- VAV terminal unit for variable supply air volume flow control
Application
Special features
Nominal sizes
Variants
Parts and characteristics
Attachments
Accessories
Useful additions
Construction features
Materials and surfaces
Variant with acoustic cladding (-D)
Mineral wool
Standards and guidelines
Fulfils the hygiene requirements of
Casing leakage:
Nominal sizes 125 – 200
Nominal sizes 250 – 400
Closed blade air leakage:
Nominal sizes 125 – 160
Nominal sizes 200 – 400
Maintenance
The VAV terminal unit is fitted with an effective pressure sensor for measuring the volume flow rate.
The control components (attachments) include an effective pressure transducer that transforms the effective pressure into an electric signal, a controller, and an actuator; the control functions can be achieved with an Easy controller or with a Compact controller or with individual components (Universal or LABCONTROL).
For most applications, the setpoint value comes from a room temperature controller.
The controller compares the actual value with the setpoint value and alters the control signal of the actuator if there is a difference between the two values.
An integral attenuator reduces the noise that is created by the restriction of the airflow.
The airflow velocity at the room end is, due to the larger rectangular cross section, about half the velocity in the circular duct.
Quick sizing tables provide a good overview of the minimum differential pressures, the volume flow rate accuracy and the room sound pressure levels that can be expected. Intermediate values may be achieved by interpolation.
The sound power levels for calculating the sound pressure levels were measured in the TROX laboratory according to DIN EN ISO 5135 - see "Basic information and nomenclature".
Precise results and spectral data for all control components can be calculated with our Easy Product Finder design program. The first selection criteria for the nominal size are the actual volume flow rates qvmin and qvmax.
Volume flow rate ranges and minimum differential pressure values
The minimum differential pressure of VAV terminal units is an important factor in designing the ductwork and in rating the fan including speed control. It must be ensured that for all operating conditions and for all terminal units a sufficient pressure differential is applied to each controller (Δpstat,min). The measurement points for fan speed control must be selected accordingly. The volume flow rates given for VAV terminal units depend on the nominal size and on the control component (attachment) that is installed.
Volume flow rate ranges and minimum differential pressure values
Control component for dynamic pressure measurements – Easy (potentiometers)
Attachment: Easy
NS | qv [l/s] | qv [m³/h] | Δpstmin [Pa] | Δqv [±%] | |
---|---|---|---|---|---|
① | ② | ||||
125 | 14 | 50 | 1 | 2 | 20 |
125 | 56 | 201 | 13 | 18 | 9 |
125 | 98 | 353 | 39 | 55 | 7 |
125 | 140 | 504 | 79 | 111 | 5 |
160 | 24 | 83 | 1 | 2 | 19 |
160 | 94 | 339 | 12 | 18 | 9 |
160 | 165 | 595 | 35 | 53 | 6 |
160 | 236 | 851 | 72 | 109 | 5 |
200 | 37 | 133 | 1 | 2 | 19 |
200 | 150 | 540 | 11 | 22 | 9 |
200 | 263 | 948 | 34 | 65 | 6 |
200 | 376 | 1355 | 70 | 133 | 5 |
250 | 58 | 208 | 1 | 2 | 19 |
250 | 236 | 848 | 12 | 24 | 9 |
250 | 413 | 1488 | 37 | 72 | 6 |
250 | 591 | 2128 | 74 | 146 | 5 |
315 | 96 | 344 | 1 | 2 | 19 |
315 | 390 | 1405 | 12 | 20 | 9 |
315 | 685 | 2467 | 36 | 59 | 6 |
315 | 980 | 3528 | 73 | 121 | 5 |
400 | 157 | 563 | 1 | 1 | 19 |
400 | 638 | 2298 | 12 | 17 | 9 |
400 | 1120 | 4033 | 36 | 51 | 6 |
400 | 1602 | 5768 | 73 | 104 | 5 |
① Basic unit
② Basic unit with secondary silencer TS
Volume flow rate ranges and minimum differential pressure values
Control component dynamic measurement principle – qv Extended
Attachments: BC0, BL0 **, BM0, BM0-J6
NS | qv [l/s] | qv [m³/h] | Δpstmin [Pa] | Δqv [±%] | |
---|---|---|---|---|---|
① | ② | ||||
125 | 14 | 50 | 1 | 2 | 20 |
125 | 68 | 244 | 19 | 26 | 8 |
125 | 121 | 437 | 59 | 84 | 6 |
125 | 175 | 631 | 123 | 174 | 5 |
160 | 24 | 83 | 1 | 2 | 19 |
160 | 114 | 411 | 17 | 26 | 8 |
160 | 205 | 738 | 54 | 82 | 6 |
160 | 296 | 1066 | 113 | 170 | 5 |
200 | 37 | 133 | 1 | 2 | 19 |
200 | 182 | 655 | 17 | 31 | 8 |
200 | 327 | 1176 | 53 | 100 | 6 |
200 | 471 | 1698 | 109 | 208 | 5 |
250 | 58 | 208 | 1 | 2 | 19 |
250 | 285 | 1027 | 18 | 34 | 8 |
250 | 513 | 1847 | 56 | 110 | 6 |
250 | 740 | 2666 | 116 | 229 | 5 |
315 | 96 | 344 | 1 | 2 | 19 |
315 | 473 | 1703 | 17 | 29 | 8 |
315 | 851 | 3062 | 55 | 91 | 6 |
315 | 1228 | 4421 | 114 | 190 | 5 |
400 | 157 | 563 | 1 | 1 | 19 |
400 | 774 | 2785 | 17 | 25 | 8 |
400 | 1391 | 5006 | 55 | 78 | 6 |
400 | 2007 | 7228 | 115 | 162 | 5 |
① Basic unit
② Basic unit with secondary silencer TS
** Control component to be discontinued - do not include in new projects
Volume flow rate ranges and minimum differential pressure values
Control component dynamic measurement principle - qv As standard
Attachments: BUDN, BUDNF, LN0, LK0, LB0, XB0, XB4, (B13 *, B1B *)
NS | qv [l/s] | qv [m³/h] | Δpstmin [Pa] | Δqv [±%] | |
---|---|---|---|---|---|
① | ② | ||||
125 | 14 | 50 | 1 | 2 | 20 |
125 | 58 | 207 | 14 | 19 | 9 |
125 | 101 | 365 | 42 | 59 | 6 |
125 | 145 | 522 | 84 | 119 | 5 |
160 | 24 | 83 | 1 | 2 | 19 |
160 | 97 | 349 | 13 | 19 | 9 |
160 | 171 | 616 | 38 | 57 | 6 |
160 | 245 | 882 | 77 | 117 | 5 |
200 | 37 | 133 | 1 | 2 | 19 |
200 | 155 | 557 | 12 | 23 | 9 |
200 | 272 | 980 | 37 | 70 | 6 |
200 | 390 | 1404 | 75 | 143 | 5 |
250 | 58 | 208 | 1 | 2 | 19 |
250 | 243 | 874 | 13 | 25 | 9 |
250 | 428 | 1539 | 39 | 77 | 6 |
250 | 612 | 2205 | 80 | 157 | 5 |
315 | 96 | 344 | 1 | 2 | 19 |
315 | 402 | 1448 | 13 | 21 | 8 |
315 | 709 | 2553 | 38 | 64 | 6 |
315 | 1015 | 3657 | 78 | 130 | 5 |
400 | 157 | 563 | 1 | 1 | 19 |
400 | 658 | 2368 | 13 | 18 | 8 |
400 | 1159 | 4173 | 39 | 54 | 6 |
400 | 1660 | 5978 | 79 | 111 | 5 |
① Basic unit
② Basic unit with secondary silencer TS
* Control component already discontinued
Volume flow rate ranges and minimum differential pressure values
Control component of static measurement principle
Attachments: BUSN, BUSNF, BUSS, XD0, XD4, TUN, TUNF, TUS, TUSD, ELAB (BP3 *, BPG *, BPB *, BB3 *, BBB *)
NS | qv [l/s] | qv [m³/h] | Δpstmin [Pa] | Δqv [±%] | |
---|---|---|---|---|---|
① | ② | ||||
125 | 21 | 73 | 2 | 3 | 16 |
125 | 62 | 223 | 16 | 22 | 8 |
125 | 103 | 372 | 43 | 61 | 6 |
125 | 145 | 522 | 84 | 119 | 5 |
160 | 35 | 123 | 2 | 3 | 16 |
160 | 104 | 376 | 14 | 22 | 8 |
160 | 175 | 629 | 40 | 60 | 6 |
160 | 245 | 882 | 77 | 117 | 5 |
200 | 55 | 195 | 2 | 3 | 16 |
200 | 166 | 598 | 14 | 26 | 8 |
200 | 278 | 1001 | 38 | 73 | 6 |
200 | 390 | 1404 | 75 | 143 | 5 |
250 | 85 | 306 | 2 | 4 | 16 |
250 | 261 | 939 | 15 | 29 | 8 |
250 | 437 | 1572 | 41 | 80 | 6 |
250 | 612 | 2205 | 80 | 157 | 5 |
315 | 142 | 508 | 2 | 3 | 15 |
315 | 433 | 1558 | 15 | 24 | 8 |
315 | 724 | 2607 | 40 | 66 | 6 |
315 | 1015 | 3657 | 78 | 130 | 5 |
400 | 231 | 830 | 2 | 3 | 15 |
400 | 707 | 2546 | 15 | 21 | 8 |
400 | 1184 | 4262 | 40 | 57 | 6 |
400 | 1660 | 5978 | 79 | 111 | 5 |
① Basic unit
② Basic unit with secondary silencer TS
* Control component already discontinued
Quick sizing table for sound pressure level
The quick sizing tables are based on generally accepted attenuation and insulation levels. If the sound pressure level exceeds the required level, a larger air terminal unit and/or a silencer or acoustic cladding is required. For more information on the acoustic data, see basic information and nomenclature.
Quick sizing table for air-regenerated noise LPA
Controller including silencer
(total flow rate range of type)
NS | qv [l/s] | qv [m³/h] | 150 Pa | 500 Pa | ||
---|---|---|---|---|---|---|
① | ② | ① | ② | |||
125 | 14 | 50 | < 15 | < 15 | 17 | < 15 |
125 | 68 | 244 | 27 | 16 | 31 | 20 |
125 | 121 | 437 | 31 | 21 | 35 | 25 |
125 | 175 | 631 | 34 | n.V. | 37 | 28 |
160 | 24 | 83 | 16 | < 15 | 20 | < 15 |
160 | 114 | 411 | 31 | 21 | 34 | 24 |
160 | 205 | 738 | 35 | 25 | 38 | 28 |
160 | 296 | 1066 | 37 | n.V. | 40 | 30 |
200 | 37 | 133 | < 15 | < 15 | 18 | < 15 |
200 | 182 | 655 | 23 | < 15 | 28 | 16 |
200 | 327 | 1176 | 26 | 18 | 31 | 20 |
200 | 471 | 1698 | 28 | n.V. | 32 | 25 |
250 | 58 | 208 | < 15 | < 15 | < 15 | < 15 |
250 | 285 | 1027 | 20 | < 15 | 27 | 16 |
250 | 513 | 1847 | 26 | 18 | 32 | 20 |
250 | 740 | 2666 | 30 | n.V. | 35 | 26 |
315 | 96 | 344 | < 15 | < 15 | 22 | < 15 |
315 | 473 | 1703 | 23 | < 15 | 30 | 17 |
315 | 851 | 3062 | 27 | 20 | 33 | 22 |
315 | 1228 | 4421 | 30 | n.V. | 36 | 26 |
400 | 157 | 563 | < 15 | < 15 | 22 | < 15 |
400 | 774 | 2785 | 23 | < 15 | 31 | 18 |
400 | 1391 | 5006 | 27 | 22 | 34 | 24 |
400 | 2007 | 7228 | 31 | n.V. | 37 | 29 |
Air-regenerated noise LPA [dB(A)] at static differential pressure Δpst of 150 or 500 Pa
① Basic unit
② Basic unit with secondary silencer TS
n.a.: The specified static differential pressure Δpst is lower than the minimum differential pressure Δpst min.
Quick sizing table for case-radiated noise LPA
Controller including acoustic cladding
(total flow rate range of type)
NS | qv [l/s] | qv [m³/h] | 150 Pa | 500 Pa | ||
---|---|---|---|---|---|---|
① | ② | ① | ② | |||
125 | 14 | 50 | 17 | < 15 | 24 | < 15 |
125 | 68 | 244 | 25 | 15 | 32 | 21 |
125 | 121 | 437 | 29 | 20 | 35 | 25 |
125 | 175 | 631 | 32 | 23 | 37 | 28 |
160 | 24 | 83 | 15 | < 15 | 23 | < 15 |
160 | 114 | 411 | 25 | 17 | 33 | 24 |
160 | 205 | 738 | 30 | 23 | 37 | 28 |
160 | 296 | 1066 | 34 | 27 | 40 | 32 |
200 | 37 | 133 | 18 | < 15 | 27 | 15 |
200 | 182 | 655 | 28 | 20 | 36 | 26 |
200 | 327 | 1176 | 33 | 25 | 39 | 30 |
200 | 471 | 1698 | 36 | 29 | 42 | 33 |
250 | 58 | 208 | 18 | < 15 | 28 | 18 |
250 | 285 | 1027 | 27 | 20 | 37 | 28 |
250 | 513 | 1847 | 32 | 25 | 40 | 32 |
250 | 740 | 2666 | 36 | 29 | 43 | 35 |
315 | 96 | 344 | 19 | < 15 | 30 | 19 |
315 | 473 | 1703 | 29 | 20 | 39 | 30 |
315 | 851 | 3062 | 34 | 26 | 43 | 34 |
315 | 1228 | 4421 | 39 | 31 | 46 | 38 |
400 | 157 | 563 | 23 | < 15 | 34 | 24 |
400 | 774 | 2785 | 31 | 23 | 41 | 33 |
400 | 1391 | 5006 | 36 | 28 | 45 | 37 |
400 | 2007 | 7228 | 40 | 33 | 47 | 40 |
Case-radiated noise LPA [dB(A)] at static differential pressure Δpst of 150 or 500 Pa
① Basic unit
② Basic unit with acoustic cladding
n.a.: The specified static differential pressure Δpst is lower than the minimum differential pressure Δpst min.
Note:
Information on case-radiated noise for combinations of basic unit and optional acoustic cladding and secondary silencer can be found in the Easy Product Finder design program.
Rectangular VAV terminal units for variable and constant air volume systems, suitable for supply air, available in 6 nominal sizes. High control accuracy (even with upstream bend R = 1D). Ready-to-commission unit which consists of the mechanical parts and the electronic control components. Each unit contains an averaging effective pressure sensor for volume flow rate measurement, a damper blade, and an integral sound attenuator. Factory-assembled control components complete with wiring and tubing. Effective pressure sensor with 3 mm measuring holes, hence resistant to contamination. Baffle plate is fitted after the damper blade for optimum acoustic and aerodynamic performance. Casing with acoustic and thermal insulation. Position of the damper blade indicated externally at shaft extension. The damper blade is factory set to open position, which allows a ventilation airflow even without control; this does not apply to variants with defined safe position NC (normally closed). Meets the hygiene requirements of EN 16798, Part 3, of VDI 6022, Sheet 1, and of DIN 1946, Part 4.
Special features
Materials and surfaces
Mineral wool:
Connection
Equivalence criteria
Technical data
Specification text for attachment
Variable volume flow control with electronic Easy controller to connect an external control signal; actual value signal can be integrated into the central BMS.
Sizing data
Air-regenerated noise
Case-radiated noise
TVZ | – | D | / | 160 | / | D1 | / | Easy |
| | | | | | | | | | ||||
1 | 2 | 3 | 4 | 5 | ||||
TVZ
VAV terminal unit, supply air
2 Acoustic cladding
No entry required: None
D With acoustic cladding
3 Nominal size [mm]1
25160200250315400
4 Accessories
No entry required: None
D1 Double lip seal
5 Attachments (control components)
Easy Volume flow controller, dynamic, analogue interface, setting qvmin and qvmax with potentiometers
Acoustic cladding | With |
Nominal size | 200 mm |
Attachments (control components) | Easy volume flow controller, dynamic, analogue interface, setting of qvmin and qvmax with potentiometers |
TVZ | – | D | / | 160 | / | D1 | / | XB4 | / | V | 0 | / | 200 – 900 [m³/h] | / | NO |
| | | | | | | | | | | | | | | | | | |||||||
1 | 2 | 3 | 4 | 5 | 7 | 8 | 9 | 10 | |||||||
2 Acoustic cladding
No entry required: None
D With acoustic cladding
3 Nominal size [mm]
125160200250315400
4 Accessories
No entry required: None
D1 Double lip seal
5 Attachments
(control components)
For example
BC0 Compact controller
XB4 Universal controller (VARYCONTROL)
7 Operating mode
F Constant value (a setpoint value)
V Variable (setpoint value range)
8 Signal voltage range
For the actual and setpoint value signals
0 0 – 10 V DC
2 2 – 10 V DC
9 Operating values for factory setting
Volume flow rate [m³/h or l/s]
qᵥconst (in operating mode F)
qᵥmin – qᵥmax (in operating mode V)
10 Damper blade position
Only spring return actuators
NO Power off to OPEN
NC Power off to CLOSE
Acoustic cladding | with |
Nominal size | 160 mm |
Accessories | Double lip seal |
Attachments (control component) | Compact controller, dynamic, analogue interface |
Operating mode | Variable |
Signal voltage range | 0 – 10 V DC |
Operating values | qᵥmin = 180 m³/hqᵥmax = 850 m³/h |
TVZ | – | D | / | 160 | / | D1 | / | TUNF | / | RS | / | M | / | 0 | / | UMZ | / | … | / | NC |
| | | | | | | | | | | | | | | | | | | | | | ||||||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | ||||||||||
2 Acoustic cladding
No entry required: None
D With acoustic cladding
3 Nominal size [mm]
125160200250315400
4 Accessories
No entry required: None
D1 Double lip seal
5 Attachments (control components)
TROX UNIVERSAL controller with
TUN Actuator (150 s)
TUNF Spring return actuator (150 s)
TUS Fast-running actuator (3 s)
TUSD Fast-running actuator (3 s), with digital communication interface (TROX HPD)
6 Equipment function Room control
RS Supply air control (Room Supply)
7 Volume flow rate setting
M Master (RMF function)
S Slave
F Constant flow rate controller
8 Signal voltage range
0 0 – 10 V DC
2 2 – 10 V DC
9 Expansion modules
Option 1: Power supply
No entry required: 24 V AC/DC
T EM-TRF for 230 V AC
U EM-TRF-USV for 230 V AC, provides uninterruptible power supply (UPS)
Option 2: Digital communication interface
No entry required: None
B EM-BAC-MOD-01 for BACnet MS/TP
M EM-BAC-MOD-01 for Modbus RTU
I EM-IP for BACnet/IP, Modbus/IP and web server
R EM-IP with real time clock
Option 3: Automatic zero point correction
No entry required: None
Z EM-AUTOZERO with solenoid valve
10 Operating values for factory setting
Volume flow rate [m³/h or l/s]
Master (RMF function)
qᵥmin: Minimum volume flow rate
qᵥmax: Maximum volume flow rate
qᵥconst_CLOSED: Constant supply air
qᵥconst_Exhaust: Constant extract air
qᵥDiff: Supply air/extract air difference Constant value
qᵥconst: Constant volume flow rate Slave
No entry required
11 Damper blade position
Only spring return actuators
NO Power off to OPEN
NC Power off to CLOSE
Useful additions Room control panel
BE-LCD 40-character display
Nominal size | 200 mm |
Attachments (control components) | TROX UNIVERSAL controller, fast-running actuator (3 s) |
Equipment function | Supply air control |
Volume flow rate setting | Master (RMF function) |
Signal voltage range | 0 – 10 V DC |
Expansion modules | with expansion module EM-TRF-USV Transformer for 230 V AC supply with UPS functionwith expansion module EM-BAC-MOD Modbus RTU interfacewith expansion module EM-AUTOZERO Solenoid valve for automatic zero point correction |
Operating values | qᵥmin = 600 m³/h, qᵥmax = 1250 m³/h qᵥconst_CLOSED = 0 m³/h, qᵥconst_Exhaust = 0 m³/h qᵥDiff = -100 m³/h |
TVZ | – | D | / | 160 | / | D1 | / | XF4 | / | PRS | / | F | 0 | / | 30 – 60 [Pa] | / | NO |
| | | | | | | | | | | | | | | | | | | | ||||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 |
3 Nominal size [mm]
125160200250315400
4 AccessoriesNo entry required: None
D1 Double lip seal
5 Attachments (control components)
For example
XF0 Compact controller for duct pressure
XF4 Universal controller for duct pressure (VARYCONTROL)
6 Equipment function/installation location
PDS Duct pressure control, supply air
PRS Room pressure control, supply air
7 Operating mode
F Constant value (a setpoint value)
V Variable (setpoint value range)
8 Signal voltage range
For the actual and setpoint value signals
0 0 – 10 V DC
2 2 – 10 V DC
9 Operating values for factory setting
Differential pressure [Pa]
For duct pressure control, enter the differential pressure [Pa] as an absolute value
Δpconst (in operating mode F)
Δpmin – Δpmax (in operating mode V)
10 Damper blade position
Only spring return actuators
NO Power off to OPEN
NC Power off to CLOSE
Nominal size | 160 mm |
Accessories | Double lip seal (one end) |
Attachments (control components) | VARYCONTROL Universal controller for duct pressure |
Equipment function | Duct pressure control, supply air |
Operating mode | Constant value |
Signal voltage range | 2 – 10 V DC |
Operating value | 470 Pa |
Damper blade position | Power off to OPEN |
TVZ | – | D | / | 160 | / | D1 | / | TUNF | / | PRS | / | MFP | / | 0 | / | UMZ | / | … | / | NC |
| | | | | | | | | | | | | | | | | | | | | | ||||||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | ||||||||||
2 Acoustic cladding
No entry required: None
D With acoustic cladding
3 Nominal size [mm]
125160200250315400
4 Accessories
No entry required: None
D1 Double lip seal
5 Attachments (control components)
TROX UNIVERSAL controller with
TUN Actuator (150 s)
TUNF Spring return actuator (150 s)
TUS Fast-running actuator (3 s)
TUSD Fast-running actuator (3 s), with digital communication interface (TROX HPD)
6 Equipment functionY
Pressure control
PRS Room pressure control, supply air
PDS Duct pressure control, supply air
7 Differential pressure setting
MFP Master, constant pressure control
MVP Master, variable differential pressure control
SFP Slave, constant pressure control
SVP Slave, variable differential pressure control
8 Signal voltage range
0 0 - 10 V DC
2 2 - 10 V DC
9 Expansion modules
Option 1: Power supply
No entry required: 24 V AC/DC
T EM-TRF for 230 V AC
U EM-TRF-USV for 230 V AC, provides uninterruptible power supply (UPS)
Option 2: Digital communication interface
No entry required: None
B EM-BAC-MOD-01 for BACnet MS/TP
M EM-BAC-MOD-01 for Modbus RTU
I EM-IP for BACnet/IP, Modbus/IP and web server
R EM-IP with real time clock
Option 3: Volume flow rate measurement
No entry required: None
V EM-V Volume flow rate measurement for differential pressure control
Option 4: Automatic zero point correction
No entry required: None
Z EM-AUTOZERO solenoid valve (only with V)
10 Operating values for factory setting
Pressure [Pa], volume flow rate [m³/h or l/s]
Slave SVP
Δpmin: minimum differential pressure
Δpmax: maximum differential pressure Slave SFP
Δpconst: Constant differential pressure Master MFP and MVP like Slave, but additionally
qᵥmin: minimum volume flow rate
qᵥmax: maximum volume flow rate
qᵥconst_CLOSED: constant supply air
qᵥconst_Exhaust: constant extract air
qᵥDiff: Supply air/extract air difference
11 Damper blade position
Only spring return actuators
NO Power off to OPEN
NC Power off to CLOSE
Useful additions Room control panel
BE-LCD 40-character display
The differential pressure transducer required for room or duct pressure control has to be ordered separately, e.g.
PT-699 for room pressure control
PT-699-DUCT for duct pressure control, including tube and pressure tap
Order example: TVZ/200/TUS/PRS/MVP/0/B/-10/-60/ 600/1250/ 0/ 0/-100
Nominal size | 200 mm |
Attachments (control components) | TROX UNIVERSAL controller, fast-running actuator (3 s) |
Equipment function | Room pressure control, supply air |
Differential pressure setting | Master, variable differential pressure control |
Signal voltage range | 0 – 10 V DC |
Expansion modules | with expansion module EM-BAC-MODBACnet MS/TP interface card |
Operating values | Δpmin = -10 Pa, Δpmax = -60 Paqᵥmin = 600 m³/h,qᵥmax = 1250 m³/hqᵥconst_Supply air = 0 m³/h, qᵥconst_Extract air = 0 m³/hqᵥDiff = - 100 m³/h |
TVZ | – | D | / | 160 | / | D1 | / | ELAB | / | S | / | RS | / | UMZ | / | LAB | / | … |
| | | | | | | | | | | | | | | | | | | | |||||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 9 | 10 | 11 |
3 Nominal size [mm]
125160200250315400
4 Accessories
No entry required: None
D1 Double lip seal
5 Attachments (control components)
ELAB EASYLAB controller TCU3
6 Actuators
S Fast-running actuator (3 s)
SD Fast-running actuator (3 s), with digital communication interface (TROX HPD)
7 Equipment function Room control
RS Supply air control (Room Supply)
PC Differential pressure control (Pressure Control)
9 Expansion modules
Option 1: Power supply
No entry required: 24 V AC/DC
T EM-TRF for 230 V AC
U EM-TRF-USV for 230 V AC, provides uninterruptible power supply (UPS)
Option 2: Digital communication interface
No entry required: None
B EM-BAC-MOD-01 for BACnet MS/TP
M EM-BAC-MOD-01 for Modbus RTU
I EM-IP for BACnet/IP, Modbus/IP and web server
R EM-IP with real time clock
Option 3: Automatic zero point correction
No entry required: None
Z EM-AUTOZERO
Solenoid valve for automatic zero point correction
10 Additional functions
Without room management function
LAB Extract air led system (laboratories)
CLR Supply air led system (clean rooms)
With room management function
LAB-RMF Extract air led system
CLR-RMF Supply air led system
11 Operating values for factory setting
(only required when room management function is active)
Volume flow rate [m³/h or l/s], pressure [Pa]
Total extract air/supply air of room:
qv1: Standard mode
qv2: reduced operation
qv3: increased operation
qv4: constant supply air
qv5: constant extract air
qv6: Supply air/extract air difference
ΔpSet: Setpoint pressure (only with differential pressure control)
Useful additions
Room control panel (only for devices with RMF)
BE-LCD 40-character display
The differential pressure transducer required for room pressure control (equipment function) has to be ordered separately, e.g.
PT-699 Measuring range ±50 Pa or ±100 Pa
PT-GB604 Measuring range ±100 Pa
Acoustic cladding | without |
Nominal size | 200 mm |
Attachments (control components) | EASYLAB controller TCU3 with fast-running actuator (3 s) |
Actuator | Fast-running actuator (3 s), with digital communication interface |
Equipment function | Supply air control (Room Supply) |
Additional function | Supply air led system with room management function |
Operating values | qv1 = 3500 m³/hqv2 = 1000 m³/hqv3 = 5000 m³/hqv4 = 250 m³/hqv5 = 0qv6 = -150 m³/h |
TVZ | – | D | / | 160 | / | D1 | / | ELAB | / | S | / | SC | – | E0 | / | UMZ | / | … |
| | | | | | | | | | | | | | | | | | | | |||||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 11 |
2 Acoustic cladding
No entry required: None
D With acoustic cladding
3 Nominal size [mm]
125160200250315400
4 Accessories
No entry required: None
D1 Double lip seal
5 Attachments (control components)
ELAB EASYLAB controller TCU3
6 Actuators
S Fast-running actuator (3 s)
SD Fast-running actuator (3 s), with digital communication interface (TROX HPD)
7 Equipment function
Single operation
SC Supply air controller
8 External volume flow rate setting
E0 Voltage signal 0 – 10 V DC
E2 Voltage signal 2 – 10 V DC
2P Switch contacts (provided by others) for 2 switching steps
3P Switch contacts (provided by others) for 3 switching steps
F Volume flow rate constant value, without signalling
9 Expansion modules
Option 1: Power supply
No entry required: 24 V AC/DC
T EM-TRF for 230 V AC
U EM-TRF-USV for 230 V AC, provides uninterruptible power supply (UPS)
Option 2: Digital communication interface
No entry required: None
B EM-BAC-MOD-01 for BACnet MS/TP
M EM-BAC-MOD-01 for Modbus RTU
I EM-IP for BACnet/IP, Modbus/IP and web server
R EM-IP with real time clock
Option 3: Automatic zero point correction
No entry required: None
Z EM-AUTOZERO Solenoid valve for automatic zero point correction
11 Operating values for factory setting
Volume flow rate [m³/h or l/s]
Depending on external volume flow rate setting
E0, E2: qᵥmin/qᵥmax
2P: qᵥ1/qᵥ2
3P: qᵥ1/qᵥ2 /qᵥ3
F: qᵥ1
Nominal size | 315 mm |
Attachments (control components) | EASYLAB controller TCU3 |
Actuator | Fast-running actuator (3 s) |
Equipment function | Supply air controller |
External volume flow rate setting | Volume flow rate constant value |
Operating value | qᵥ1 = 2800 m³/h |
NG | B | H | L | ∅D | A | B₁ | B₃ | H₁ | H₃ | W | kg |
---|---|---|---|---|---|---|---|---|---|---|---|
125 | 198 | 152 | 1185 | 124 | 150 | 232 | 300 | 186 | 236 | 115 | 21 |
160 | 308 | 152 | 1235 | 159 | 200 | 342 | 410 | 186 | 236 | 115 | 25 |
200 | 458 | 210 | 1520 | 199 | 200 | 492 | 560 | 244 | 281 | 115 | 33 |
250 | 598 | 201 | 1690 | 249 | 250 | 632 | 700 | 235 | 311 | 215 | 55 |
315 | 798 | 252 | 1690 | 314 | 250 | 832 | 900 | 286 | 361 | 215 | 73 |
400 | 898 | 354 | 2070 | 399 | 250 | 932 | 1000 | 388 | 446 | 215 | 118 |
NG | B | H | L | ∅D | A | B₁ | B₃ | H₁ | H₃ | W | kg |
---|---|---|---|---|---|---|---|---|---|---|---|
125 | 198 | 152 | 1185 | 124 | 110 | 232 | 380 | 186 | 316 | 155 | 41 |
160 | 308 | 152 | 1235 | 159 | 160 | 342 | 490 | 186 | 316 | 155 | 50 |
200 | 458 | 210 | 1520 | 199 | 160 | 492 | 640 | 244 | 361 | 155 | 63 |
250 | 598 | 201 | 1690 | 249 | 210 | 632 | 780 | 235 | 391 | 255 | 95 |
315 | 798 | 252 | 1690 | 314 | 210 | 832 | 980 | 286 | 441 | 255 | 133 |
400 | 898 | 354 | 2070 | 399 | 210 | 932 | 1080 | 388 | 526 | 255 | 193 |
Installation and commissioning
Upstream conditions
The volume flow rate accuracy Δqᵥ applies to straight upstream section of the duct. Bends, junctions or a narrowing or widening of the duct cause turbulence that may affect measurement. Duct connections, e.g. branches off the main duct, must comply with EN 1505. Some installation situations require straight duct sections upstream.
VARYCONTROL control components
Attachment | Controlled variable | Interface | Pressure transducer | Actuator | Manufacturer |
---|---|---|---|---|---|
Easy controller, dynamic | |||||
Easy | qv | 0 – 10 V | integral | slow-running integral | ① |
Compact controller, dynamic | |||||
BC0 | qv | 0 – 10 V or 2 – 10 V or MP bus interface | integral | slow-running integral | ② |
BL0 ** | qv | LonWorks FTT 10 interface | integral | slow-running integral | ② |
BM0 | qv | Modbus RTU/BACnet MS/TP | integral | slow-running integral | ② |
BM0-J6 | qv | Modbus RTU/BACnet MS/TP with RJ12 socket (for X-AIRCONTROL) | integral | slow-running integral | ② |
LK0 | qv | KNX interface | integral | slow-running integral | ⑤ |
LN0 | qv | 0 – 10 V or 2 – 10 V | integral | slow-running integral | ⑤ |
XB0 | qv | 0 – 10 V or 2 – 10 V | integral | slow-running integral | ③ |
Compact controller, static | |||||
XD0 | qv | 0 – 10 V or 2 – 10 V | integral | slow-running integral | ③ |
XF0 | Δp | 0 – 10 V or 2 – 10 V | integral, control range adjustable 25 - 550 Pa | slow-running integral | ③ |
Universal controller, dynamic | |||||
B13 * | qv | 0 – 10 V or 2 – 10 V | integral | slow-running separate | ② |
B1B * | qv | 0 – 10 V or 2 – 10 V | integral | spring return actuator separate | ② |
BUDN | qv | 0 - 10 V or 2 - 10 V or MP bus or Modbus RTU or BACnet MS/TP | integral | slow-running separate | ② |
BUDNF | qv | 0 - 10 V or 2 - 10 V or MP bus or Modbus RTU or BACnet MS/TP | integral | spring return actuator separate | ② |
XB4 | qv | 0 – 10 V or 2 – 10 V | integral | spring return actuator separate | ③ |
VARYCONTROL Universal controller, static | |||||
BB3 * | qv | 2 – 10 V | individual component | slow-running separate | ② |
BBB * | qv | 2 – 10 V | individual component | spring return actuator separate | ② |
BG3 * | Δp | 2 – 10 V | individual component 100 Pa | slow-running separate | ② |
BGB * | Δp | 2 – 10 V | individual component 100 Pa | spring return actuator separate | ② |
BH3 * | Δp | 2 – 10 V | individual component 600 Pa | slow-running separate | ② |
BHB * | Δp | 2 – 10 V | individual component 600 Pa | spring return actuator separate | ② |
BP3 * | qv | 0 – 10 V or 2 – 10 V or MP bus interface | individual component | slow-running separate | ② |
BPB * | qv | 0 – 10 V or 2 – 10 V or MP bus interface | individual component | spring return actuator separate | ② |
BPG * | qv | 0 – 10 V or 2 – 10 V or MP bus interface | individual component | fast-running separate | ② |
BR3 * | Δp | 0 – 10 V or 2 – 10 V or MP bus interface | individual component 100 Pa | slow-running separate | ② |
BRB * | Δp | 0 – 10 V or 2 – 10 V or MP bus interface | individual component 100 Pa | spring return actuator separate | ② |
BRG * | Δp | 0 – 10 V or 2 – 10 V or MP bus interface | individual component 100 Pa | fast-running separate | ② |
BS3 * | Δp | 0 – 10 V or 2 – 10 V or MP bus interface | individual component 600 Pa | slow-running separate | ② |
BSB * | Δp | 0 – 10 V or 2 – 10 V or MP bus interface | individual component 600 Pa | spring return actuator separate | ② |
BSG * | Δp | 0 – 10 V or 2 – 10 V or MP bus interface | individual component 600 Pa | fast-running separate | ② |
BUPN | Δp | 0 - 10 V or 2 - 10 V or MP bus or Modbus RTU or BACnet MS/TP | integral Control range adjustable 25 – 450 Pa | slow-running separate | ② |
BUPNF | Δp | 0 - 10 V or 2 - 10 V or MP bus or Modbus RTU or BACnet MS/TP | integral Control range adjustable 25 – 450 Pa | spring return actuator separate | ② |
BURN | Δp | 0 - 10 V or 2 - 10 V or MP bus or Modbus RTU or BACnet MS/TP | integral Control range adjustable -50 ... -10 Pa or 10 ... 50 Pa | slow-running separate | ② |
BURNF | Δp | 0 - 10 V or 2 - 10 V or MP bus or Modbus RTU or BACnet MS/TP | integral Control range adjustable -50 ... -10 Pa or 10 ... 50 Pa | spring return actuator separate | ② |
BUSN | qv | 0 - 10 V or 2 - 10 V or MP bus or Modbus RTU or BACnet MS/TP | integral | slow-running separate | ② |
BUSNF | qv | 0 - 10 V or 2 - 10 V or MP bus or Modbus RTU or BACnet MS/TP | integral | spring return actuator separate | ② |
BUSS | qv | 0 - 10 V or 2 - 10 V or MP bus or Modbus RTU or BACnet MS/TP | integral | fast-running separate | ② |
XD4 | qv | 0 – 10 V or 2 – 10 V | integral | spring return actuator separate | ③ |
XF4 | Δp | 0 – 10 V or 2 – 10 V | integral, control range adjustable 25 - 550 Pa | spring return actuator separate | ③ |
* Control component has been discontinued
** Control component to be discontinued - do not include in new projects
qv Volume flow rate
Δp Differential pressure
① TROX, ② TROX/Belimo, ③ TROX/Gruner, ⑤ Siemens
TROX UNIVERSAL control components
Attachment | Controlled variable | Interface | Pressure transducer | Actuator | Manufacturer |
---|---|---|---|---|---|
VARYCONTROL Universal controller, static | |||||
TUN | qv, Δp | TROX Plug&Play communication system and 0 - 10 V or 2 - 10 V or with optional accessories: Modbus, BACnet, web server | qv = integral Δp = separate | slow-running separate | ① |
TUNF | qv, Δp | TROX Plug&Play communication system and 0 - 10 V or 2 - 10 V or with optional accessories: Modbus, BACnet, web server | qv = integral Δp = separate | spring return actuator separate | ① |
TUS | qv, Δp | TROX Plug&Play communication system and 0 - 10 V or 2 - 10 V or with optional accessories: Modbus, BACnet, web server | qv = integral Δp = separate | fast-running separate | ① |
TUSD | qv, Δp | TROX Plug&Play communication system and 0 - 10 V or 2 - 10 V or with optional accessories: Modbus, BACnet, web server | qv = integral Δp = separate | fast-running with digital communication interface (TROX HPD), separate | ① |
qv Volume flow rate
Δp Differential pressure
① TROX
LABCONTROL EASYLAB control components
Attachment | Controlled variable | Interface | Pressure transducer | Actuator | Manufacturer |
---|---|---|---|---|---|
EASYLAB | |||||
ELAB | qv, Δp * | TROX plug and play communication system and 0 - 10 V or 2 - 10 V or with optional accessories: Modbus, BACnet, web server | qv = integral Δp = separate | fast-running, separate or fast-running with digital communication interface (TROX HPD), separate | ③ |
① TROX
* The controlled variable depends on the type of VAV terminal unit
Space required for commissioning and maintenance
Sufficient space must be kept clear near any attachments to allow for commissioning and maintenance. It may be necessary to provide sufficiently sized inspection access openings.
Space required
Attachment | ① | ② | ③ |
---|---|---|---|
VARYCONTROL | |||
Easy controller: Easy | 400 | 300 | 300 |
Compact controller: BC0, BL0 *, BM0, BM0-J6, LN0, LK0, XB0, XD0, XF0 | 400 | 300 | 300 |
Universal controller: B13 *, B1B *, BB3 *, BBB *, BG3 *, BGB *, BH3 *, BHB *, BP3 *, BPB *, BPG *, BR3 *, BRB *, BRG *, BS3 *, BSB *, BSG *, BUDN, BUDNF, BUSN, BUSNF, BUSS, BUPN, BUPNF, BURN, BURNF, XB4, XD4, XF4 | 700 | 300 | 300 |
TROX UNIVERSAL | |||
TROX UNIVERSAL: TUN, TUS, TUSD | 900 | 350 | 400 |
LABCONTROL | |||
EASYLAB: ELAB | 900 | 350 | 400 |
* Control component has been discontinued
** Control component to be discontinued - do not include in new projects
Attachment | ① | ② | ③ |
---|---|---|---|
Inspection access | 400 | 300 | 300 |
Share page
Recommend this page
Recommend this page by sending a link by mail.
Share page
Thank you for your recommendation!
Your recommendation has been sent and should arrive shortly.
Contact
We are here for you
Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
We are here for you
Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265