Order code for volume flow control (with Easy attachment)
TVZ | – | D | / | 160 | / | D1 | / | Easy |
| | | | | | | | | | | | | |
1 | | 2 | | 3 | | 4 | | 5 |
| |
|
|
|
|
|
|
|
|
1 TypeTVZ
VAV terminal unit, supply air
2 Acoustic cladding
No entry required: None
D With acoustic cladding
3 Nominal size [mm]1
25160200250315400
4 Accessories
No entry required: None
D1 Double lip seal
5 Attachments (control components)
Easy Volume flow controller, dynamic, analogue interface, setting qvmin and qvmax with potentiometers
Order example: TVZ-D/200/EasyAcoustic cladding | With |
Nominal size | 200 mm |
Attachments (control components) | Easy volume flow controller, dynamic, analogue interface, setting of qvmin and qvmax with potentiometers |
,
Order code for volume flow control (with VARYCONTROL attachment)
TVZ | – | D | / | 160 | / | D1 | / | XB4 | / | V | 0 | / | 200 – 900 [m³/h] | / | NO |
| | | | | | | | | | | | | | | | | | | | | | | | |
1 | | 2 | | 3 | | 4 | | 5 | | 7 | 8 | | 9 | | 10 |
| |
|
|
|
|
|
|
|
|
1 Type
TVZ
VAV terminal unit, supply air
2 Acoustic cladding
No entry required: None
D With acoustic cladding
3 Nominal size [mm]
125160200250315400
4 Accessories
No entry required: None
D1 Double lip seal
5 Attachments
(control components)
For example
BC0 Compact controller
XB4 Universal controller (VARYCONTROL)
7 Operating mode
F Constant value (a setpoint value)
V Variable (setpoint value range)
8 Signal voltage range
For the actual and setpoint value signals
0 0 – 10 V DC
2 2 – 10 V DC
9 Operating values for factory setting
Volume flow rate [m³/h or l/s]
qᵥconst (in operating mode F)
qᵥmin – qᵥmax (in operating mode V)
10 Damper blade position
Only spring return actuators
NO Power off to OPEN
NC Power off to CLOSE
Order example: TVZ-D/160/D1/BC0/V0/180–850 m³/hAcoustic cladding | with |
Nominal size | 160 mm |
Accessories | Double lip seal |
Attachments (control component) | Compact controller, dynamic, analogue interface |
Operating mode | Variable |
Signal voltage range | 0 – 10 V DC |
Operating values | qᵥmin = 180 m³/hqᵥmax = 850 m³/h |
,
Order code for volume flow control (with TROX UNIVERSAL attachment)
TVZ | – | D | / | 160 | / | D1 | / | TUNF | / | RS | / | M | / | 0 | / | UMZ | / | … | / | NC |
| | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
1 | | 2 | | 3 | | 4 | | 5 | | 6 | | 7 | | 8 | | 9 | | 10 | | 11 |
| | | |
|
|
|
|
|
|
|
|
1 Type
TVZ
VAV terminal unit, supply air
2 Acoustic cladding
No entry required: None
D With acoustic cladding
3 Nominal size [mm]
125160200250315400
4 Accessories
No entry required: None
D1 Double lip seal
5 Attachments (control components)
TROX UNIVERSAL controller with
TUN Actuator (150 s)
TUNF Spring return actuator (150 s)
TUS Fast-running actuator (3 s)
TUSD Fast-running actuator (3 s), with digital communication interface (TROX HPD)
6 Equipment function Room control
RS Supply air control (Room Supply)
7 Volume flow rate setting
M Master (RMF function)
S Slave
F Constant flow rate controller
8 Signal voltage range
0 0 – 10 V DC
2 2 – 10 V DC
9 Expansion modules
Option 1: Power supply
No entry required: 24 V AC/DC
T EM-TRF for 230 V AC
U EM-TRF-USV for 230 V AC, provides uninterruptible power supply (UPS)
Option 2: Digital communication interface
No entry required: None
B EM-BAC-MOD-01 for BACnet MS/TP
M EM-BAC-MOD-01 for Modbus RTU
I EM-IP for BACnet/IP, Modbus/IP and web server
R EM-IP with real time clock
Option 3: Automatic zero point correction
No entry required: None
Z EM-AUTOZERO with solenoid valve
10 Operating values for factory setting
Volume flow rate [m³/h or l/s]
Master (RMF function)
qᵥmin: Minimum volume flow rate
qᵥmax: Maximum volume flow rate
qᵥconst_CLOSED: Constant supply air
qᵥconst_Exhaust: Constant extract air
qᵥDiff: Supply air/extract air difference Constant value
qᵥconst: Constant volume flow rate Slave
No entry required
11 Damper blade position
Only spring return actuators
NO Power off to OPEN
NC Power off to CLOSE
Useful additions Room control panel
BE-LCD 40-character display
Order example: TVZ 200/TUS/RS/M/0/UMZ/600/1250/0/0/-100Nominal size | 200 mm |
Attachments (control components) | TROX UNIVERSAL controller, fast-running actuator (3 s) |
Equipment function | Supply air control |
Volume flow rate setting | Master (RMF function) |
Signal voltage range | 0 – 10 V DC |
Expansion modules | with expansion module EM-TRF-USV Transformer for 230 V AC supply with UPS functionwith expansion module EM-BAC-MOD Modbus RTU interfacewith expansion module EM-AUTOZERO Solenoid valve for automatic zero point correction |
Operating values | qᵥmin = 600 m³/h, qᵥmax = 1250 m³/h qᵥconst_CLOSED = 0 m³/h, qᵥconst_Exhaust = 0 m³/h qᵥDiff = -100 m³/h |
,
Order code for differential pressure control (with VARYCONTROL attachment)
TVZ | – | D | / | 160 | / | D1 | / | XF4 | / | PRS | / | F | 0 | / | 30 – 60 [Pa] | / | NO |
| | | | | | | | | | | | | | | | | | | | | | | | | | | |
1 | | 2 | | 3 | | 4 | | 5 | | 6 | | 7 | 8 | | 9 | | 10 |
1 Type
TVZ
VAV terminal unit, supply air 2 Acoustic cladding
No entry required: None
D With acoustic cladding
3 Nominal size [mm]
125160200250315400
4 AccessoriesNo entry required: None
D1 Double lip seal
5 Attachments (control components)
For example
XF0 Compact controller for duct pressure
XF4 Universal controller for duct pressure (VARYCONTROL)
6 Equipment function/installation location
PDS Duct pressure control, supply air
PRS Room pressure control, supply air
7 Operating mode
F Constant value (a setpoint value)
V Variable (setpoint value range)
8 Signal voltage range
For the actual and setpoint value signals
0 0 – 10 V DC
2 2 – 10 V DC
9 Operating values for factory setting
Differential pressure [Pa]
For duct pressure control, enter the differential pressure [Pa] as an absolute value
Δpconst (in operating mode F)
Δpmin – Δpmax (in operating mode V)
10 Damper blade position
Only spring return actuators
NO Power off to OPEN
NC Power off to CLOSE
Order example: TVZ/160/D1/XF4/PDS/F/2/470 Pa/NONominal size | 160 mm |
Accessories | Double lip seal (one end) |
Attachments (control components) | VARYCONTROL Universal controller for duct pressure |
Equipment function | Duct pressure control, supply air |
Operating mode | Constant value |
Signal voltage range | 2 – 10 V DC |
Operating value | 470 Pa |
Damper blade position | Power off to OPEN |
,
Order code for differential pressure control (with TROX UNIVERSAL attachment)
TVZ | – | D | / | 160 | / | D1 | / | TUNF | / | PRS | / | MFP | / | 0 | / | UMZ | / | … | / | NC |
| | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
1 | | 2 | | 3 | | 4 | | 5 | | 6 | | 7 | | 8 | | 9 | | 10 | | 11 |
| | | |
|
|
|
|
|
|
|
|
1 Type
TVZ
VAV terminal unit, supply air
2 Acoustic cladding
No entry required: None
D With acoustic cladding
3 Nominal size [mm]
125160200250315400
4 Accessories
No entry required: None
D1 Double lip seal
5 Attachments (control components)
TROX UNIVERSAL controller with
TUN Actuator (150 s)
TUNF Spring return actuator (150 s)
TUS Fast-running actuator (3 s)
TUSD Fast-running actuator (3 s), with digital communication interface (TROX HPD)
6 Equipment functionY
Pressure control
PRS Room pressure control, supply air
PDS Duct pressure control, supply air
7 Differential pressure setting
MFP Master, constant pressure control
MVP Master, variable differential pressure control
SFP Slave, constant pressure control
SVP Slave, variable differential pressure control
8 Signal voltage range
0 0 - 10 V DC
2 2 - 10 V DC
9 Expansion modules
Option 1: Power supply
No entry required: 24 V AC/DC
T EM-TRF for 230 V AC
U EM-TRF-USV for 230 V AC, provides uninterruptible power supply (UPS)
Option 2: Digital communication interface
No entry required: None
B EM-BAC-MOD-01 for BACnet MS/TP
M EM-BAC-MOD-01 for Modbus RTU
I EM-IP for BACnet/IP, Modbus/IP and web server
R EM-IP with real time clock
Option 3: Volume flow rate measurement
No entry required: None
V EM-V Volume flow rate measurement for differential pressure control
Option 4: Automatic zero point correction
No entry required: None
Z EM-AUTOZERO solenoid valve (only with V)
10 Operating values for factory setting
Pressure [Pa], volume flow rate [m³/h or l/s]
Slave SVP
Δpmin: minimum differential pressure
Δpmax: maximum differential pressure Slave SFP
Δpconst: Constant differential pressure Master MFP and MVP like Slave, but additionally
qᵥmin: minimum volume flow rate
qᵥmax: maximum volume flow rate
qᵥconst_CLOSED: constant supply air
qᵥconst_Exhaust: constant extract air
qᵥDiff: Supply air/extract air difference
11 Damper blade position
Only spring return actuators
NO Power off to OPEN
NC Power off to CLOSE
Useful additions Room control panel
BE-LCD 40-character display
The differential pressure transducer required for room or duct pressure control has to be ordered separately, e.g.
PT-699 for room pressure control
PT-699-DUCT for duct pressure control, including tube and pressure tap
Order example: TVZ/200/TUS/PRS/MVP/0/B/-10/-60/ 600/1250/ 0/ 0/-100
Nominal size | 200 mm |
Attachments (control components) | TROX UNIVERSAL controller, fast-running actuator (3 s) |
Equipment function | Room pressure control, supply air |
Differential pressure setting | Master, variable differential pressure control |
Signal voltage range | 0 – 10 V DC |
Expansion modules | with expansion module EM-BAC-MODBACnet MS/TP interface card |
Operating values | Δpmin = -10 Pa, Δpmax = -60 Paqᵥmin = 600 m³/h,qᵥmax = 1250 m³/hqᵥconst_Supply air = 0 m³/h, qᵥconst_Extract air = 0 m³/hqᵥDiff = - 100 m³/h |
,
Order code for room control (with EASYLAB attachment)
TVZ | – | D | / | 160 | / | D1 | / | ELAB | / | S | / | RS | / | UMZ | / | LAB | / | … |
| | | | | | | | | | | | | | | | | | | | | | | | | | | | |
1 | | 2 | | 3 | | 4 | | 5 | | 6 | | 7 | | 9 | | 10 | | 11 |
1 Type
TVZ
VAV terminal unit, supply air 2 Acoustic cladding
No entry required: None
D With acoustic cladding
3 Nominal size [mm]
125160200250315400
4 Accessories
No entry required: None
D1 Double lip seal
5 Attachments (control components)
ELAB EASYLAB controller TCU3
6 Actuators
S Fast-running actuator (3 s)
SD Fast-running actuator (3 s), with digital communication interface (TROX HPD)
7 Equipment function Room control
RS Supply air control (Room Supply)
PC Differential pressure control (Pressure Control)
9 Expansion modules
Option 1: Power supply
No entry required: 24 V AC/DC
T EM-TRF for 230 V AC
U EM-TRF-USV for 230 V AC, provides uninterruptible power supply (UPS)
Option 2: Digital communication interface
No entry required: None
B EM-BAC-MOD-01 for BACnet MS/TP
M EM-BAC-MOD-01 for Modbus RTU
I EM-IP for BACnet/IP, Modbus/IP and web server
R EM-IP with real time clock
Option 3: Automatic zero point correction
No entry required: None
Z EM-AUTOZERO
Solenoid valve for automatic zero point correction
10 Additional functions
Without room management function
LAB Extract air led system (laboratories)
CLR Supply air led system (clean rooms)
With room management function
LAB-RMF Extract air led system
CLR-RMF Supply air led system
11 Operating values for factory setting
(only required when room management function is active)
Volume flow rate [m³/h or l/s], pressure [Pa]
Total extract air/supply air of room:
qv1: Standard mode
qv2: reduced operation
qv3: increased operation
qv4: constant supply air
qv5: constant extract air
qv6: Supply air/extract air difference
ΔpSet: Setpoint pressure (only with differential pressure control)
Useful additions
Room control panel (only for devices with RMF)
BE-LCD 40-character display
The differential pressure transducer required for room pressure control (equipment function) has to be ordered separately, e.g.
PT-699 Measuring range ±50 Pa or ±100 Pa
PT-GB604 Measuring range ±100 Pa
Order example: TVZ/200/ELAB/SD/RS/CLR-RMF/3500/1000/5000/250/0/-150Acoustic cladding | without |
Nominal size | 200 mm |
Attachments (control components) | EASYLAB controller TCU3 with fast-running actuator (3 s) |
Actuator | Fast-running actuator (3 s), with digital communication interface |
Equipment function | Supply air control (Room Supply) |
Additional function | Supply air led system with room management function |
Operating values | qv1 = 3500 m³/hqv2 = 1000 m³/hqv3 = 5000 m³/hqv4 = 250 m³/hqv5 = 0qv6 = -150 m³/h |
Order code for single operation (with EASYLAB attachment)
TVZ | – | D | / | 160 | / | D1 | / | ELAB | / | S | / | SC | – | E0 | / | UMZ | / | … |
| | | | | | | | | | | | | | | | | | | | | | | | | | | | |
1 | | 2 | | 3 | | 4 | | 5 | | 6 | | 7 | | 8 | | 9 | | 11 |
1 Type
TVZ
VAV terminal unit, supply air
2 Acoustic cladding
No entry required: None
D With acoustic cladding
3 Nominal size [mm]
125160200250315400
4 Accessories
No entry required: None
D1 Double lip seal
5 Attachments (control components)
ELAB EASYLAB controller TCU3
6 Actuators
S Fast-running actuator (3 s)
SD Fast-running actuator (3 s), with digital communication interface (TROX HPD)
7 Equipment function
Single operation
SC Supply air controller
8 External volume flow rate setting
E0 Voltage signal 0 – 10 V DC
E2 Voltage signal 2 – 10 V DC
2P Switch contacts (provided by others) for 2 switching steps
3P Switch contacts (provided by others) for 3 switching steps
F Volume flow rate constant value, without signalling
9 Expansion modules
Option 1: Power supply
No entry required: 24 V AC/DC
T EM-TRF for 230 V AC
U EM-TRF-USV for 230 V AC, provides uninterruptible power supply (UPS)
Option 2: Digital communication interface
No entry required: None
B EM-BAC-MOD-01 for BACnet MS/TP
M EM-BAC-MOD-01 for Modbus RTU
I EM-IP for BACnet/IP, Modbus/IP and web server
R EM-IP with real time clock
Option 3: Automatic zero point correction
No entry required: None
Z EM-AUTOZERO Solenoid valve for automatic zero point correction
11 Operating values for factory setting
Volume flow rate [m³/h or l/s]
Depending on external volume flow rate setting
E0, E2: qᵥmin/qᵥmax
2P: qᵥ1/qᵥ2
3P: qᵥ1/qᵥ2 /qᵥ3
F: qᵥ1
Order example: TVZ/315/ELAB/S/SC/F/2800 m³/hNominal size | 315 mm |
Attachments (control components) | EASYLAB controller TCU3 |
Actuator | Fast-running actuator (3 s) |
Equipment function | Supply air controller |
External volume flow rate setting | Volume flow rate constant value |
Operating value | qᵥ1 = 2800 m³/h |