VAV terminal unit variant TVE-Q (standard, galvanised steel)
TVE-Q_img_08psd.png
Differential pressure measurement via damper blade

Differential pressure measurement via damper blade

TVE-Q_img_09psd.png
Compact controller with display

Compact controller with display

TVE_gc_09V2ai.png
Installation directly on the main duct

Installation directly on the main duct

doc_graphic_000009.png
Tested to VDI 6022

Conforms to VDI 6022

TVE-Q_img_01psd.png
TVE-Q_img_08psd.png
TVE-Q_img_09psd.png
TVE_gc_09V2ai.png
doc_graphic_000009.png

TVE-Q 

Compact solution for low airflow velocities

Angular air terminal units for use in variable air terminal systems at low airflow velocities, even under unfavourable upstream conditions

  • Tubeless differential pressure measurement via damper blade
  • Differential pressure transmission through differential pressure duct in shaft
  • Connection terminals with protective cover, no junction box required
  • Any airflow direction if dynamic transducer is used
  • Suitable for airflow velocities from 0.8 - 8 m/s
  • Compact dimensions for use in confined ceiling areas
  • Plug-and-play solution in conjunction with X-AIRCONTROL room control
  • Exact measurement even with low airflow velocities
  • Any installation orientation also with static transducer
  • Closed blade leakage air flow according to EN 1751, at least class 2
  • Casing air leakage according to DIN EN 1751, class C
  • Volume flow range 1:10
  • Individual testing, parameterisation and adjustment of each TVE-Q on a test rig under air
  • Individual report of testing, parameterisation and adjustment available online


Optional equipment and accessories

  • Acoustic cladding for the reduction of case-radiated noise
  • Secondary silencer to reduce air-regenerated noise
  • Hot water heat exchanger Type WT for reheating the airflow

Updating order code
Save configuration
Calculate price
Updating technical data
  • Media
Specification text:
Updating specification text
Show complete text Hide complete text
Initialize order code

General information

Application

  • Square VAV terminal units for use in ventilation and air conditioning systems (AHUs)
  • For almost all tasks when controlling, restricting, or shutting off supply and extract air flows
  • Also for unfavourable upstream conditions at low air velocities
  • Closed-loop volume flow control using an external power supply
  • For variable or constant volume flow systems
  • Shut-off by override control (by the client)


Special characteristics

  • High differential pressure signal with small angle of attack
  • Factory set-up or programming and aerodynamic function testing
  • Volume flow rate can be measured and subsequently adjusted. Additional adjustment tool may be required (depending on the variant of the control component)
  • Tubeless differential pressure measurement via damper blade
  • Differential pressure transmission through differential pressure duct in axis
  • Any airflow direction if dynamic transducer is used
  • Any installation orientation also with static transducer
  • Suitable for air velocities from 0.8 - 8 m/s
  • Compact dimensions for use in confined ceiling areas


Nominal sizes

  • 200 × 100, 300 × 100
  • 200 × 200, 300 × 200, 400 × 200, 500 × 200, 600 × 200


Variants

  • TVE-Q: VAV terminal unit
  • TVE-Q-D: VAV terminal unit with acoustic cladding Units with acoustic cladding and/or secondary silencer Type TX for demanding acoustic requirements


Construction

  • Galvanised sheet steel
  • P1: Powder-coated, silver grey (RAL 7001)


Parts and characteristics

  • Ready-to-commission unit which consists of mechanical parts and control components.
  • Damper blade with integrated measuring unit
  • Axis with differential pressure duct for measured value transmission
  • Control component factory mounted
  • Each unit is tested on a special aerodynamic test rig at the factory
  • Documentation of the test rig data with a test label or a volume flow scale on the unit
  • High control accuracy even in case of unfavourable upstream conditions


Attachments

  • EASY controller: compact unit consisting of controller with potentiometers, differential pressure transducer and actuator
  • Compact controller: compact unit consisting of controller, differential pressure transducer and actuator
  • Compact controller Modbus: variant with Modbus RTU interface and disply; Plug-and-play solution in conjunction with X-AIRCONTROL room control
  • Compact controller BACnet: Variant with BACnet-MS/TP interface and display; can also be converted to Modbus RTU by the customer


Useful additions

  • Secondary silencer Type TX for the reduction of air regenerated noise
  • Hot water heat exchanger Type WT for reheating the airflow


Construction features

  • Rectangular casing
  • Flanges on both ends, suitable for air duct profiles
  • Position of the damper blade can be seen from the outside via position indicator
  • Simple exchange of the control components possible
  • Acoustic cladding cannot be retrofitted


Material and surfaces

Galvanised sheet steel variant

  • Casing, damper blade made of galvanised sheet steel
  • Shaft made of PA6 (H ≤ 200) or aluminium (H > 200)
  • Damper blade seal and sealing plug made of EPDM
  • Bearing bushes made of PBT or TPU
  • Fixing (screws, rivets) galvanised steel, aluminium

Powder-coated variant (P1)

  • Casing, damper blade galvanised with powder coating, RAL 7001, silver-grey
  • Shaft made of PA6 (H ≤ 200) or aluminium (H > 200)
  • Damper blade seal and sealing plug made of EPDM
  • Bearing bushes made of PBT or TPU
  • Fastening (screws, rivets) stainless steel, aluminium

Variant with acoustic cladding (-D)

  • Acoustic cladding made of galvanised sheet steel
  • Lining made of mineral wool

Mineral wool

  • According to EN 13501, fire rating class A1, non combustible RAL quality mark 
  • RAL-GZ 388
  • Non-hazardous to health thanks to high biosolubility according to the German Hazardous Substance Ordinance and Note Q of the European Regulation (EC) No. 1272/2008


Standards and guidelines

Meets the hygiene requirements of

  • EN 16798, Part 3
  • VDI 6022, Sheet 1
  • DIN 1946, Part 4
  • For further standards and guidelines, please refer to the hygiene certificate

Casing air leakage

  • EN 1751, Class C

Closed damper blade air leakage:

NS 200 × 100, NS 300 × 100, NS 200 × 200

  • EN 1751, Class 2

NS 300 × 200, NS 400 × 200, NS 500 × 200, NS 600 × 200

  • EN 1751, Class 3


Maintenance

  • Maintenance-free as construction and materials are not subject to wear and tear

Technical information

  • FUNCTION
  • TECHNICAL DATA
  • SPECIFICATION TEXT
  • ORDER CODE
TVE-Q_gc_09ai.png

1 Flange for air duct profiles
2 Casing
3 Damper blade including differential pressure sensor
4 Axis with differential pressure duct
5 Electronic volume flow controller
6 Preferred airflow direction

Functional description

The damper blade works as a control element and as a differential pressure sensor. Through the differential pressure duct in the shaft, the detected differential pressure reaches the transducer (static or dynamic), and is converted into an electrical signal and compared with the setpoint value. In case of a control deviation, the integrated actuator changes the position of the damper blade. Thereby, the volume flow rate is kept constant in close tolerances over the entire differential pressure range.

Nominal sizes
  • 200 × 100, 300 × 100
  • 200 × 200, 300 × 200, 400 × 200, 500 × 200, 600 × 200
Volume flow rate range

16 - 960 l/s or 58 - 3456 m³/h

Volume flow rate control range (controller with dynamic differential pressure measurements)

approx. 10 - 100 % of the nominal volume flow rate

Minimum differential pressure

up to 50 Pa (without secondary silencer)

Maximum differential pressureControl component with dynamic transducer: 900 Pa, Control component with static transducer: 600 Pa
Operating temperature10 to 50 °C

 


 

This specification text describes the general properties of the product. Texts for variants can be generated with our Easy Product Finder design programme.


Specification text

VAV terminal units in rectangular design for variable and constant volume flow systems, for supply air or extract air, in several nominal sizes. High control accuracy of set volume flow rates, even in unfavourable upstream conditions. Control range at least 1:10. Differential pressure measurement and control via damper blade. Tubeless differential pressure transmission through differential pressure duct in shaft Ready-to-commission unit which consists of the mechanical parts and the factory mounted electronic control component. Position of the damper blade indicated on the outside of the control component. Damper blade open on delivery, thus ensuring airflow even without control function, fulfils the hygiene requirements according to EN 16798 Part 3, VDI 3803 Sheet 1, VDI 6022 Sheet 1, DIN 1946, Part 4

Special characteristics

  • High differential pressure signal with small angle of attack
  • Factory set-up or programming and aerodynamic function testing
  • Volume flow rate can be measured and subsequently adjusted. Additional adjustment tool may be required (depending on the variant of the control component)
  • Tubeless differential pressure measurement via damper blade
  • Differential pressure transmission through differential pressure duct in axis
  • Any airflow direction if dynamic transducer is used
  • Any installation orientation also with static transducer
  • Suitable for air velocities from 0.8 - 8 m/s
  • Compact dimensions for use in confined ceiling areas


Materials and surfaces

  • Casing and damper blade made of galvanised sheet steel
  • Shaft made of PA6, UL94-V0 (H ≤ 200) or aluminium (H > 200)
  • Closed-cell damper blade seal made of EPDM
  • Bearings made of plastic


Equivalence criteria

  • Declaration of hygiene conformity in accordance with VDI 6022, part 1 (01/2018), ÖNORM H 6020 (03/2015) and ÖNORM H 6021 (08/2016)
  • Meets the hygiene requirements according to EN 16798 Part 3, VDI 6022 Sheet 1, DIN 1946 Part 4
  • Acoustic data determined according to ÖNORM EN ISO 5135
  • Independent of air direction - airflow in both directions
  • Suitable for airflow velocities of 0.8 – 8 m/s
  • No upstream section required (even behind T-piece)
  • Maximum control deviation 5% at qvmax without upstream section
  • Setting of the volume flow rates without adjustment device via Vmin and Vmax potentiometers
  • Electrical connections with screw terminals, no additional connection box required
  • The test report of the factory parameterisation, functional test and adjustment under air by reference measurement on a regularly validated test rig in accordance with DIN EN ISO 9001 is made available


Connection type

  • Flanges on both ends, suitable for duct connections


Technical data

  • Minimum differential pressure: up to 50 Pa (without secondary silencer)

Maximum differential pressure

  • Control component with dynamic transducer: 900 Pa
  • Control component with static transducer: 600 Pa

Closed blade leakage air flow according to EN 1751, class 2 or 3 depending on nominal size.

  • Casing air leakage according to EN1751: class C


Specification text attachment

  • Variable volume flow control with electronic Easy controller for applying a reference value and capturing an actual value to be integrated with the central BMS.
  • 24 V AC/DC supply voltage
  • Signal voltages 0 – 10 V DC
  • Possible override controls with external switches using volt free contacts: CLOSE, OPEN, qvmin and qvmax
  • Potentiometers with percentage scales to set the volume flow rates qvmin and qvmax
  • The actual value signal relates to the nominal volume flow rate so that commissioning and subsequent adjustment are simplified
  • Volume flow rate control range: approx. 10 – 100% of the nominal volume flow rate
  • Visible indicator light for signalling the various operating conditions
  • Electrical connections with screw terminals.
  • Double screw terminals for looping the supply voltage, i.e. for simple connection of voltage transmission to the next controller.


Life cycle assessment

A life cycle assessment is available for the product type in the form of an environmental product declaration (EPD), which has been checked and published by a programme holder.

Order code for volume flow control (with Easy controller)
TVE-QD/300 × 200/Easy
||||
1245

1 Type
TVE-Q VAV terminal unit

2 Acoustic cladding
No entry: without acoustic cladding
D with acoustic cladding

4 Nominal size [mm]
Specify width × height

5 Attachments (control component)
Easy Volume flow controller, dynamic, analogue interface, setting of qvmin and qvmax with potentiometers, provided by the client


Order example: TVE-Q-D/300×200/Easy

TypeTVE-Q - VAV terminal unit
Acoustic claddingwith acoustic cladding
Nominal size [mm]Width 300, height 200
Attachments (control component)

Volume flow controller, dynamic, analogue interface, setting qvmin and qvmax with potentiometers, provided by the client



Order code for volume flow control (with VARYCONTROL attachment)
TVE-QDP1/300 × 200/XB0/V0/200 – 900 [m3/h]
|||||
|||
12345
678

1 Type
TVE-Q VAV terminal unit

2 Acoustic cladding
No entry: without acoustic cladding
D with acoustic cladding

3 Material
No entry: Galvanised sheet steel
P1 Air duct powder-coated RAL 7001, silver grey

4 Nominal size [mm]
Specify width × height

5 Attachment (control component)
XB0 Dynamic volume flow controller, analogue interface
XM0 Dynamic volume flow controller with display, interface
Modbus RTU or analogue
XM0-J6 Dynamic volume flow controller with display, Modbus

RTU interface, RJ12 socket (for X-AIRCONTROL)

XS0 Static volume flow controller with display, Modbus RTU or analogue interface
XS0-J6 Static volume flow controller with display, Modbus RTU interface, RJ12 socket (for X-AIRCONTROL)
XDMB0 Dynamic volume flow controller with display, Modbus
RTU or BACnet MS/TP or analogue interface
XSMB0 Static volume flow controller with display, Modbus RTU or BACnet MS/TP or analogue interface

6 Operating mode
For attachments XB0, XM0, XS0
F Constant value mode, one setpoint value (no external switch contact)
V Variable operation (default setpoint value from analogue signal)
For attachments XM0, XM0-J6, XS0, XS0-J6
M Modbus RTU interface, variable operation (default setpoint value in Modbus register)
For attachments XDMB0, XSMB0
B BACnet MS/TP interface, variable operation (setpoint specification via BACnetObject)

7 Signal voltage range
Only with operating mode F or V
0 0 – 10 V DC
2 2 – 10 V DC

8 Operating values for factory setting
Volume flow rate [m³/h or l/s]
qvconst (with operating mode F)
qvmin – qvmax (for operating mode V, M, B)


Order example: TVE-Q-D-P1/500×200/XB0/V0/850-2200[m³/h]

Type
TVE-Q - VAV terminal unit
Acoustic claddingwith acoustic cladding
MaterialDuct powder-coated RAL 7001 (silver grey)
Nominal size [mm]Width 500, height 200
Attachment (control component)Volume flow controller, dynamic, analogue interface
Operating typeVariable operation
Signal voltage range0 – 10 V DC
Operating values for factory setting850 – 2200 [m³/h]




Downloads

product information

certificates

operation manuals

production {"X-Frame-Options"=>"SAMEORIGIN", "X-XSS-Protection"=>"1; mode=block", "X-Content-Type-Options"=>"nosniff", "X-Download-Options"=>"noopen", "X-Permitted-Cross-Domain-Policies"=>"none", "Referrer-Policy"=>"strict-origin-when-cross-origin", "Strict-Transport-Security"=>"max-age=31536000; includeSubDomains", "Content-Type"=>"text/html; charset=utf-8"}

Share page

Recommend this page

Recommend this page by sending a link by mail.

Fields marked with an (*) are required fields.

Share page

Thank you for your recommendation!

Your recommendation has been sent and should arrive shortly.

Contact

We are here for you

Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

Contact

We are here for you

Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

Attachment (max. 10MB)

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265