with spring return actuators
NO Power off to OPEN
NC Power off to CLOSE
Order example: TVRK/160/XD4/V2/200–900 m³/h/NODuct connection | Spigot |
Nominal size | 160 mm |
Attachments (control components) | VARYCONTROL Universal controller with static effective pressure transducer and safe position function with spring return actuator |
Operating mode | Variable operation |
Signal voltage range | 2 – 10 V DC |
Operating values | qvmin = 200 m³/hqvmax = 900 m³/h |
Damper blade position | NO power off to OPEN |
,
Order code for volume flow control (with TROX UNIVERSAL attachment)
TVRK | – | FL | / | 160 | / | GK | / | TUNF | / | RE | / | M | / | 0 | / | UMZ | / | … | / | NC |
| | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
1 | | 2 | | 3 | | 4 | | 5 | | 6 | | 7 | | 8 | | 9 | | 10 | | 11 |
|
| | | |
| |
|
|
|
|
|
|
1 Type
TVRK VAV terminal unit, plastic
2 Duct connection
No entry required: Spigot
FL Flanges on both ends
3 Nominal size [mm]
125, 160, 200, 250, 315, 400
4 Accessories
No entry required: None
GK Matching flanges both sides
5 Attachments (control components)
TROX UNIVERSAL controller variants:
TUN Actuator (150 s)
TUNF Spring return actuator (150 s)
TUS Fast-running actuator (3 s)
TUSD Fast-running actuator (3 s), with digital communication interface (TROX HPD)
6 Equipment function
Room control
RE Extract air control (Room Extract)
7 Volume flow rate setting
M Master (RMF)
S Slave
F Constant flow rate controller
8 Signal voltage range
0 0 – 10 V DC
2 2 – 10 V DC
9 Expansion of attachments
Option 1: Power supply
No entry required: 24 V AC/DC
T EM-TRF for 230 V AC
U EM-TRF-USV for 230 V AC, provides uninterruptible power supply (UPS)
Option 2: Digital communication interface
No entry required: None
B EM-BAC-MOD-01 for BACnet MS/TP
M EM-BAC-MOD-01 for Modbus RTU
I EM-IP: EM-IP for BACnet/IP, Modbus/IP and web server
R EM-IP with real time clock
Option 3: Automatic zero point correction
No entry required: None
Z EM-AUTOZERO with solenoid valve
10 Operating values [m³/h or l/s]
Master
qᵥmin: Minimum volume flow rate
qᵥmax: Maximum volume flow rate
qᵥconst_Supply air: Constant supply air
qᵥconst_Extract air: Constant extract air
qᵥDiff: Supply air/extract air difference
Constant value
qᵥconst: constant volume flow rate
Slave
No entry required
11 Damper blade position
Only with control component TUNF (spring return actuator)
NO Power off to OPEN
NC Power off to CLOSE
Useful additions
Room control panel
BE-LCD 40-character display
Order example: TVRK-FL/125/TUN/RE/S/0/UZ/Flange | both ends |
Nominal size | 125 mm |
Accessories | Without |
Attachments (control components) | TROX UNIVERSAL controller, actuator run time 150 s |
Equipment function | Extract air control |
Volume flow rate setting | Slave |
Signal voltage range | 0 – 10 V DC |
Expansion modules | With expansion module EM-TRF-USV,transformer for 230 V AC and uninterruptible power supply (UPS)With expansion module EM-AUTOZERO,solenoid valve for automatic zero point correction |
Operating values | No entry required (slave) |
,
Order code for differential pressure control (with VARYCONTROL attachment)
TVRK | – | FL | / | 160 | / | GK | / | XF4 | / | PDE | / | F | 2 | / | 500 Pa | / | NO |
| | | | | | | | | | | | | | | | | | | | | | | | | | | |
1 | | 2 | | 3 | | 4 | | 5 | | 6 | | 7 | 8 | | 9 | | 10 |
|
| | | |
| |
|
|
|
|
|
|
1 Type
TVRK
VAV terminal unit, plastic
2 Duct connection
No entry: spigot
FL Flanges on both ends
3 Nominal size [mm]
125160200250315400
4 Accessories
No entry: none
GK Matching flanges for both ends
5 Attachments (control components)
For example
XF0 Compact controller for duct pressure
XF4 Universal controller for duct pressure (VARYCONTROL)
6 Equipment function/Installation location
PDS Duct pressure control, supply air
PDE Duct pressure control, extract air
PRS Room pressure control, supply air
PRE Room pressure control, extract air
7 Operating mode
F Constant value (one setpoint value)
V Variable (setpoint value range)
8 Signal voltage range
For the actual and setpoint value signals
0 0 – 10 V DC
2 2 – 10 V DC
9 Operating values for factory setting
For duct pressure control, enter the differential pressure [Pa] as an absolute value.
∆pconst. (with operating mode F)
∆pmin - ∆pmax (with operating mode V)
10 Damper blade position
Only with spring return actuators
NO Power off to OPEN
NC Power off to CLOSE
Order example: TVRK/315/XF0/PDE/F0/550 PaDuct connection | Spigot |
Nominal size | 315 mm |
Attachments (control components) | Compact controller, static, duct pressure control |
Equipment function/installation location | Duct pressure control, extract air |
Operating mode | Constant value control |
Signal voltage range | 0 – 10 V DC |
Operating value | ∆pconst. = 550 Pa |
,
Order code for differential pressure control (with TROX UNIVERSAL attachment)
TVRK | – | FL | / | 160 | / | GK | / | TUNF | / | PRE | / | MFP | / | 0 | / | UMZ | / | … | / | NC |
| | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
1 | | 2 | | 3 | | 4 | | 5 | | 6 | | 7 | | 8 | | 9 | | 10 | | 11 |
|
| | | |
| |
|
|
|
|
|
|
1 Type
TVRK VAV terminal unit, plastic
2 Duct connection
No entry required: Spigot
FL both ends
3 Nominal size [mm]
125, 160, 200, 250, 315, 400
4 Accessories
No entry required: None
GK Matching flanges both sides
5 Attachments (control components)
TROX UNIVERSAL controller variants:
TUN Actuator (150 s)
TUNF Spring return actuator (150 s)
TUS Fast-running actuator (3 s)
TUSD Fast-running actuator (3 s), with digital communication interface (TROX HPD)
6 Equipment function
Pressure control
PRE Room pressure control, extract air
PDE Duct pressure control, extract air
7 Effectivepressure setting
MFP Master, constant pressure control
MVP Master, variable differential pressure control
SFP Slave, constant pressure control
SVP Slave, variable differential pressure control
8 Signal voltage range
0 0 – 10 V DC
2 2 – 10 V DC
9 Expansion of attachments
Option 1: Power supply
No entry required: 24 V AC/DC
T EM-TRF for 230 V AC
U EM-TRF-USV for 230 V AC, provides uninterruptible power supply (UPS)
Option 2: Digital communication interface
No entry required: None
B EM-BAC-MOD-01 for BACnet MS/TP
M EM-BAC-MOD-01 for Modbus RTU
I EM-IP: EM-IP for BACnet/IP, Modbus/IP and web server
R EM-IP with real time clock
Option 3: Volume flow rate measurement
No entry required: None
V EM-V Volume flow rate measurement for differential pressure control
Option 4: Automatic zero point correction
No entry required: None
Z EM-AUTOZERO with solenoid valve (only with V)
10 Operating values [Pa, m³/h or l/s]
Slave SVP
Δpmin: Minimum differential pressure
Δpmax: Max. differential pressure
Slave SFP
Δpconst: Constant differential pressure
Master MFP and MVP – same as slave, but additionally:
qᵥmin: Minimum volume flow rate
qᵥmax: Maximum volume flow rate
qᵥconst_CLOSED: Constant supply air
qᵥconst_Exhaust: Constant extract air
qᵥDiff: Supply air/extract air difference
11 Damper blade position
Only with control component TUNF (spring return actuator)
NO Power off to OPEN
NC Power off to CLOSE
Useful additions
Room control panel
BE-LCD 40-character display
Differential pressure transducers for room pressure control or duct pressure control to be ordered separately, e.g.:
PT-699 for room pressure control
PT-699-DUCT for duct pressure control, including tube and pressure tap
Order example: TVRK/125/TUN/PDE/SVP/0/TVZ/100/350 Pa
Duct connection | Spigot |
Nominal size | 125 mm |
Attachments (control components) | TROX UNIVERSAL controller, actuator run time 150 s |
Equipment function | Duct pressure control, extract air |
Effective pressure setting | Slave, variable differential pressure control |
Signal voltage characteristics | 0 – 10 V DC |
Expansion modules | With expansion module EM-TRF, transformer for 230 V AC supply
With expansion module EM-V, for volume flow rate measurement with differential pressure control
With expansion module EM-AUTOZERO, solenoid valve for automatic zero point correction |
Operating values | ∆pmin = 100 Pa
∆pmax = 350 Pa |
,
Order code for room control (with EASYLAB attachment)
TVRK | – | FL | / | 160 | / | GK | / | ELAB | / | S | / | RE | / | UMZ | / | LAB | / | … |
| | | | | | | | | | | | | | | | | | | | | | | | | | | | |
1 | | 2 | | 3 | | 4 | | 5 | | 6 | | 8 | | 9 | | 10 | | 11 |
1 Type
TVRK
VAV terminal unit, plastic
2 Duct connection
No entry: spigot
FL Flanges on both ends
3 Nominal size [mm]
125160200250315400
4 Accessories
No entry: none
GK Matching flanges both sides
5 Attachments (control components)
ELAB EASYLAB controller TCU3
6 Actuators
S Fast-running actuator (3 s)
SD Fast-running actuator (3 s), with digital communication interface (TROX HPD)
8 Equipment function
Room control
RE Extract air control (Room Exhaust)
PC Differential pressure control (Pressure Control)
9 Expansion modules
Option 1: Power supplyNo entry: 24 V AC/DC
T EM-TRF for 230 V AC
U EM-TRF-USV for 230 V AC, provides uninterruptible power supply (UPS)
Option 2: Digital communication interface
No entry: none
B EM-BAC-MOD-01 for BACnet MS/TP
M EM-BAC-MOD-01 for Modbus RTU
I EM-IP for BACnet/IP, Modbus/IP and web server
R EM-IP with real time clock
Option 3: Automatic zero point correction
No entry: none
Z EM-AUTOZERO Solenoid valve for automatic zero point correction
10 Additional functions
Without room management function
LAB Extract air led system (laboratories)
CLR Supply air led system (clean rooms)
Room management function is active
LAB-RMF Extract air led system
CLR-RMF Supply air led system
11 Operating values [m³/h or l/s, Pa]
(only required when room management function is active)
Total extract air/supply air of room:
qv1: Standard mode
qv2: Reduced operation
qv3: Increased operation
qv4: Constant supply air
qv5: Constant extract air
qv6: Supply air/extract air difference
Δpset: Setpoint pressure (only with differential pressure control)
Useful additionsRoom control panel
BE-LCD 40-character display
The differential pressure transducer required for room pressure control (equipment function) has to be ordered separately, e.g.
PT-699 Measuring range ±50 Pa or ±100 Pa
PT-GB604 Measuring range ±100 Pa
Order example: TVRK-FL/160/GK/ELAB/S/RE/LABDuct connection | Flanges on both ends |
Nominal size | 160 mm |
Accessories | Matching flanges for both ends |
Attachments (control components) | EASYLAB controller TCU3 |
Actuator | Fast-running (3 s) |
Equipment function | Extract air control |
Additional function | Room management function has been deactivated Extract air led system |
Operating values | not required |
,
Order code for single operation (with EASYLAB attachment)
TVRK | – | FL | / | 160 | / | GK | / | ELAB | / | S | / | EC | – | E0 | / | UMZ | / | … |
| | | | | | | | | | | | | | | | | | | | | | | | | | | | |
1 | | 2 | | 3 | | 4 | | 5 | | 6 | | 7 | | 8 | | 9 | | 10 |
1 Type
TVRK
VAV terminal unit, plastic
2 Duct connection
No entry required: Spigot
FL Flanges on both ends
3 Nominal size [mm]
125160200250315400
4 Accessories
No entry required: None
GK Matching flanges both sides
5 Attachments (control components)
ELAB EASYLAB controller TCU3
6 Actuators
S Fast-running actuator (3 s)
SD Fast-running actuator (3 s), with digital communication interface (TROX HPD)
7 Equipment function
Single operation
EC Extract air controller
8 External volume flow rate setting
E0 Voltage signal 0 – 10 V DC
E2 Voltage signal 2 – 10 V DC
2P Switch contacts (provided by others) for 2 switching steps
3P Switch contacts (provided by others) for 3 switching steps
F Volume flow rate constant value, without signalling
9 Expansion modules
Option 1: Power supply
No entry required: 24 V AC/DC
T EM-TRF for 230 V AC
U EM-TRF-USV for 230 V AC, provides uninterruptible power supply (UPS)
Option 2: Digital communication interface
No entry required: None
B EM-BAC-MOD-01 for BACnet MS/TP
M EM-BAC-MOD-01 for Modbus RTU
I EM-IP for BACnet/IP, Modbus/IP and web server
R EM-IP with real time clock
Option 3: Automatic zero point correction
No entry required: None
Z EM-AUTOZERO Solenoid valve for automatic zero point correction
10 Operating values [m³/h or l/s]
Depending on external volume flow rate setting
E0, E2: qvmin/qvmax
2P: qv1/qv2
3P: qv1/qv2/qv3F: qvconst.
Order example: TVRK/200/ELAB/S/EC/E2/600/900Duct connection | Spigot |
Nominal size | 200 mm |
Attachments (control components) | EASYLAB controller TCU3 |
Actuator | Fast-running actuator (3 s) |
Equipment function | Extract air controller |
External volume flow rate setting | Voltage signal 2 – 10 V DC |
Operating values | qvmin = 600 m³/hqvmax = 900 m³/h |
,
Order code for fume cupboard control (with EASYLAB attachment)
TVRK | – | FL | / | 160 | / | GK | / | ELAB | / | S | / | FH – VS | / | UMZS | / | 200 – 900 [m³/h] |
| | | | | | | | | | | | | | | | | | | | | | | | | |
1 | | 2 | | 3 | | 4 | | 5 | | 6 | | 7 | | 8 | | 9 |
1 Type
TVRK VAV terminal unit, plastic
2 Duct connection
No entry: spigot
FL Flanges on both ends
3 Nominal size [mm]
125160200250315400
4 Accessories
No entry: none
GK Matching flanges both sides
5 Attachments (control components)
ELAB EASYLAB controller TCU3
6 Actuators
S Fast-running actuator (3 s)
SD Fast-running actuator (3 s), with digital communication interface (TROX HPD)
7 Equipment function
Fume cupboard control With face velocity transducer
FH-VS Face velocity control strategy
With face velocity transducer and sash distance sensor
FH-VD Optimised face velocity control strategy
With sash distance sensor
FH-DS Linear control strategy
FH-DV Safety-optimised control strategy
With switch contacts (by others) for switching steps
FH-2P Two switching steps
FH-3P Three switching steps
Without signalling
FH-F Volume flow rate constant value control
8 Expansion modules
Option 1: Supply voltage
No entry: 24 V AC/DC
T EM-TRF for 230 V AC
U EM-TRF-USV for 230 V AC, provides uninterruptible power supply (UPS)
Option 2: Digital communication interface
No entry: none
B EM-BAC-MOD-01 for BACnet MS/TP
M EM-BAC-MOD-01 for Modbus RTU
I EM-IP for BACnet/IP, Modbus/IP and web server
R EM-IP with real time clock
Option 3: Automatic zero point correction
No entry: none
Z EM-AUTOZERO Solenoid valve for automatic zero point correction
Option 4: Lighting
No entry: none
S EM-LIGHT, wired socket for the connection of lighting and for switching the lighting on/off using the control panel
(only in combination with connection EM-TRF or EM-TRF-USV)
9 Operating values [m³/h or l/s]
Depending on the equipment function
FH-VS: qvmin – qvmax
FH-VD: qvmin – qvmax
FH-DS: qvmin – qvmax
FH-DV: qvmin – qvmax
FH-2P: qv1/qv2
FH-3P: qv1/qv2 /qv3
FH-F: qv1
Useful additions
Control panel for fume cupboard controller, for displaying the functions of the control system according to EN 14175BE-SEG-** OLED display
BE-LCD 40-character display
Order example: TVRK/200/ELAB/S/FH-2P/TZ/600/1200
Duct connection | Spigot |
Nominal size | 200 mm |
Attachments (control components) | EASYLAB controller TCU3 with fast-running actuator |
Actuator | Fast-running actuator (3 s) |
Equipment function | Two switching steps |
Expansion module | With expansion module EM-TRF, transformer for 230 V AC supply With expansion module EM-AUTOZERO, solenoid valve for automatic zero point correction |
Operating values | qvmin = 600 m³/h qvmax = 1200 m³/h |