Application
Special characteristics
Nominal sizes
Variants
Construction
Parts and characteristics
Attachments
Useful additions
Construction features
Material and surfaces
Galvanised sheet steel variant
Powder-coated variant (P1)
Variant with acoustic cladding (-D)
Mineral wool
Standards and guidelines
Meets the hygiene requirements of
Casing air leakage
Closed damper blade air leakage:
NS 200 × 100, NS 300 × 100, NS 200 × 200
NS 300 × 200, NS 400 × 200, NS 500 × 200, NS 600 × 200
Maintenance
1 Flange for air duct profiles
2 Casing
3 Damper blade including differential pressure sensor
4 Axis with differential pressure duct
5 Electronic volume flow controller
6 Preferred airflow direction
Functional description
The damper blade works as a control element and as a differential pressure sensor. Through the differential pressure duct in the shaft, the detected differential pressure reaches the transducer (static or dynamic), and is converted into an electrical signal and compared with the setpoint value. In case of a control deviation, the integrated actuator changes the position of the damper blade. Thereby, the volume flow rate is kept constant in close tolerances over the entire differential pressure range.
Nominal sizes |
|
Volume flow rate range | 16 - 960 l/s or 58 - 3456 m³/h |
Volume flow rate control range (controller with dynamic differential pressure measurements) | approx. 10 - 100 % of the nominal volume flow rate |
Minimum differential pressure | up to 50 Pa (without secondary silencer) |
Maximum differential pressure | Control component with dynamic transducer: 900 Pa, Control component with static transducer: 600 Pa |
Operating temperature | 10 to 50 °C |
This specification text describes the general properties of the product. Texts for variants can be generated with our Easy Product Finder design programme.
Specification text
VAV terminal units in rectangular design for variable and constant volume flow systems, for supply air or extract air, in several nominal sizes. High control accuracy of set volume flow rates, even in unfavourable upstream conditions. Control range at least 1:10. Differential pressure measurement and control via damper blade. Tubeless differential pressure transmission through differential pressure duct in shaft Ready-to-commission unit which consists of the mechanical parts and the factory mounted electronic control component. Position of the damper blade indicated on the outside of the control component. Damper blade open on delivery, thus ensuring airflow even without control function, fulfils the hygiene requirements according to EN 16798 Part 3, VDI 3803 Sheet 1, VDI 6022 Sheet 1, DIN 1946, Part 4
Special characteristics
Materials and surfaces
Equivalence criteria
Connection type
Technical data
Maximum differential pressure
Closed blade leakage air flow according to EN 1751, class 2 or 3 depending on nominal size.
Specification text attachment
Life cycle assessment
A life cycle assessment is available for the product type in the form of an environmental product declaration (EPD), which has been checked and published by a programme holder.
TVE-Q | – | D | / | 300 × 200 | / | Easy |
| | | | | | | | |||
1 | 2 | 4 | 5 |
1 Type
TVE-Q VAV terminal unit
2 Acoustic cladding
No entry: without acoustic cladding
D with acoustic cladding
4 Nominal size [mm]
Specify width × height
5 Attachments (control component)
Easy Volume flow controller, dynamic, analogue interface, setting of qvmin and qvmax with potentiometers, provided by the client
Order example: TVE-Q-D/300×200/Easy
Type | TVE-Q - VAV terminal unit |
Acoustic cladding | with acoustic cladding |
Nominal size [mm] | Width 300, height 200 |
Attachments (control component) | Volume flow controller, dynamic, analogue interface, setting qvmin and qvmax with potentiometers, provided by the client |
TVE-Q | – | D | – | P1 | / | 300 × 200 | / | XB0 | / | V | 0 | / | 200 – 900 [m3/h] |
| | | | | | | | | | | | | | | | ||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
1 Type
TVE-Q VAV terminal unit
2 Acoustic cladding
No entry: without acoustic cladding
D with acoustic cladding
3 Material
No entry: Galvanised sheet steel
P1 Air duct powder-coated RAL 7001, silver grey
4 Nominal size [mm]
Specify width × height
5 Attachment (control component)
XB0 Dynamic volume flow controller, analogue interface
XM0 Dynamic volume flow controller with display, interface
Modbus RTU or analogue
XM0-J6 Dynamic volume flow controller with display, Modbus
RTU interface, RJ12 socket (for X-AIRCONTROL)
XS0 Static volume flow controller with display, Modbus RTU or analogue interface
XS0-J6 Static volume flow controller with display, Modbus RTU interface, RJ12 socket (for X-AIRCONTROL)
XDMB0 Dynamic volume flow controller with display, Modbus
RTU or BACnet MS/TP or analogue interface
XSMB0 Static volume flow controller with display, Modbus RTU or BACnet MS/TP or analogue interface
6 Operating mode
For attachments XB0, XM0, XS0
F Constant value mode, one setpoint value (no external switch contact)
V Variable operation (default setpoint value from analogue signal)
For attachments XM0, XM0-J6, XS0, XS0-J6
M Modbus RTU interface, variable operation (default setpoint value in Modbus register)
For attachments XDMB0, XSMB0
B BACnet MS/TP interface, variable operation (setpoint specification via BACnetObject)
7 Signal voltage range
Only with operating mode F or V
0 0 – 10 V DC
2 2 – 10 V DC
8 Operating values for factory setting
Volume flow rate [m³/h or l/s]
qvconst (with operating mode F)
qvmin – qvmax (for operating mode V, M, B)
Order example: TVE-Q-D-P1/500×200/XB0/V0/850-2200[m³/h]
TypeTVE-Q - VAV terminal unit | |
Acoustic cladding | with acoustic cladding |
Material | Duct powder-coated RAL 7001 (silver grey) |
Nominal size [mm] | Width 500, height 200 |
Attachment (control component) | Volume flow controller, dynamic, analogue interface |
Operating type | Variable operation |
Signal voltage range | 0 – 10 V DC |
Operating values for factory setting | 850 – 2200 [m³/h] |
Share page
Recommend this page
Recommend this page by sending a link by mail.
Share page
Thank you for your recommendation!
Your recommendation has been sent and should arrive shortly.
Contact
We are here for you
Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
We are here for you
Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265